7h i

U S N R C R E m M ; :;

i cTLANT/.. Y ~,t.

Georgia Power Company Post Office Box 4545

^=n a. wa amo2 "O SEP 8 A10 : 12 Teieonone 404 s22eso Vogtle Proj.ect Southern Company Services, Inc.

Post Office Box 2625 Birmingharg Alabama 35202 Telephone PoS 870-6011 September 2, 1980 United States Nuclear Regulatory Commission

REFERENCE:

Office of Inspection and Enforcement H: JP0 Region II - Suite 3100 50-424 101 Marietta Street 50-425 Atlanta, GA 30303 File: X7BC24 Attention: Mr. James P. O'Reilly Log:

GM-687 Gentlemen:

The following is submitted in response to your letter dated July 31, 1980 concerning I.E.Bulletin 80-19.

Westinghouse and Bechtel do not provide mercury-vietted relays for matri., logic applications in the reactor protection system for Plant Vogtle.

The only use of mercury-wetted relays in the Westinghouse 7300 protection system are relays used for temperature channel test inputs from resistance temperature detectors. These relays are hermetically sealed and are not used in reactor trip circuits.

It is estimated that 40 hours4.62963e-4 days <br />0.0111 hours <br />6.613757e-5 weeks <br />1.522e-5 months <br /> were used for the review of design and preparation of this report. No manpower will be required for corrective actions.

Very tr

urs,

+A Doug Du ton Project General Manager CWH:sb xc:

U. S. Nuclear Regulatory Commission Office of Inspection and Enforcement Division of Reactor Operations Inspection Washington, DC M. D. Hunt - USNRC, Regicn II 8 00924o 3 gcj OFFICIAL COPY

.I 1

Mr. James P. O'Reilly RII: JP0/50-424,50-425 September 2, 1980 Page Two xc:

J. H. Miller, Jr.

W. E. Ehrensperger F. G. Mitchell, Jr.

C. F. Whitmer R. J. Kelly R. E. Conway R. W. Staffa J. T. Beckham K. M. Gillespie C. W. Hayes E. D. Groover D. L. McCrary R. A. Thomas M. Z. Jeric J. L. Vota

.