Forwards LER 80-140/03L-0
Date released: 12/18/2019 Download: ML19338C921


LER 80-140/03L-0:on 800809,during Preoperational Test,Diesel Generator 86LOR Relay Coils Burned Out Following Blackout Initiation.Caused by 86LOR Relay Being Reset Before Blackout Relays.Coils Replaced & Relays Reset
ML19338C923
Person / Time
Site: Sequoyah 
Issue date: 08/29/1980
From: Romine D
TENNESSEE VALLEY AUTHORITY
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19338C923 (2)
Forwards LER 80-140/03L-0
ML19338C920
Person / Time
Site: Sequoyah 
Issue date: 08/29/1980
From: Calhoun J
TENNESSEE VALLEY AUTHORITY
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19338C920 (1)