ML19344F010

From kanterella
Jump to navigation Jump to search
Forwards IE Info Notice 80-31, Maloperation of Gould-Brown Boveri 480 Volt Type K-600S & K-DON 600S Circuit Breakers. No Written Response Required
ML19344F010
Person / Time
Site: Grand Gulf  Entergy icon.png
Issue date: 08/27/1980
From: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To: Stampley N
MISSISSIPPI POWER & LIGHT CO.
References
NUDOCS 8009120260
Download: ML19344F010 (1)


Text

i

'o,,

UNITED STATES l'

NUCLEAR REGULATORY COMMISSION n

d

a REGION 11 ft 101 MAR!ETTA ST N.W..SulTE 3100 Y

ATLANTA, GEORGIA 303J3 g.....

AUG 2 71980 In Reply Refer To:

RII:JP0 50T416 ' )

~

'j 50-417 Mississippi Power and Light Company ATTN:

N. L. Stampley Vice President o Production P. O. Box 1640 Jackson, MS 39205 Gentlemen:

This Information Notice is provided as a notification of a matter of possible safety significance. It is expected that recipients will review the information for possible applicability to their facilities, and where applicable, consider the recommended action. If you have questions regarding this matter, please contact the director of this office.

Sincerely,

\\

w?o*

ames P. O'Reilly rector

Enclosures:

1.

IE Information Noti No. 80-31 2.

List of Recently Issu IE infa ma ion Notices cc w/ enc 1:

C. K. McCoy, Plant Manager 80091202 @

A

SSINS No.: 6870 Accession No.;g 8006190040 C >'J M f

s IN 80-31 7

i UNITED STATES i

NUCLEAR REGULATORY COMMISSION

{

OFFICE OF INSPECTION AND ENFORCEMENT l

WASHINGTON, D.C. 20555 August 27, 1980 l

IE Information Notice No. 80-31: MALOPERATION OF GOULD-BROWN BOVERI 480 VOLT-TYPE K-600S AND K-DON 600S CIRCUIT BREAKERS Description of Circumstances:

The Cincinnati Gas & Electric Company reported problems with the Gould-Brown Boveri Type K-600S and K-DON 600S circuit breakers used in 480 volt a.c.

circuits at the William H. Zimmer nuclear stations. The problem involved

]

inadvertent circuit breaker closure during operation of the breaker charging springs when the breaker was racked out to the test position.

1 The problem resulted from the use of undersized bushings in the circuit breaker l

secondary close latches. The undersized bushings caused the secondary close latch to hang-up on the shunt trip device resulting in an inadvertent circuit breaker closure when the spring charging motor was energized.

The vendor has stated that the problem does not exist during normal operations with the circuit breaker in the connected position.

Recommended Action for Licensees and Holders of Construction Permits:

All licensees of operating nuclear power reactors and holders of construction permits should be aware of the potential problems described above. The vendor has stated that a small number of circuit breakers were assembled with under-l sized secondary latch bushings between 1969 and 1977.

It is recommi tdd that the following actions be taken:

(1) Determine if the subject circuit breakers are installed in any safety-related application at your facility. The affected circuit breakers are manufactured by Gould-Brown Boveri and are types K-600S and K-DON 600S, 480-volt a.c. electrically operated, drawout type with static trip device.

(2) If it is determined that your facility has the circuit breakers described in Item (1) above, perform the K-600S, K-DON 600S Field Test Procedure l

l attached to this information notice (Gould-Brown Poveri I.B.-9.1.7-6 Issue F, Addendum 2, dated March 4, 1980).

(3) If maloperation of the circuit breaker occurs during performance of the field test procedure described in Item (2) above, perform the corrective action described in the attac 0.050 shim to the secondary el DUPLICATE DOCUMENT Entire document previously entered into system under:

AN L, EWal400 Lla No. of pages:

-._.