?5C

],#* Y'%

UNITED STATES

[~

NUCLEAR REGULATORY COMMISSION

+*

REGION IV

[E 611 RYAN PLAZA oRIVE. SUITE 1000 h,

ARLINGTON. TEXAS 76011 October 22, 1980 fn Reply Refer To:

RIV Docket No. 50-498 50-499 Houston Lighting and Power Company ATTN: Mr. G. W. Oprea, Jr.

Executive Vice President Post Office Box 1700 Houston, Texas 77001 Gentlemen:

This confirms the discussion between Mr. D. G. Barker and Messrs. W. A. Crossman and H. S. Phillips of my staff relative to your letter (ST-HL-AE-562) to me, dated October 17, 1980, in regard to your request for additional AWS safety-related welding.

Specifically, with regard to your request to perform Category I (AWS D1.1) structural steel welding beyond the limits of the agreement described in our letter to you, dated October 3, 1980, we understand that:

1.

Your five commitments regarding AWS welding referenced in our letter to you, dated October 3,1980, remain in effect.

2. of your ST-HL-AE-562 letter describes a twelve week work plan for the fourth quarter 1980 relative to additional production welding on a limited basis.

The work plan covers the welding of structural steel for embeds up to 1-1/2 inch thickness in the fabrication shop while all other structural steel welding will be restricted to a thickness not to exceed 3/4 inch.

The continuation of your re-examination ind repair of previously completed AWS 3afety-related welding described in your letter (ST-HL-AE-555), dated October 2, 1980, is again identified in the twelve week work plan.

We concur with your plans to continue re-examination and repair of AWS welding as set forth in Attachment 1 of your letter.

We request that you inform this office sufficiently in advance of field welding involving greater than 3/4 inch thickness, so that we may review the procedures for controlling such work.

CERTIFIED MAIL RETURN RECEIPT REQUESTED e

80.1Jusofo 5 g

m

-r

.g.

Houston Lighting and Power Company. October 22, 1980 If your understanding of this matter is inconsistent with the above, please contact this office immediately.

Sincerely, f'

.-,Y

,/ /c.A:y %.c.,,y],,,

N K. V. Seyfrit Director

.My.d t

I s

l l

l 1

l I

o