ML19338D391
| ML19338D391 | |
| Person / Time | |
|---|---|
| Site: | La Crosse File:Dairyland Power Cooperative icon.png |
| Issue date: | 08/28/1980 |
| From: | James Keppler NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
| To: | Linder F DAIRYLAND POWER COOPERATIVE |
| References | |
| NUDOCS 8009230087 | |
| Download: ML19338D391 (1) | |
Text
._
6 an anog
[
l'o,,
. UNITED STATES
,y h
NUCLEAR REGULATORY COMMISSION o
E REGION lli e
P 799 ROOSEVELT ROAD o
GLEN ELLYN, ILLINOIS 60137 Docket No. 50-409
$U620 N Dairyland Power Cooperative ATTN:
Mr. F. W. Linder General Manager 2615 East Avenue - South La Crosse, WI 54601 Gentlemen:
This IE Information Notice No. 80-31 is provided as a notification of a matter of possible safety significance.
It is expected that recipients will review the information for possible applicability to their facilities, and where applicable, consider the recommended action.
If you have questions regarding this matter, please contact the director of this office.
Sincerely, A, s.
James G. Keppler
& Director
Enclosure:
IE Information Notice No. 80-31 cc w/ encl:
Mr. R. E. Shimshak, Plant Superintendent Central Files Director, NRR/DPM Director, NRR/ DOR AEOD Resident Inspector, RIII PDR Local PDR NSIC
' TIC Hr. John Duffy, Chief Boiler Inspector, Department-of Industry, Labor and Human Relations 8009230087 T -;L t
1
SSINS No.: 6870 Accession No.:
8006190040 IN 80-31 UNITED STATES o
NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C. 20555 August 27, 1980 IE Information Notice No. 80-31:
MALOPERATION OF GOULD-BROWN BOVERI 480 V0LT-TYPE K-6005 AND K-DON 6005 CIRCUIT BREAKERS Description of Circumstances:
The Cincinnati Gas & Electric Company reported problems with the Gould-Brown l
Boveri Type K-6005 and K-DON 6005 circuit breakers used in 480 volt a.c.
l circuits at the William H. Zimmer nuclear stations.
The problem involved inadvertent circuit breaker closure during operation of the breaker charging springs when the breaker was ra ked out to the test position.
The problem resulted from the use of undersized bushings in the circuit breaker secondary close latches.
The undersized bushings caused the secondary close latch to hang-up on the shunt trip device resulting in an inadvertent circuit breaker closure when the spring charging motor was energized.
The vendor has stated that the problem does not exist during normal operations with the circuit breaker in the connected position.
Recommended Action for Licensees and Holders of Construction Permits:
All licensees of operating nuclear power reactors and holders of construction permits should be aware of the potential problems described above.
The vendor has stated that a small number of circuit breakers were assembled with under-sized secondary latch bushings between 1969 and 1977.
It is recommended that the following actions be taken:
(1) Determine if the subject circuit breakers are installed in any safety-related application at your facility.
The affected circuit breakers are manufactured by Gould-Brown Boveri and are types K-6005 and K-DON 6005, 480-volt a.c. electrically operated, drawout type with static trip device.
(2) If it is determined that your facility has the circuit breakers described-in Item (1) above, perform the K-6005, K-DON 6005 Field Test Procedure attached to this information notice (Gould-Brown Boveri I.B.-9.1.7-6 Issue F, Addendum 2, dated March 4, 1980).
(3) If maloperation of the circuit breaker occurs during performance of the field test procedure described in Item (2) above, perform the corrective action described in the a hed field test procedure (installation of a atch and retest of the circuit breaker).
DUPLICATE DOCUMENT Entire document previously entered into system under:
b[.., d..h ANO No. of es:
1 j