ML19340C841

From kanterella
Jump to navigation Jump to search
Forwards IE Info Notice 80-37, Containment Cooler Leaks & Reactor Cavity Flooding at Indian Point Unit 2. No Written Response Required
ML19340C841
Person / Time
Site: Columbia, Washington Public Power Supply System, Satsop  
Issue date: 10/24/1980
From: Engelken R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
To: Ferguson R
WASHINGTON PUBLIC POWER SUPPLY SYSTEM
References
NUDOCS 8012170680
Download: ML19340C841 (1)


Text

.

T/C

~

p reo ug[o, UNITED STATES i

E NUCLEAR REGULATORY COMMISSION o

~

,E REGION V o,

1990 N. CALIFORNI A BOULEVARD

[g SUITE 202, WALNUT CREEK PLAZA 4,,,a WALNUT CR EEK. CALIFORNIA 94536 1

GCT 2 "O

Docket Nos. 50-397, 50-460, 50-508, 50-509, 50 G13 i

Washington Public Power Supply System P. O. Box 968 3000 George Washington Way Richland, Washington 99352 i

Attention: Mr. R. L. Ferguson Managing Director Gentlemen:

i This Information Notice is being forwarded to you for information. No written response to this Information Notice is required.

If you have any questions related to the subject, please contact this office.

Sincerely, Ym,4 R. H. Engelken Director

Enclosures:

1. ~ IE Information Notice flo. 80-37 2.

List of Recently Issued Information Notices cc w/ enclosures:

M. E. Witherspoon W. C. Bibb J. P. Thomas D. E. Dobson G. C. Sorensen 4

i.

i l

80 12 yyo C Pc

SSINS tio.: 6835 Accession No.:

8008220249 UNITED STATES IN 80-37 NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND. ENFORCEMENT h

UASHItiGTON, D.C.

20555

)

October 24, 1980 IE Information Motice No. 80-37:

CONTAINMEtiT COOLER LEAKS AND REACTOR CAVITY FLOODING AT INDIAN POINT UNIT 2 Discriotion of Circumstances:

This Notice contains information regarding multiple service water leaks into containment with resulting damage to reactor instrumentation and potential damage to the reactor pressure vessel.

Upon-containment entry on October 17, 1980 at Indian Point Unit 2, to repair a malfunctioning power range nuclear detector, it was discovered that a significant amount of water was collected (approximately 100,000 gal) on the containment floor, in the containment sumps, and in the cavity under the reactor pressure vessel (RPV).

This collected water probably caund the detector malfunction, and the water in the cavity under the RPV is believed +o have been deep enough to wet several feet of the pressure vessel lower head, caesing an unanalyzed thermal stress condition of potential safety significance.

This condition resulted from the following combination of conditions:

(1) Both containment sump pumps were inoperable, one due to blown fuses from an unknown cause and the other due to binding of its controlling float;.(2) The two containment sump level indicating lights which would indicate increasing

~

Wdi.sr level over the water level range present in the containment were stuck (on) and nay have been for several days, leaving the operator with no operable instrumentation to measure water level in the containment; (3) The moisture level indicators in the containment did not indicate high moisture levels, apparently because they are designed to detect pressurizri hot water or steam leaks (i.e., a LOCA), and are not sensitive to the lower airborne moisture levels resulting from relatively small cold water leaks; (4) The hold-up tanks which ultimately receive water pumped from the containment sump also receive Unit 1 process water, lab drain water, etc. These other water sources masked the effect of cessation of water flows from the Unit 2 sump;-(5)- There were significant, multiple service water leaks frcm the containment fan cooling units directly cannot be detected by supply inventory losses since the supply system (ge, whic onto the containment floor. These coolers have a history of such leaka l

service water system) is not a closed system; (6) The two' submersible pumps in the cavity under the Peactor pressure Vessel were ineffective since they pump onto the con-tainment floor for ultimate removal by the (inoperable) containment sump pumps.

There is no water level instrumentation in the cavity under the RPV, nor was there any indication outside the containment when these pumps are running.

The licensee has installed redundant sump level annunciated alarms in the control room and has installed an annunciated alarm in the control room to indicate if either submersible pump in the reactor cavity activates. The licensee has also repaired the service water leaks, installed guide bushings on the sump pump control floats to prevent their binding, and has repaired the containment sump water level indicators.

t

It! 80-37 October 24, 1980 Page 2 of 2 The licensee plans in the lencer t -n to replace the containment fan unit cooling coils.

It is anticipated that results of a ct1tinuino NRC investication into this incident will result in issuance of an IE Bulletin and/or an NRR Generic Letter in the near future which will reconnend or recuire specific licensees and aoplicant actions.

In the interim, we reconmend that all licensee ascertain that the potential does not exist for undetected water accumulation in the containment.

This Infornation Notice is crovided to inforn licensees of a possibly significat matter.

No written resconse to this Infornation f:otice is reouired.

-w

IN 30-37 October 24, 1980 RECENTLY ISSUED IE INF0PMATION NOTICES Information Date of Notice No.

Sub.iect Issue Issued to 80-36 Failure of steam 10/10/80 All nuclear power cenerator support bolting reactor facilities holding OLs or cps 80-35 Leaking and dislodged 10/10/80 All categories G and Iodine-124 implant seeds G1 medical licensees 80-34 Roron dilution of reactor 9/26/80 All pressurized water ccolant during steam reactor facilities generator decontamination holding power reactor OLs 80-33 Deternination of teletherapy 9/15/80 All teletherapy tirer accuracy (G3) licensees 80-32 Clarification of certain 8/17'80 All NRC and agreement recuirenents for Exclu-state licensees sive-use shipments of radioactive materials 80-31 Maloperation of Gould-8/27/80 All light water reactor Crown Boveri Type 480 facilities holding OLs valt tyoe K-600S and or cps M-C0" 600S circuit breakers 80-30 Potential for unaccept-3/19/80 All boiling water reactor able interaction between facilities holding power the control rod drive scram reactor OLs or cps.

function and non-essential control air at certain GE EUR facilities 80-29 Broken studs on Terry 3/7/80 All light water reactor turbine steam inlet facilities holding flange power reactor OLs or cps

  • Supplement to Notification of 7/29/80 All holders of eactor 80-06 significant events at and near-tern OL operating power reactor applicants facilities 80-28 Prompt reporting of 6/13/80 All applicants for and required information holders of nuclear power to NRC reactor cps
  • Operating Licenses or Construction Permits