This IE Information Notica is provided as a notification of a matter of possible safety significanca.
It is expected that recipiants will review the infor: nation for possible applicability to their fac4li ties, and where applicable, consider the taconsnandad action.
If you hava questions regarding this matter, please contact the director of this offica.
Sincerely, NAA >
M Karl V. Seyfric Director 1
F.nclosures:
l.
IE Information Notica No. 80-31:
j-2.
List of recently issued IE Information Noticas cr.:
James P. O'Hanlon,~ Plant Manager Arkansas Nucinar One.
P. O.-Box 608 Russellville, Arkansas-72801 8009120420
-)
,7
_ _,,. ~.
w
SSINS No.: 6870 Accession No.:j 8006190040 @ '*>@
UNITED STATES T
NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C. 20555 IE Information Notice 80-31 Date: August 27, 1980 Page 1 of 2 MALOPERATION OF GOULD-BROWN B0 VERI 480 VOLT-TYPE K-600S AND K-DON 600S CIRCUIT BREAKERS Description of Circumstances:
The Cincinnati Gas & Electric Company reported problems with the Gould-Brown Boveri Type K-600S and K-DON 600S circuit breakers used in 480 volt a.c.
circuits at the William H. Zimmer nuclear station.
The problem involved inadvertent circuit breaker closure during operation of the breaker charging springs when the breaker was racked out to the test position.
The problem resulted from the use of undersized bushings in the circuit breaker secondary close latches.
The undersized bushings caused the secondary close latch to hang-up on the shunt trip device resulting in an inadvertent circuit breaker closure when the spring charging motor was energized.
The vendor has stated that the problem does not exist during normal operations with the circuit breaker in the connected position.
Recommended Action for Licensees and Holders of Construction Permits:
All licensees of operating nuclear power reactors and holders of construction permits should be aware of the potential problems described above.
The vendor has stated that a small number of circuit breakers were assembled with under-sized secondary latch bushings between 1969 and 1977.
It is recommended that the following actions be taken:
(1) Determine if the subject circuit breakers are installed in any safety-related application at your facility.
The affected circuit breakers are manufactured by Gould-Brown Boveri and are types K-600S and K-DON 600s, 480-volt a.c. electrically operated, drawout type with static trip device.
(2)
If it is determined that your facility has the circuit breakers described in Item (1) above, perform the K-600S, K-DON 600S Field Test Procedure attached to this information notice (Gould-Brown Boveri I.B.-9.1.7-6 Issue F, Addendum 2, dated March 4, (3)
If maloperation of the circuit break DUPLICATE DOCUMENT field test procedttre described in It action described in the attached fie Entire document previously 0.050 inch shim to the secondary clo entered into system under:
breaker).
ANo 300619do//d No. of pages:
[