ML19344D604

From kanterella
Jump to navigation Jump to search
Responds to IE Bulletin 80-03, Loss of Charcoal from Std Type II,Two-Inch Tray,Adsorber Cells. No Replacements Necessary Due to Damage to or Corrosion of Engineered Safety Feature Filters
ML19344D604
Person / Time
Site: Haddam Neck File:Connecticut Yankee Atomic Power Co icon.png
Issue date: 03/24/1980
From: Counsil W, Fee W
CONNECTICUT YANKEE ATOMIC POWER CO.
To: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML19344D605 List:
References
IEB-80-03, IEB-80-3, NUDOCS 8004250132
Download: ML19344D604 (5)


Text

m 0

0 VL CONNECTICUT YAN K EE ATOMIC POWER COMPANY BERLIN, CONNECTICUT P.O. BOX 270 H ARTFORD. CONNECTICUT e6101 Ta t s enom e 203-666 6911 Mareh 24, 1980 Docket No. 50-213 Mr. Boyce H. Grier, Director Region 1 Office of Inspection and Enforcement U. 3. Nuclear Regulatory Commission 631 Park Avenue King of Prussia, PA 19h06

Reference:

(1)

B. H. Grier letter to W. G. Counsil dated February 6,1980, transmitting I&E Bulletin No. 80-03 Gentlemen:

Haddam Neck Plant Response to I&E Bulletin No. 80-03 In accordance with Reference (1), Connecticut Yankee Atomic Power Company (CYAPCO) has performed a review of the design of, (1) the charcoal adsorber cells used in the Emergency Safeguard Feature '

-I filtration systems, and (2) the systems which contribute to the "as as reasonably achievable" design criteria of 10CFR50, Appendix I.

This review us not revealed any cells of the riveted type design described in the above reference.

A visual inspection of all the subject filters except the ESP filters was recently conducted in accordance with Reference (1). The ESF filters (Contain-ment Air Recirculation Fan) were previously inspected during the last refueling outage, in March,1979 A compilation of the results, any subsequent actions taken, and a brief description of the inspection are presented in the attached table.

During the 1979 refueling outage, 40 filters were added to three of the four ESF charcoal filter banks, to upgrade to the latest LOCA dose analysis. At that time, every existing ESF filter was inspected for signs of damage or corrosion. The result was that no replacements were necessary for damage or corrosion. Also, during the past two years, 295 out of 480 filters, total, were replaced in the four separate ESF charcoal filter banks. All replacement filters are inspected by the manufacturer or by the manufacturer's refilling service, and receive an additional inspection at the site for damage upon installation.

8004250 g37

We trust you find this information satisfactory to disposition the Reference (1)

I concerns. We remain available should the Staff require clarification of any of the above information.

Very truly yours, j

i CONNECTICUT YANKEE ATOMIC POWER COMPANY j

l 9

9 W. G. 05unsil I

Vice President By:

W. F. Fee

-f Vice President i

Attachments r

i (1) Integrity Inspection of Charcoal Adsorber Filters.

j (2) Operations and Maintenance Manual, Ventilation Filter Assemblies for i

Haddam Neck Plant of Connecticut Yankee Atomic Power Company and Northeast Utilities, Designed and Manufactured by CVI Corporation.

{

(3) Connecticut Yankee.Special Maintenance Procedure, SPL 10 7-5,

" Containment Air Recirculation Fans - Installation of Additional Charcoal Filters PDCR #299".

r

+

f I

l e

1 A

~,

INTEGRITY INSPECTION dF CHARCOAL ADSORBER FILTERS Fan / Filter Name Type of Cells Observed Cell Condition (l)

Construction No. Inspected

' Spent Fuel Pool Mine Safety Appliance No Degradation Welded 2 out of 12 Type II Cell No Further Action Ventilation and CVI Division of Penwalt No Degradation Welded All Purge Fan Filter Bulk Type With 2" Beds No Further Action Containment Air Mine Safety Appliance No Degradation Welded All

' Recirculation (2)

Type II Cell and NUCON No Further Action Type II Cell with 2" Beds (1) Inspected for the following conditions and number of cells exhibited condition:

1

~

a) Cracked velds b) Damaged Screens c) Signs of rust or other chemical deposits d) ' Signs of charcoal leaks e) Loose, broken, or missing rivets or other cell fasteners f) Damaged Seal g) Channeling (2) Inspected during March 1979 Refueling Outage.

1 n-w

-r-----

-%--r-.--em

- - -, -T---

y,-

y s

--s--

y---4.

em-,.-m--

9 -

et

-w--

g,,

g-g-

,de-p-

re-, - -

-.9-,.

--,eo

.g g

OPERATIONS AND MAINTENANCE MANUAL VENTILATION FILTER ASSEMBLIES FOR HADDAM NECK PLANT OF THE CONNECTICUT YANKEE ATOMIC POWER AND

~

' NORTHEAST UTILITIES SERVICE CO.

DESIGNED AND MANUFACTURED BY CVI CORPORATION P. O. BOX 2138 COLUMBUS, OHIO 43216 A SUBSIDIARY OF PENNWALT CORPORATION REFERENCE STONE & WEBSTER P.O. NO. WL-446 CVI W. O. A911

B.

HEPA Filters The IIEPA filters furnished are a nominal 24 x 24 x 11-1/2 in. size. They have 14 gage chromized steel frames, waterproof, glass fiber media, and do not have separators.

The media is protected by a wire mesh face guard. The filters supplied are in accordance with the requirements of AEC Health and Safety Bulletin 212 and UL-586 Each filter is tested to verify an efficiency of 99. 9% for 0.3 micron DOP particles at rated flow and at 20% of rated flow. The filter can operate at temperatures up to 250*F.

C.

Carbon Adsorber Bank (HECAD)

M The charcoal adsorber bank supplied is the CVI, HECA o

design. This bank features all welded constsuction and the elimination of all elastomer seals. This eliminates 4

the possibilities of By-Pass through conventionally gas-keted areas and through fastener holes in the filter frame.

Charcoal is replaced without violation of filter assembly, and without manhandling of cells inside the housing.

D.

Test Ports Di-octyl pthalate (DOP) injection points are provided in the access doors.

-- - -- --