J ADMINISTRATIVE CONTROLS A health physics qualified individual (i.e., qualified in c.
radiation protection procedures) with a radiation cose rate monitoring device who is.* esp nsible for providing positive contr:1 over the activities within the area and wno will perform radiatica surveillance a :ne frequency specified in the Rwp.
4.hesurveillancefrequencywillbeestablishedbythePlan:
ealth Physicist.
The above precedure shall also apply to each high radiation area in which
.he intens1:y o radiation is greater tnan 1000 nrem/hr.
In adcition locked doors shall be provided to prevent unauthori:ed entry into suc[1 a eas ag the key sh'all be maintained under the administrative con:r:1 cf
...e shf.. superviser en duty and/or the Plan: Health Physicist.
6.13 ENVIRONMENTAL OUALIFICATION A.
Sy no later than June 30, 1982 all safety-related electrical equi;nent
.in the faGIity sha,11 be quali'fied fu accordance with the previsions of; Division.af Operating Reactors " Guidelines for Evaluating Environmental ~
Qualification of Class IE Electrical Equipment in Ope ating Rea'etors" (DOR Guidelinesh or, NUP.EG-0538 " Interim Staff Position on Environmental
~,
Qualifir tion of Safety-Related Electrical Equipment". December 1979.
~~
Copies of these documents r.re attached to Order for Modification of License DPR-3 dated October 24, 1980.
I S.
By.no later than Dece=ber 1,1980, comp 1ete and auditible records must be available and maintained at a central location which describe the D
envirerrnental qualification. method used for all safety-r' elated G.
electrical equipnent in sufficient detail to document the degree of co=pliance with the DDR Guidelines or NUREG-05BS. Thereafter, such records should be updated and maintained curren as equipmtnt is j
replaced, further tened, or otherwise further qualified.
li n
l!
lI 16 I!
l!
l D**D
- I) 3'Yh l
o.J
. J
. A frt=
o 6-24
~
l Order dated October 24, 1980 7 ' 4ep AG Db9b
~
a
~
~
nn..-
s
A0 MINIS 7 ATION CCNTROLS g.
Records of training and qualification fer current members of the plant staff.
h.
Rec:rds of in-service inspections perf =ed pursuant :: these Technical Specifications.
i.
Records of Quality Assurance acti,vities required by the QA Manual.
J.
Records of reviews performed for changes made :: precedures or equipment er reviews of tests and experiments pursuant to 10 CFR 50.5g.
k.
Rec:rds of meetings of the p0R0 and the NSAR Comittee.
1.
Re:erds for 'i.svirermental cualificati.es */r.ich are eevered under the previsior.s of paragraoh S.13 I
-6.11 RA !AT!CN ?ROTECTICN PROGRAM Frecedures f r perscnnel radiatica pr: ection shall be precared ::nsisten:
with requirements of 10 0.:R par: 20 and shall be a:pr:ved, maintained and adhere! :: for all cpera:icns involving perscnnel racia-icn exposures.
6.12 MIGM R!.0!ATION AREA 5.12.1 Paragraph 20.203 " Caution signs, labels, signals, and c:ntrols."
In lieu of the "c:ntrol device" or " alar = signal" recuired by :aragra:n
~ 20.203(c)(2), eacn high radia icn a'rea in wnich the intensity of racia-tien is 1000 cre:/hr er less shall be barricaced and cens:icu:usly posted as a high radia:icn area and entrance theret scall be c:ntrolled by requiring issuance cf a Radiation Work Permit.' An indivicual er grcu:
of individuals permitted :: entar such areas shall be previced wita one
~
cr =:re of the f 11cwing:
a.
A radinien monit: ring device wnich continuously indicates the radiatica dose rate in the area.
b.
A radiatica =cnit: ring device which centinueusly integrates the radiation dese ra:e in :ne area and alar =s wnen a prese:
integrated dose is received. Entry int such areas with this
=cnit: ring devica may be made after the dose rate level in the area have been es ablished and persennel have been made knew-1ecgeable Of them.
= heal:n Fnysics persennel shall be exempt frc: the RWp. issuance requirement during the perfor:ance of : heir assigned radia-icn protection cu:ies, pr:-
viding they are fc11owing piant radia-ion Orc:ac:icn precedures for en ry into high radiation areas.
iA'mEE-ROWE 6-23 Avendmeni; No. 47, Order dated October 24, 1980 s-
,,,