Forwards IE Info Notice 80-31, Maloperation of Gould-Brown Boveri 480 Volt Type K-600S & K-DON 600S Circuit Breakers. No Written Response Required
ML19338D379
Person / Time
Site: Midland
Issue date: 08/28/1980
From: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Jackie Cook
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
References
NUDOCS 8009230071
Download: ML19338D379 (1)


Text

sucu

[e kk UNITED STATES

,og NUCLEAR REGULATORY COMMISSION o

3,,7 - [E REGION lli 799 ROOSEVELT ROAD 6-o, D

GLEN ELLYN, ILLINOls 60137 o

'AUG 2 81980 Docket No. 50-329 Docket No. 50-330 Consumers Power Company ATTN:

Mr. James W. Cook Vice President Midland Project 1945 West Parnall Road Jackson, MI 49201 Gentlemen:

This IE Information Notice No. 80-31 is provided as a notification of a matter of possible safety significance.

It is expected that recipients will review the information for possible applicability to their facilities, and where applicable, consider the recommended action.

If you have questions regarding this matter, please contact the director of this office.

Sincerely, James G. Keppler Director

Enclosure:

IE Information Notice No. 80-31 cc w/ enc 1:

Central Files Director, NRR/DPM

-Director, NRR/ DOR PDR Local PDR NSIC TIC Ronald Callen, Michigan Public Service Commission Myron M. Cherry,-Chicago 8009230071

SSINS No.: 6870 Accession No.:

8006190040 1N 80-31 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C. 20555 August 27, 1980 IE Information Notice No. 80-31:

MALOPERATION OF GOULD-BROWN B0 VERI 480 VOLT-TYPE K-6005 AND K-DON 6005 CIRCUIT BREAKERS Description of Circumstances:

The Cincinnati Gas & Electric Company reported problems with the Gould-Brown Boveri Type K-6005 and K-00N 6005 circuit breakers used in 480 volt a.c.

circuits at the William H. Zimmer nuclear stations.

The problem involved inadvertent circuit breaker clesure during operation of the breaker charging springs when the breaker was racked out to the test position.

The problem resulted from the use of undersized bushings in the circuit breaker secondary close latches.

The undersized bushings caused the secondary close latch to hang-up on the shunt trip device resulting in an inadvertent circuit breaker closure when the spring charging motor was energized.

The vendor has stated that the problem does not exist during normal operations with the circuit breaker in the connected position.

Recommended Action for Licensees and Holders of Construction Permits:

All licensees of operating nuclear power reactors and holders of construction permits should be aware of the potential problems described above.

The vendor has stated that a small number of circuit breakers were assembled with under-sized secondary latch bushings between 1969 and 1977.

It is recommended that the following actions be taken:

(1) Determine if the subject circuit breakers are installed in any safety-related application at your facility.

The affected circuit breakers are manufactured by Gould-Brown Boveri and are types K-6005 and K-DON 6005, 480-volt a.c. electrically operated, drawout type with static trip device.

(2)

If it is determined that your facility has the circuit breakers described-in Item (1) above, perform the K-6005, K-DON 6005 Field Test Procedure attached to this information notice (Gould-Brown Boveri I.B.-9.1.7-6 Issue F, Addendum 2, dated March 4, 1980).

(3) If maloperation of the circuit breaker occurs during performance of the field te:,t procedure described in Item (2) above, perform the corrective action described in the attac ld test procedure (installation of a ch and retest of the circuit breaker).