H Cr h

Appendix A NOTICE OF VIOLATION Consumers Power Company Docket No. 50-329 Docket No. 50-330 Based on the inspection conducted on July 8-10, 1980, it appears that certain l

'of your activities were in noncompliance with NRC requirements, as noted below.

This item is an infraction, 10 CFR 50, Appendix B, Criterion IV, states, in part, that, " Measures shall be established to assure that applicable regulatory requirements, design j

bases, and other requirements which are necessary to assure adequate quality l

are suitable included or referenced in the documents for procurement of material, equipment, and services.

i l

Consumers Power Company Quality Assurance Program Policy No. 4, Revision 9, I

states, in part that, "During design and construction, and during the opera-tions phase including the Palisades SGRP and major modifications; these reviews are accomplished to assure that Consumers Power Company procurement l

documents contcin or reference provisions such as the following:

Basic technical requirements including.'.rawings, specifications, codes, a.

i and standards with applicable revision data, test and inspection require-ments, and special requirements, such as for designing, fabricating, "

j cleaning, erecting, packaging, handling, shipping, and storage.

Bechtel Corporation Welding Standard WFMC-1, Revision 8, dated January 4, 1971, " Welding Filler Material Control Procedure Specification" paragraph l

2.1, states, in part, that, "

.. Welding filler material ordering infor-mation shall include the appropriate requirements of the job engineering l

. specification, the applicable Code, and this procedure specification..."

l l

Contrary to the above, on July 10, 1980, the inspector establ..

_d Bechtel l

Purchase Order No. 7220-F-5780, dated November 2, 1973 for 60,000 lbs. of j.

E7018 electrodes did not specify the applicable code.

l

~ 8009150 /97

.-