ML19341B839
| ML19341B839 | |
| Person / Time | |
|---|---|
| Site: | Farley |
| Issue date: | 01/16/1981 |
| From: | James O'Reilly NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II) |
| To: | Mcdonald R ALABAMA POWER CO. |
| References | |
| NUDOCS 8102270908 | |
| Download: ML19341B839 (1) | |
Text
r N
.' [pm asog D
UNITED STATES
$5
- 7, NUCLEAR REGULATORY COMMISSION 5.I )
. E REGION i:
s o
101 MARIETTA sT., N.W., SUITE 3100 ATLANTA, GEORGI A 30303 J A N 161981 M}*
In Reply Refer To:
RII JEQ O ' ((f H./ k 0-348 h f k
[
0-_364 j
/
JAN 2 d 1981. ?
Alabama Power Company
... %,u..,,
ATTN:
R. P. McDonaid C
- 855'a' Vice President-Nuclear Generation
' b.
P. O. Box 2641
/
Birmingham, AL 35291 N
Gentlemen:
This Information Notice is provided as an early notification of a possibly significant matter.
It is expected that recipients will review the information for possible applicability to their facilities. No specific action or response is requested at this time.
If further NRC evaluations so indicate, an IE Circular or Bulletin will be issued to recommend or request specific licensee actions.
If you have questions regarding this matter, please contact the Director of the appropriate NRC Regional Of fice.
Sincerely,
,s
. e. -:
James P. '0'Rei'lly Director
Enclosures:
1.
IE Information Notice No. 81-01 2.
List of Recently issued IE Information Notices cc w/ enc 1:
W. O. Whitt, Executive Vice President l
F. L. Clayton, Jr., Senior Vice-President i
H. O. Thrash, Manager-Nuclear Generation O. D. Kingsley, Jr., Manager, Nuclear Engineering and Technical Services J. W. McGowan, Manager-Operations Quality Assurance W. G. Hairston, III, Plant Manager W. C.. Petty, Manager-Quality Assurance (Design and Construction)
R. E. Hollands, Jr., QA Supervisor 8410227 0@
Q J
m
e SSINS No.:
6835 Accession No.:
8011040254 mn o
g g
UNITED STATES 3J NUCLEAR REGULATORY COMMISSION
- W OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D. C.
20555 January 16, 1981 IE INFORMATION NOTICE NO. 81-01: FOSSIBLE FAILURES OF GENERAL ELECTRIC TYPE HFA RELAYS
Purpose:
The intent-of this Information Notice is to alert licensees and holders of construction permits of a potentially generic problem involving defective coil spools used in General Electric (GE) type HFA relays. Such defective relays were recently found at Turkey Point Unit 4 (Docket No. 50-250).
Description of Circumstances:
The defective coil spools are fabricated of either black or clear Lexan, a polycarbonate material that is susceptible to surface cracking when exposed to hydrocarbons.
The concern here is that such surface cracks could ultimately deteriorate to such a degree that relay actuation would be blocked by the resultant debris, thereby inhibiting a required safety function.
-Indications of the above mentioned cracks were recently detected on the RFA relays used to sequence the emergency loads on the diesel generators at Turkey Point Unit 4 upon a loss-of-coolant accident coincident with a loss of offsite power. After detecting the cracks, the spare coils in the storeroom were in-
-spected and, although these coils are new units, one was found to be cracked.
The possible failures of GE type HFA relays highlights two salient points:
. (1) HFA relays have had a long history of failures (e.g., GE has issued several Service Information Letters (SIL) ~ addressing these relays, the oldest one of which. dates back to 1973, and it is anticipated that GE will issue a new SIL in the near future addressing this new concern); (2) the cracking phenomena seems to be.similar to that experienced on the cam followers used on GE type l
SBM switches (e.g., these cam followers are fabricated of Lexan, and after I
their exposure to hydrocarbons during fabrication or during maintenance severe
(
- cracking resulted.
See IE Information Notice No. 80-13.for additional details.)
I
. The above information identifies means whereby the integrity of a major safety-related system can be~ jeopardized or compromised by the blocking of
(
relay actuation. - Accordingly, this Information Notice is provided as an early
-notification of a possibly.significant matter that is still under review by the NRC staff.
Recipients should, therefore, review the information for possible applicability to their. facilities.
Although.no specific action or j
' response is-requested at this time, further licensee actions may be requested j
'or required pending the outcome of the NRC staff evaluation.
-If you.have any question regarding this matter, please contact the director of I'
the_ appropriate NRC Regional Office.
(
m
IN 81-01 January 16, 1981 RECENTLY ISSUED IE INFORMATION NOTICES In fo rma tion Date of Notice No.
Subject Issue Issued to 81-01 Possible Failures of General 01/16/81 All Power reactor Electric Type HFA Relays facilities with an OL or CP 80-45 Potential Failure of 12/17/80 All BWR facilities BWR Backup Manual Scram with an OL or CP Capability 80-44 Actuation of ECCS in the 12/16/80 All PWR facilities Recirculation Mode While with an OL or CP in Hot Shutdown 80-43 Failures of the Continuous 12/5/80 All power reactor Water Level Monitor for facilities with OL the Scram Discharge Volume or CP at Dresden Unit No. 2 80-42 Effect of Radiation on 11/24/80 All power reactor Hydraulic Snubber Fluid facilities with OL or CP 80-41 Failure of Swing Check 11/10/80 All power reactor Valve in the Decay Heat facilities with an OL Removal System at Davis-or CP Besse Unit No. 1 80-40 Excessive Nitrogen Supply 11/10/80 All power reactor Pressure Actuates Safety-facilities with Relief Valve Operation to OL or CP Cause Reactor Depressur-ization 80-39 Malfunctions of Solenoid 10/31/80 All light water reactor Valves Manufactured By facilities with Valcor Engineering Corporation OLs or cps 80-38 Cracking in Charging Pump 10/30/80 All PWR facilities Casing Cladding with an OL or CP i