Forwards IE Info Notice 80-31, Maloperation of Gould-Brown Boveri 480 Volt Type K-600S & K-DON 600S Circuit Breakers. No Written Response Required
ML19344F118
Person / Time
Site: Fort Saint Vrain 
Issue date: 08/27/1980
From: Seyfrit K
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To: Millen K
PUBLIC SERVICE CO. OF COLORADO
References
NUDOCS 8009120433
Download: ML19344F118 (1)


Text

p bec to DAC:ADM:

v CENTRAL FILES

  1. jW87uy%

UNITED STATES.

POR:HQ --

y, NUCLEAR REGULATORY COMMISSION -

LPOR N e REGloN IV.

-,a 15s i ' ' " ' I O'

611 RYAN PLAZA oRIVE. SulTE 1000 -

-3 ARLINGTON, TEXAS 76012 N$1C

'44 yce ;j' August-27, 1980

- Docket No. ' 50-267

w.

~

Public Service Coinpany of Colorado ATTN:

Mr. C. K. Millen Senior Vice President

.P. 0.- Box 840 Denver, Colorado 80201 Gentlemen:

. This IE Information Notic.e is provided as a notification of a matter of possible safety significance.

It is expected that recipients will'reviw the information~ for possible applicabm ty to their f acility, and where applicable, consider' the recommended action.

If you have questions regarding this matter, please contact the director of this office.

Sincerely, WS %Y~hw Karl V. Seyfrit Director

Enclosures:

1.

II Information Notice No.-80-31

2.. List of recently issued II Information Notices D,. W. Warambourg, Nuclear Production cc:

Manager-Fort St. Vrain Nuclear Station P. O. Box 368 Platteville,. Colorado -80651 L.- 3 rey, Manager, Quality Assurance

8009120433

SSINS No.: 6870 Accession No.

8006190040 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C. 20555 IE Information Notice 80-31 Date:

August 27, 1980 Page 1 of 2 MALOPERATION OF GOULD-BROWN BOVERI 480 VOLT-TYPE K-600S AND K-DON 600S CIRCUIT BREAKERS Description of Circumstances:

The Cincinnati Gas & Electric Company reported problems with the Gould-Brown Boveri Type K-600S and K-DON 600S circuit breakers used in 480 volt a.c.

circuits at the William H. Zimmer nuclear station.

The problem involved inadvertent circuit breaker closure during operation of the breaker charging springs when the breaker was racked out to the test position.

The problem resulted from the use of undersized bushings in the circuit breaker secondary close latches. The undersized bushings caused the secondary close latch to hang-up on the shunt trip device resulting in an inadvertent circuit breaker closure when the spring charging motor was energized.

The vendor has stated that the problem does not exist during normal ope:ations with the circuit breaker in the connected position.

Recommended Action for Licensees and Holders of Construction Permits:

All licensees of operating nuclear power reactors and holders of construction permits should be aware of the potential problems described above.

The vendor has stated that a small number of circuit breakers were assembled with under-sized secondary latch bushings between 1969 and 1977.

It is recommended that the following actions be taken:

(1) Determine if the subject circuit breakers are installed in any safety-related application at your facility.

The affected circuit breakers are manufactured by Gould-Brown Boveri and are types K-600S and K-DON 600S, 480-volt a.c. electrically operated, drawout type with static trip device.

(2)

If it is determined that your facility has the circuit breakers described in Item (1) above, perform the K-600S, K-DON 600S Field Test Procedure attached to this information notice (Gould-3rown Boveri I.B.-9.1.7-6 Issue F, Addendum 2, dated March (3)

If maloperation of the circuit br DUPLICATE DOCUMENT field test procedure described in action described in the attached Entire dcctunent previously 0.050.ach shim to the secondary entered into system under:

breaker).

ANO

$O0(nlQQO&O No. of pages:

M