ML19344E963

From kanterella
Jump to navigation Jump to search
Forwards IE Info Notice 80-31, Maloperation of Gould-Brown Boveri 480 Volt Type K-600S & K-DON 600S Circuit Breakers. No Written Response Required
ML19344E963
Person / Time
Site: 05000363
Issue date: 08/27/1980
From: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Finfrock I
JERSEY CENTRAL POWER & LIGHT CO.
References
NUDOCS 8009120177
Download: ML19344E963 (1)


Text

P 1TC-a

[sc re tog #

8" 4'7, UNITED STATES NUCLEAR REGULATORY COMMISSION i

E REGION I o

631 PARK AVENUE g'+, +....',g

,o KING OF PRUSSIA,PENNSYl.VANIA TH06 August 27, 1980 Docket No. 50-363 Jersey Central Power and Light Company ATTN:

Mr. I. R. Finfrock, Jr.

Vice President 260 Cherry Hill Road Parsippany, New Jersey 07054 Gentlemen:

The enclosed IE Information Notice No. 80-31, "Maloperation of Gould-Brown Boveri Type 480 Volt Type K-600S and K-DON 600S Circuit Breakers," is forwarded to you for information.

No written response is required.

If you desire additional information regarding this matter, please contact this office.

Sincerely, C6 Boyce H. Grier Director

Enclosures:

1.

IE Information Notice No. 80-31 2.

List of Recently Issued IE Information Notices CONTACT:

S. D. Ebneter (215-337-5283) cc. w/encls:

M. K. Pastor, Project Manager l

t i

l

.8009120 177

SSINS No.: 6870 Accession No :

8006190040 IN 80-31 UNITED STATES NUCLEAR REGULATORY COMMISSION l

OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C. 20555 August 27, 1980 IE Information Notice No. 80-31:

MALOPERATION OF G0ULD-BROWN B0 VERI 480 VOLT-TYPE K-600S AND K-00N 6005 CIRCUIT BREAKERS Description of Circumstances:

The Cincinnati Gas & Electric Company reported problems with the Gould-Brown Boveri Type K-6005 and K-DON 600S circuit breakers used in 480 volt a.c.

circuits at the William H. Zimmer nuclear stations.

The problem involved inadvertent circuit breaker closure during operation of the breaker charging springs when the breaker was racked out to the test position.

l The problem resulted from the use of undersized bushings in the circuit breaker secondary close latches.

The undersized bushings caused the secondary close l

latch to hang-up on the shunt trip device resulting in an inadvertent circuit I

breaker closure when the spring charging motor was energized.

The vendor has stated that the problem does not exist during normal operations l

with the circuit breaker in the connected position.

Recommended Action for Licensees and Holders of Construction Permits:

All licensees of operating nuclear power reactors and holders of construction permits should be aware of the potential problems described above.

The vendor has stated that a small number of circuit breakers were assembled with under-sized secondary latch bushingt between 1969 and 1977.

It is recommended that i

the following actions be taken:

1 (1) Determine if the subject circuit breakers are installed in any safety-related application at your facility.

The affected circuit breakers are manufactured by Gould-Brown Boveri and are types K-6005 and K-DON 600S, 480-volt a.c. electrically operated, drawout type with static trip device.

l (2)

If it is determined that your facility has the circuit breakers described in Item (1) above, perform the K-600S, K-DON 6005 Field Test Procedure attached to this information notice (Gould-Brown Boveri I.B.-9.1.7-6 Issue F, Addendum 2, dated March 4, 1980).

(3)

If maloperation of the circuit bre DUPLICATE DOCUMENT field test procedure described in action described in the attached f Entire document previously 0.050 shim to the secondary close entered into system under:

t ANO 3MblhDOUO No. of pages:

8 1

_ _ _ _ _. _