ML19338F151

From kanterella
Jump to navigation Jump to search
Forwards LER 80-034/03L-0
Date released: 12/18/2019 Download: ML19338F151


LER 80-034/03L-0:on 800905,during Normal Operation,Small Primary to Secondary Leak Developed from Steam Generator E24A.Caused by Flow Induced Vibration Crack in Tube 74-2. Tube Was Plugged & Unit Returned to Svc
ML19338F163
Person / Time
Site: Arkansas Nuclear 
Issue date: 10/01/1980
From: Shively C
ARKANSAS POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
Download: ML19338F163 (1)
Forwards LER 80-034/03L-0
ML19338F150
Person / Time
Site: Arkansas Nuclear 
Issue date: 10/01/1980
From: Trimble D
ARKANSAS POWER & LIGHT CO.
To: SEYFRIT K V
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
Download: ML19338F150 (1)