T&s-AUBLIC SERVICE Companyof New Hampshere SEAsROOK STATION Engineering Office:

20 Turnpike Road Wootborough, MA 01541 August 4, 1980 SBN-130 Ref SBU-37748 SBU-38001 T.F. B 4.2.5 U.S. Nuclear Regulatory Commission Region I 631 Park Avenue King of Prussia, Pennsylvania 19406 Attention: Office of Inspection and Enforcement

Reference:

1.

Docket.No. 50-443 and 50-444 2.

NRC letter dated April 4, 1980 3.

IE Bulletin No.79-03A

Subject:

Longitudinal Weld Defects in ASME SA-312 Type 304 Stainless Steel Pipe

Dear Sir:

We have reviewed all of the SA-312 Type 304 fusion welded stainless steel pipe specified for use in safety related system for the Seabrook Project, and have performed pipe wall thickness calculations using the 85% of the maximum allowable stress criteria defined in IE Bulletin 79-03A.

Results of our review indicate that we have sufficient minimum pipe wall thickness.

W6 contacted the Commission for clarification of the IE Bulletin 79-03A criteria. We were informed that if the 85% of maximum allowable stress criteria is met, examination of the piping in the field by etching is not required.

If you require further information, please do not hesitate to contact us.

I l

ery truly yours, John DeVincentis Project Manager k

HEWatan cc: NRC Office of Inspection and Enforcement Divisien of Reactor Construction Inspection Washindton,D.C.

20555 m

8009110 d ? 8

.