ML19338D381

From kanterella
Jump to navigation Jump to search
Forwards IE Info Notice 80-31, Maloperation of Gould-Brown Boveri 480 Volt Type K-600S & K-DON 600S Circuit Breakers. No Written Response Required
ML19338D381
Person / Time
Site: Clinton  
Issue date: 08/28/1980
From: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Gerstner W
ILLINOIS POWER CO.
References
NUDOCS 8009230073
Download: ML19338D381 (1)


Text

.

d'pSHoog#

  1. o UNITED STATES ILjC

[y g NUCLEAR REGULATORY COMMISSION g

i 4

e REGION lil

' g, %'.v, o,,

799 ROOSEVELT ROAD a

,[

cLEN ELLYN,ILLIN0ls 60137

>AUS 2 8 880 Docket No. 50-461 Docket No. 50-462 Illinois Power Company ATTN:

Mr. W. C. Gerstner Executive Vice President 500 South 27th Street Decatur, IL 62525 Gentlemen:

This IE Information Notice No. 80-31 is provided as a notification of a matter c,f possible safety significance.

It is expected that recipients will revi2w the information for possible applicability to their facilities, and where applicable, consider the recommended action.

If you have questions regarding this matter, please contact the director of this office.

Sincerely, b.

ames G. Keppler Director

Enclosure:

IE Information Notice No. 80-31 cc w/ enc 1:

Central Files Director, NRR/DPM Director, NRR/ DOR PDR Local PDR NSIC TIC Mr. Dean Hansell, Office of Assistant Attorney General Mr. Gary N. Wright, Chief Division of Nuclear Safety 8009230073

SSINS No.: 6870 Accession No..

8006190040 IN 80-31 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C. 20555 August 27, 1980 IE Information Notice No. 80-31:

MALOPERATION OF GOULD-BROWN B0 VERI 480 VOLT-TYPE K-6005 AND K-DON 6005 CIRCUIT BREAKERS Description of Circumstances:

The Cincinnati Gas & Electric Company reported problems with the Gould-Brown Boveri Type K-6005 and K-DON 6005 circuit breakers used in 480 volt a.c.

circuits at the William H. Zimmer nuclear stations.

The problem involved inadvertent circuit breaker closure during operation of the breaker charging springs when the breaker was racked out to the test position.

The prob 1cm resulted from the use of undersized bushings in the circuit breaker secondary close latches.

The undersized bushings caused the secondary close latch to hang-up on the shunt trip device resulting in an inadvertent circuit breaker closure when the spring charging motor was energized.

The vendor has stated that the problem does not exist during normal operations with the circuit breaker in the connected position.

Recommended Action for Licensees and Polders of Construction Permits:

All licensees of operating nuclear power reactors and holders of construction permits should be aware of the potential problems described above.

The vendor has stated that a small number of circuit breakers were assembled with under-sized secondary latch bushings be seen 1969 and 1977.

It is recommended that i

the following actions be taken:

(1) Determine if the subject circuit breakers are installed in any safety-related application at your facility.

The affected circuit breakers are manufactured by Gould-Brown Boveri and are types K-6005 and K-DON 6005, 480-volt a.c. electrically operated, drawout type with static trip device.

(2) If it is determined that your facility has the circuit breakers described in Item (1) above, perform the K-6005, K-DON 6005 Field Test Procedure attached to this information notice (Gould-Brown Boveri I.B.-9.1.7-6 Issue F, Addendum 2, dated March 4, 1980).

(3)

If maloperation of the circuit breaker occurs during performance of the field test procedure described in Item (2) above, perform the corrective action described in the attached field test procedure (installation of a d retest of the circuit breaker).

)

DUPLICATE DCCUMENT Entire document previously entered into system under:

ANO 3C)Q (MOC)%C)

No. of pages:

"7

- - _.