Interim Deficiency Rept Originally Reported on 801014 Re Embedded Plates W/O Heat Traceability.Number of Embedded Plates W/O Traceability Will Be Determined.Affected Plates to Be Chipped Out of Auxiliary Bldg Walls
ML19339C528
Person / Time
Site: Phipps Bend 
Issue date: 11/13/1980
From: Mills L
TENNESSEE VALLEY AUTHORITY
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
10CFR-050.55E, 10CFR-50.55E, PBNP-156, NUDOCS 8011180551
Download: ML19339C528 (2)


Text

,,

~-

400 Chestnut Street 7twer II November 13, 1980

~

l l

Mr. James P. O'Reilly, Director i

l Office of Inspection and Enforcement U.S. Nuclear Regulatory Cemnission Region II - Suite 3100 101 Marietta Street Atlanta, Georgia 30303

Dear Mr. O'Reilly:

PHIPPS BEND MJCLEAR PLANT UNIT 1 - REPORTABLE DEFICIENCY - EMBEDDED PLATES WITHOUT HEAT TRACEABILITY (NCR PIMP 156)

Initial notification of the subject deficiency was made to NBC-OIE Region II, Inspector R. W. Wright on October 14, 1980. In empliance with paragradt 50.55(e) of 10 CFR Part 50, we are enclosing the first interim report on the subject deficiency. Tennessee Valley Authority anticipates transmitting the final report on or before January 12, 1981. If you have any questions regarding this subject, please call Jim Deer at FTS 857-2014.

Very truly yours, TENNESSEE VALLEY AUTHORITY L. M. Mills, Manager Nuclear Regulation and Safety Ehclosure cc: Mr. Victor Stello, Director (Enclosure)

Office of Inspection and Enforcement U.S. reclear Regulatory Cannission Washington, DC 20555 30/7 S

lll son 18o 5{

i An Ecual opportunity Employer

.e DCIOSURE PHIPPS BDO WCLEAR PLANT UNIT 1 DG3EDDED PIATES WI'IH0tTP HEAT TRACEABILITY 10 CFR 50.55(e) REPORP NO.1 (INTERIM)

On October 14,1980, 'IVA informed NBC-OIE Region II, Inspector R. W. Wright of a condition involving the difficulty in tracing heat numbers on embedded plates in the auxiliary building of the Phipps Bend Nuclear Plant unit 1.

m is is the first interim report on the subject reportable deficiency. '1VA anticipates transmitting the final report on or before January 12, 1981.

Descriotion of Deficiency Enbedded plates used to connect and strengthen supports for systems in the auxiliary building are stamped with heat numbers which are not currently on Phipps bend's list of acceptable material heat numbers. Bis anmaly was detected during a routine inspection. Because the heat numbers of the subject plates are not on Ibipps Bend's heat lists, the cmpositien of these plates is not now known. We composition of ~ these plates must be determined in order to establish the adequacy of the plates in fulfilling their intended purpose.

Interim Progress At present, TVA is in the process of determining how many plates afe without heat traceability. Plates representative of those with nontraceable heat numbers will be chipped out of the auxiliary building walls. Wese " samples" will be sent to Singleton Laboratories and their emposition determined.

N 1