Notice of Violation from Insp on 800916-17 & 1007-10
ML19343B543
Person / Time
Site: Waterford 
Issue date: 10/30/1980
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To:
Shared Package
ML19343B530 List:
References
50-382-80-26, NUDOCS 8012240177
Download: ML19343B543 (1)


Text

(

Docket No. 50.382/80-26 Appendix A NOTICE OF VIOLATION Based on the results of the NRC inspection conducted during the period October 7-10, 1980, it appears that certain of your activities were not conducted in full compliance with the conditions of your NRC Construction Permit No. CPPR-103 as indicated below:

Failure to Follow Procedures Relative to the Instal ation of Safety-Related Tubing Assemblies Ci-itiedon V'of"AppEndit B:t'o'10 'CFR '50 reqnires that activit'ies *

^

affecting quality shall be prescribed by documented instructions, procedures,.or drawings of a type 4.,ropriate to the circumstances, and shall be accomplished in accorosace with these instructions, procedures, or drawings.

The Mercury Company Procedure SP-656, " Fabrication of Local Instru-ment Piping and Tubing Assemblies," Revision 3, dated November 15, 1978, paragraph 6.3.7 states, " Plug all open ended valves with plastic caps or. equal.",

Contrary to the above:

On October 9,1980, during the IE inspector's tracking of instrument sensor tubing runs, the IE inspector observed six installed 1/2 inch needle valves that were open and unprotected. Two of these valves were identified as safety-related valves (Item 3 on Mercury Company Drawing 151-T-014-C, Rev. 0) at the 46 foot elevation in the Reactor Containment Building.

This is an infraction.

r 8