{{#Wiki_filter:. (. ( UNITED STATES p g NUCLEAR REGULATORY COMMISSION -] g g CASHINGToN, C. C. 20Ss5 o, .f = % * *** * / q=lq-YANKEE A'IDMIC ELECTRIC COMPANY M _ ai=+eif DOCKET NO. 50-29 g+; - '.N...::..b.: YANKEE NUCLEAR POWER STATION (YANKEE-ROWE) !E - )pi: AMENDMENT TO FACILITY OPERATING LICENSE f Amendment No. 2A License No. DPR-3 =H 1. The Nuclear Regulatory Commission (the Commission) has found that: A. The application for amendment by Yankee Atomic Electric Company (the licensee) dated August 19, 1975, and. supplement dated March 15, 1976, complies with the standards and requirements of
==: the Atomic Energy Act of 1954, as amended (the Act), and the ce=_g Commission's rules and regulations set forth in 10 CFR Chapter I;
- l}
B. The facility will operate in conformity with the application, the provisions o.f the Act, and the rules and regulations of the Commission; 7-C. There is reasonable assurance (i) that the activities authorized [: by this amendment can be conducted without endangering the health and safety of the public and (ii) that such activities will be ...} conducted in compliance with the Commission's regulations; D. The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; 'l E. The receipt, possession, and use of source, byproduct, and special nuclear material as authori:ed by this license amendment will be in accordance with the Commission's regulations in 10 CFR Parts 30, 40, and 70, including 10 CFR Sections 30.33, 40.32, 70.23, and 70.31; and F. An environmental statement or negative declaration need not be = prepared in connection with the issuance of this amendment. ~
- p. w:1.
f9 i I 8011030[O2 O
( = 8 2. Accordingly, the license is amended by revising Paragraphs 2.A, 2.B, and 2.C and adding new Paragraphs 2.D and 2.E as follows. The license is also amended by a change to the Technical Specifications as indicated ~in the attachment to this license amendment. m= 2. A. Pursuant to Sectic1 104b of the Act and 10 CFR ~5 Part 50, "Licensir., of Preduction and Utilization E Facilities", to possess, use, and operate the facility at the designated location in accordance s with the procedures and limitations set forth in this license; B. Pursuant'to the Act and 10 CFR Part 70, to receive, possess, and use at any time special nuclear material as reactor fuel, in accordance with the limitations for storage and amounts required for reactor operation, as described in the Final ifa:ards Summary Report, as supplemented and amended. fg7 r .C. Pursuant te the Act and 10 CFR' Parts 30, 40, and 70 [ to receive, pos. :ss, and use at any time any byproduct, '~ source, and special nuclear material as sealed neutron sources for reactor startup, scaled sources for reactor instrumentation and radiation monitoring cquip-ment calibration, and as fission detectors in amounts as required; I. D. Pursuant to the Act and 10 CFR Parts 30, 40, and 70, to receive, possess, and use in amounts as required any byproduct, source, or special nuclear material without restriction to chemical or physical form, for sample analysis or instrument calibration or associated with radioactive apparatus or components; and E. Pursuant to the Act and 10 CFR Parts 30 and 70, to possess, but not separate, such byproduct and special nuclear materials as may be produced by the operation of the facility." = P M N em e P00R HOGiNAL
\\ 3. This license amendment is effective as of the date of its issuance. FOR EE NUCLEAR REGULATORY COE!ISSION i. m O i-C%.,. 4 3.e'- -- g.,.g t s. Robert A. Purple, Chief Operating Reactors Branch #1 Division of,0perating Reactors Attachne'nt: Changes to the Technical Specificatons Date of Issuance: April 26, 1976 I: k [ G 8
t _ ;.g n= Zf~,-[; =- ATTAOIMENT TO LICENSE AMENDMENT NO. 24 .;;[~
- = =...
FACILITY OPERATING LICENSE NO. DPR-3
- i
- .i.4 t.
- g.
=.3 3 DOCKET NO. 50-29 M.f.'.5. y==== ??: E-se. .: = lIU!
- ==
== Revise Appendix A as follows: Ih, ,.:::-l- ~ Remove page 18a and insert revised page 18a. -{:;. Add page 509:4 ^ " "l2":.. .5.w' = .. i.L'. ' 2:'*;:.L::^""
- '- :' 'n
e - - ~ ~, s_ ;, ~ j'J::: -t {.;' ';:.C :1 . :h.. e ~;.7? : ':=::. ~* T 2 ^:.; ;^
- -^~"
';2 2 : ~..., *
( (3) Solid Waste (a) The total a=ount of solid waste shipped (in cubic feet). - :=:. . (b) The total estinated radioactivity (in curies) involved. (c) Disposition including dA:.a and destination. .= y__. -a: c. Other Reports { T}E' (1) Annually: Results of required leak. tests.1erfor=ed on sources 5 if the tssts reveal the presence of 0.005 =icimeurie or more of removable contamination.
== b.. FOOTNOTES F ~ ~ j: = 1. A single sub=ittal may be cade for a cultiple unit sta:icn. The sub=1:tal should ce=bine those secticas that are coc=en to all units at the station. = 2. The ter: " forced reduction in power" is nor. ally defined in the electric l-- pcuer industry as the occurrence of a co=ponent failure or o:her condi:irn I which requires that the load on the unit be reduced for corree:ive actic:- N i==edia cif or up to and including the very nex: veckend.
- ote that routinc preventive taintenance, surveillence and calibra:ica ac:1vitics requiring pcver reductions are.not covered by this sectien.
3. The ter: " forced outage" is nor= ally defint!d in the electric power indus:ry as the occurrence of a ec=ponent f ilure or other cendition which requires :hst the unit be re=oved frc= service for corrective action 1_ cdiately or up to and including the very nex: veekend. 4 This tabulatien supple =ents the require = cuts of s20.407 of 10 CF?. Part 20. i-(. 18a Amendment No. 24 P002 M MMAL z
(. 509:4 Radicactive Source f.eak Tests - Licensed radioactive scaled sources shall bc Icak tested for contamination. Tests for Icakage and/or nr contamination shall be performed by the licensee or by other persons specifically authorized by the Commission o'r an agreement State as follows: [1...;=
- a. ~.. :
A. Each licensed scaled source except startup sources and fission detectors subject to core flux, containing radioactive =sterials, other than Hydrogen 3, with half-life greater than. thirty days and in any form other than gas shall bc tested. for Icahage and/or contamination at intervals not to exceed six months. In the absenes of a certificate frcm a transferor indicating that B. a leak test has been made within six months prior to the transfer, scaled sources shall not be put into use until tested. C. Startup sources shall be Icak tested within 31 days before being subjected to core flux and following any repair or maintenance. The Icakage test shall be capabic of detecting the presence of 0.005 microcuric of radioactive material on the test sample. If the test reveals the presence of 0.005 microcurie or core, of rc=ovable conta=ination, it shall inacdictcly be withdrawn from use, deconta=inated, and repaired, or be disposed of in accordance with Cc= mission regulations. F. Notwithstanding the periodic leak tests required by this Technical Specification, any scaled source is exempt from such Icak test when the source contains 100 microcuries or less of beta and/or gacma cmitting material or 5 microcuries or less of alpha emitting material.
- 1 u
i Amendment No. 24 . P9020AMsg}}