ML19339C062

From kanterella
Jump to navigation Jump to search
Responds to IE Bulletin 80-16, Potential Misapplication of Rosemount,Inc,Models 1151 & 1152 Pressure Transmitters W/ Either a or D Output Codes. Transmitters Cannot Be Exposed to Input Pressures That Result in Anomalous Output Signals
ML19339C062
Person / Time
Site: Davis Besse Cleveland Electric icon.png
Issue date: 10/24/1980
From: Crouse R
TOLEDO EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
1-168, IEB-80-16, NUDOCS 8011170411
Download: ML19339C062 (1)


Text

T/6 Docket No. 50-346

/Z*\\

License No. NPF-3 W-C.]

TOLEDO Se ial No. 1-168

'Tx2EEE) lei [)rd October 24, 1980 Ac,4w; P cuaa V.te h e et

.Y SL id I[O '?h A d2l Mr. James Keppler Regional Director, Region III Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137

Dear Mr. Keppler:

This is a response to IE Bulletin 80-16 concerning " Potential Misapplication of Rosemount, Inc., Models 1151 and 1152 Pressure Transmitters with either "A" or "D" Output Codes."

Toledo Edison has determined that twelve such transmitters have been installed at the Davis-Besse Nuclear Power Station Unit 1.

All of these transmitters are utilized in safety related applications. These include:

a) Eight Model ll52DPSA92PB transmitters in the Steam and Feedwater Rupture Control System (Nos. LTSP9A6 to A9 and LTSP9B6 to B9).

b) Four Model ll52GP9A92T0010PB Reactor Coolant System pressure transmitters for the Reactor Protection System.

(Nos. PT RC2Al, 2A2, 2B1 and 2B2).

Toledo Edison's investigation has revealed that thcsc transmitters cannot be exposed to input pressures that could result in anomalous output signals during normal operation, anticipated transients or design basis accidents.

As a result, no corrective actions are required. This completed Toledo Edison's action on this Bulletin.

Very truly yours, 79-RPC/TJM/aa ec:

NRC Davis-Besse 1 Resident Inspector U.S. Nuclear Regulatory Commission Of fice of Inspection and Enforcement Division of Reactor Operations Inspection Washington, D.C.

20555 THE TOLEDO EDISON COMPANY EDISON PLAZA 300 MADISON AVENUE TOLEDO. OHIO 43652 801117 o ef//

OCT 2 9 000