Final Deficiency Rept,Originally Submitted 800620,re Out of Tolerance Conditions on Major Bolt Diameters & Minor Nut Diameters Supplied by Industrial Mechanic,Inc.Analysis by A/E Indicates No Predicted Reduction in Design Capacity
ML19340E439
Person / Time
Site: Callaway Ameren icon.png
Issue date: 01/07/1981
From: Bryan J
UNION ELECTRIC CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
10CFR-050.55E, 10CFR-50.55E, ULNRC-408, NUDOCS 8101140505
Download: ML19340E439 (2)


Text

...

UNION ELEC'i*RIC COMPANY 1901 GRATIOT STREET er. covi ui..ov i

"":* ^ff,"1."'

.m,.

January 7, 1981 Mr. James G.

Keppler, Director Region III Office of Inspection & Enforcement a

3 US Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, IL 60137 ULNRC-408

Dear Mr. Keppler:

FINAL 10CFR50.55(e) REPORT INDUSTRIAL MECHANICS, INC. - ANCHOR BOLTS AND NUTS CALLAWAY UNIT 1 On Friday, June 20, 1980; we provided Mr. H. M. Wescott verbal notification of a 10CFR50.55(e) report regarding out of tolerance conditions on major bolt diameters and minor nut diameters for material supplied by Industrial Mechanics, Inc.

' In our letter ULNRC-366, dated July 18, 1980 we requested that the submittal date of our final report on this matter be extended to December 1, 1980.

In our letter ULNRC-401, dated November 28, 1980 we

' requested that the submittal date of our final report be extended to January 9, 1981 due to the field inspection program and evaluation of data having taken longer than estimated.

The analysis of data"from the field inspection program has been completed by our A/E, Bechtel and has been submitted to us in a report.

The report indicates that of the nuts and bolts checked, not a single anchor (nut-bolt combination) was found for which the predicted fa~ilure mode is in the threads.

This results in no predicted reduction in design' capacity.

We have concluded that'had the out-of-tolerance nuts and bolts remained undetected there would have been no impact on the health and safety of the public and we no longer consider this matter significant.

gpIT

?

}

no129

. _ - - -. =

o 2-January 7, 1981 Mr. Gaston Fiorelli A copy of the Bechtel report is available at the Callaway jobsite for your review.

ry truly yours, s

i

  1. t John ryan DBS/jds cc:

H. Wescott B. H. Grier Victor Stello, J.

W. A. Hansen (Callaway Resident Inspector)

Missouri Public Service Commission

~