ML19340C857

From kanterella
Jump to navigation Jump to search
Forwards IE Info Notice 80-39, Malfunction of Solenoid Valves Mfg by Valcor Engineering Corp. No Written Response Is Required
ML19340C857
Person / Time
Site: River Bend  
Issue date: 10/31/1980
From: Seyfrit K
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To: Draper E
GULF STATES UTILITIES CO.
References
NUDOCS 8012170826
Download: ML19340C857 (1)


Text

?S

'"*N.

UNITED STATES i

NUCLEAR REGULATORY COMMISSION t

REGION IV

- /,#

611 RYAN PLAZA DRP/E SUITE 1000

'....8 ARLINGTON. TEXAS 76011 October 31, 1980 In Reply Refer To:

my RIV ri C

Docket Nos.

50-458/IE Information Notice No. 80-39 50-459/IE Information Notice No. 80-39 Q

[?,i N

id W5 Y$

mg;o

_a e,

d-i Gulf States Utilities m

"Q1 Attn:

Dr. E. Linn Draper, Jr.

O c

Vice President - Technology C

N Post Office Box 2951 Beaumont, Texas 77704 Gentlemen:

The enclosed IE Information Notice provides early notification of an event that may have safety significance.

Accordingly, you should review the Information Notice for possible applicability to your facilities.

No specific action or response is requested at this time; however, contingent upon the results of further staff evaluation, a Bulletin or Circular recom-mending or requesting specific licensee actions may be issued.

If you have questions regarding this matter, please contact me.

Sincerely, r

~,

'I-G -): :

Karl V. Seyfrit. //

I Director

Enclosures:

1.

IE Infor=ation Notice No. 80-39 2.

List of Recently issued IE Information Notices 8 012170 WLC

l SSINS No.-

6835 l

Accession No.:

8008220245 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D. C. 20555 IE Information Notice No. 80-39 Date: October 31, 1980 Page 1 of 1 MALFUNCTION OF SOLEN 0ID VALVES MA.WFACTURED BY VALCOR ENGINEERING CORPORATION PLTPOSE:

The intent of this Information Notice is to alert holders of construction permits and operating licenses for nuclear power plants of a potentially generic problem involving the malfunctioning of certain solenoid valves manu-factured by the Valcor Engineering Corporation (Valcor).

The solenoid valves so involved are designated as Valcor Valve Model No. V52600-554-1.

Valcor has informed us that these valves have only been supplied to the McGuire facility; however, since these valves were substituted for solenoid valves of another manufacturer that did not meet the requirements of IE Bulletin No. 79-01 and its amendments, licensees and holders of construction permits should uake into account the problem identified in this Information Notice prior to making any similar substitution.

l BACKGROUND:

By TWX dated June 27, 1980, Valcor submitted a preliminary 10 CFR Part 21 Report addressing the malfunctioning of Valcor solenoid valves at the McGuire facility.

The malfunctioning valves have been identified as Valcor Valve Model No. V52600-554-1.

This TWX was subsequently followed by a letter dated July 3, 1980, transmitting a more detailed Part 21 Report entitled, " Quality Assurance Report", a copy of which is attached hereto as Enclosure No. 1.

In brief, the malfun.. tion appears to be an intermittent type wherein the valve fails to cycle from OPEN to CLOSE to OPEN immediately after a sustained period of operation in the energized (OPEN) mode.

Although the valves are rated for

" continuous operation", Valcor contends that the valves were not designed to meet the operating conditions requiring the immediate cycling from OPEN to CLOSE to OPEN after a sustained period of continuous energization.

A major source of the problem, therefore, may be a misunderstanding of the term July 14, 1980 to Duke Power Company, this matter entitled, " Outline -

l y of which is attached hereto as 1

DUPLICATE DOCUMENT Entire document previously entered into system under:

0&h 0hhhCY' G ANO No. of pages:

7

.