ML19331C385
| ML19331C385 | |
| Person / Time | |
|---|---|
| Site: | Callaway |
| Issue date: | 08/07/1980 |
| From: | James Keppler NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
| To: | Bryan J UNION ELECTRIC CO. |
| References | |
| NUDOCS 8008180213 | |
| Download: ML19331C385 (1) | |
Text
i
/
UNITED STATES 8
NUCLEAR REGULATORY COMMISSION
~
o n"
REGION lli n
,a Q
793 ROOSEVELT ROAD GLEN ELLYN, ILLINOIS 60137
'g' o
AUG 7 900-Docket No. 50-483 Docket No. 50-486 Union Electric Company ATTN:
Mr. John K. Bryan Vice President - Nuclear P. O. Box 149 St. Louis, MO 63166 Gentlemen This Information Notice is provided as an early notification of a po-r'bly significant matter.
It is expected that recipients will rev.ew the information for possible applicability to their facilities.
No specific action or response is requested at this time.
If further NRC evaluations so indicate, and IE Circular or Bulletin will be issued to recommend or request specific licensee actions.
If you have questions regarding this matter, please contact the Director of the appropriate NRC Regional Office.
Sincerely, As m
ames G. Keppler Director
Enclosure:
IE Information Notice No. 80-29 cc w/ encl:
Mr. W. H. Weber, Manager, Nuclear Construction Central Files Director, NRR/DPM Director, NRR/ DOR AEOD PDR Local PDR NSIC TIC Region I & IV Ms. K. Drey Mr. Ronald Fluegge, Utility Division, Missouri Public Service Commission 8008180 2/3 -
A SSINS No.: 6835 Accession No.:
UNITED STATES 8006190620 NUCLEAR REGULATORY C0t94ISSION OFFICE OF -INSPECTION AND ENFORCEMENT WASHINGTON, D.C.
20555 August 7,i980 IE Information Notice No. 80-29 BROKEN STUDS ON TERRY TURBINE STEAM INLET FLANGE When removing the governor and stop valve on the Unit 1 steam driven emergency feedwater pump at Arkansas Nuclear One for repair of a steam leak at the steam inlet flange Arkansas Power and Light discovered that five of the eight studs securing the flange were broken.
The cause of the stud failure is unknown at this time. Metallurgical evalua-tion of the failed bolting will be performed to identify the mode of failure.
The failed studs are 3/4 in. diameter by 3-1/2 in.
long and are thought to be of ASTM-lo" grade B7 steel. The turbine flange bolting is generally covered with in'alation and not visible for inspection.
From the information available, the bolting has not been removed or inspected since installation seven to eight years ago.
The steam driven emergency feedwater pump turbir.e at ANO-1 is a type G turbine manufactured by the Terry Steam Turbine Company of Hartford, Connecticut.
The turbine is rated at 680 BHP and 3560 RPM.
The turbine operates at a reduced steam pressure of 270 psig and temperature of 400 F and has previously experienced overspeed trips and vibrations which may have been caused by slugs of water from the piping.
Licensees are encouraged to carefully examine insulation in the flange to turbine casing region for evidence of leakage and consider inspection of the turbine steam inlet flange bolting.
Further, during surveillance testing, care should be taken to observe if abnormal vibration or other transients occur whict. could promote loss of bolting integrity.
This Information Notice is provided as an early notification of a possibly significant matter that is still under review by the NRC staff.
It is expected that recipients will review the information for possible applicability to their facility.
No specific action or response is requested at this time.
If you have any questions regarding this matter, please contact the Director af the appropriate NRC Regional Office.
r
?
IE Information iotice No. 80-29 Enclosure August 7, 1980 RECENTLY ISSUED IE INFORMATION NOTICES p
Information Subject Date Issued To Notice No.
Issued
~
Supplement to Notification of 7/29/80 All holder of Reactor 80-06 Significant Events at OLs and to near Operating Power Reactor operating license Facilities applicants 80-28 Prompt Reporting Of 6/13/80 All applicants for and Required Information holders of nuclear power To NRC reactor construction 80-27 Degradation of Reactor 6/11/80 All Pressurized Water Coolant Pump Studs Reactor Facilities holding power reactor OLs or cps 80-26 Evaluation of Contractor 6/10/80 All Part 50 Licensees QA Programs 80-25 Transportation of 5/30/80 Material Licensee in Pyrophoric Uranium Priority / Categories II-A, II-D, III-I and IV-DI; Agreement State Licensees in equivalent categories 80-24 Low Level Radioactive 5/30/80 All NRC and Agreement Waste 8urial Criteria State Licensees 80-23 Loss of Suction to 5/29/80 All power reactor to Emergency Feedwater facilities with an Pumps OL or CP 80-22 Breakdown In Contamina-5/28/80 All power reactor tion Control Programs OLs and near term cps 80-21 Anchorage and Support of 5/16/80 All povtr reactor Safety-Related Electrical facilities with an Equipment OL or CP 80-20 Loss of Decay Heat 5/8/80 All light water reactor Removal Capability at facilities holding Davis-Besse Unit 1 While power reactor OLs or cps in a Refueling Mode I
i
~ ~
'^
w
,.*w
,+
.,_v.
=g
,,_