,f-Cansumars 1 Ptmr C:mC. GD7 General Offices: 212 West Mecnigan Avenue, Jackson, Michigan 49201. Area Code 517788-0550 March 5, 1976 Director of Nuclear Reactor Regulation Attention:
Mr. Roger Boyd, Director Tms DOC %ENT CONTAINS Division of Porject Management U. S. Nuclear Regulatory Commission k
g gg$IS --
u n ', i r -
Washington, DC 20555
- g. f gcgg MIDLAND PROJECT
~
-~~
DOCKET NUMBERS: 50-329, 50-330 FIRE PROTECTION SYSTEM FILE: 0505.2 SERIAL: 2191 The attached information responds to the March 3, 1976, request for information on the Midland Plant Fire Protection System.
In accordance with the staff request our response is in table form and addresses 23 areas of the plant.
The attached table is based on preliminary system design concepts and is, therefore, subject to change as engineering is finalized.
Please advise if additional information is required.
^W-R. C. Bauman Project Engineer RCB/pc
/
G.,J s\\
o
- k, 1975 '.
N-u.s. kk'M
@ ic,, M Ay ey-8006160 g
m Attachment to CPCo Serial 2191 MIDLAND PLANT UNITS 1 & 2 CONSUMERS POWER COMPANY PRELIMINARY FIRE PROTECTION SYSTEM DESIGN CONCEPT ABBREVIATIONS:
}
- Available for Use from Adjoining Area I
- Ionization Portable Fire Extinguishers Type DC - Dry Chemical Extinguishers 4
Type CO2-CO2 Extinguishers FIRE SUPPRESSION SYSTEM FIRE DETECTION, ALARM AND ANNUNCIATIC f
AREA PRIMARY SYSTEM SECONDARY SYSTEM ALARM AND ANNUNCIATION LOCATION
)
DEVICE LOCALLY MAIN CONTROL ROOM (See Note #1) 4 Reactor Building Portable Extinguishers Wet Stand Pipe I
Yes Type CO2*
System
- l Control Room Portable Extinguishers Wet Stand Pipe I
Yes Yes j
Type CO2*
System
- I Cable Spreading Rooms Automatic Fixed CO2 Wet Stand Pipe I
Yes Yes System System
- Plant Computer Room Automatic Fixed CO2 Wet Stand Pipe I
Yes Yes or Automatic Fixed System
- and Halon System Portable Extinguishers Type DC*
Switch Gear Rooms Portable Extinguishers I
Yes Yes i
Type CO2
/
i Remote Shutdown Area Portable Extinguishers Wet Stand Pipe I
Yes Yes Type CO2 System *
'lon Battery Rooms Portable Extinguishers Wet Stand Pipe Type CO2 and DC*
System
- Ne Oil Storage Automatic Wet Sprinker Wet Stand Pipe Yes Yes System System Automatic Wet Sprinkler Wet Stand Pipe Yes Yes eas System System
- Portable Extinguishers Wet Stand Pipe Yes Yes Type DC System *
%:tomatic Fixed CO2 Yard Hydrants Yes Yes am Yard Hydrants i
Page 1
o Attachment to CPCo Serial 2191 MIDLAND PLANT UNITS 1 & 2 CONSUMERS POWER COMPANY PRELIMINARY FIRE PROTECTION SYSTEM DESIGN CONCEPTS FIRE SUPPRESSION SYSTEM FIRE DETECTION, ALARM AND ANNUNCIATION AREA PRIMARY SYSTEM SECONDARY SYSTEM ALARMANDANNUNCIATIONLOCAT(ON DEVICE LOCALLY MAIN CONTROL ROOM (See Note #1)
Safety Related Pump Rooms Portable Extinguishers Wet Stand Pipe I
Yes Yes Type DC*
System
- f Service Water Pump llouse Portable Extinguishers Yard Ilydrants I
Yes Yes l
Type C09 l
New Fuel Storage Area Portable Extinguishers Wet Stand Pipe l
type CO2 and DC*
System Spent Fuel Pool Area
~);
Radwaste Area Portable Extinguishers Wet Stand Pipe I
Yes Yes l
Type DC System Decontamination Area Portable Extinguishers Wet Stand Pipe Type CO2 and DC*
System
- Outside Safety Related Yard Hydrant Storage Tanks (See Note #2)
Record Storage Vault Automatic Fixed llalon Wet Stand Pipe I
Yes Yes l
System System
- Shop and Warehouse Automatic Wct Sprinkler Portable Extinguishers I
Yes Yes System Type DC and C07 Outside Transformers Automatic Deluge System Yard Hydrant Yes Yes Auxiliary Boiler Room Automatic Wet Sprinkler Wet Stand Pipe Yes Yes System System *
)
l Ilydrogen Seal Oil Area Automatic Wet Sprinkler Wet Stand Pipe Yes Yes System or Automatic System
- Preaction System Auxiliary Building Automatic Fixed CO2 Wet Stand Pipe I
Yes Yes
-Electrical Penetration Rm. System System *
-All Other Areas Portable Extinguishers Wet Stand Pipe I
Yes Yes Type DC and CO2 System
- NOTES:
(1) Detection devices will be located as required within the areas.
r (2) Outside safety related storage tanks and contents for Midland project are non combustible.
~
Page 2 c
. N.
'lON DOp. ~ - 1 9 NRC ronM 105 2 '/
3Q (2 76)
NRC DISTRIBUTION FOR PART 50 DOCKET MATERI AL FROM:
TO:
Mr BOya Consumers ewr CO JaCf sun,.diCn ATE RECEIVED R C Bau= tan 3_,_
hbETTEn O NOTO RIZED -
PROP INPUT FORM NUMBER OF COPIES RECEIVED
$ COPY Cne $1GnQu
/
ENCLOSU R E DESCRIPTION Luc te Our 3-3-7o requess...tranS ene tu.iuw:
Addl into in response to Our requesL concernin; rire protection systesm......(. cy rec'd)
_. _ _ _ _. _ _. ~
PLANT NAME:
Midland 1 & 2 SAiETY FOR ACTION /INFORMATION ENVIRO 3-31-7e ehf
/
ASSIGNED AD
- 1
% U,3 4
~ Bid M H CHIEF.
ASSIGNED AD.'
A,,, c_ / '
/
BRANCH CHIEF :
/
/
PROJECT 14ANAGER:
C,oe /(t r PROJECT MANAGER.'
/
LIC. A$ST. :
Suvic 6 LIC. ASST. -
INTERNAL DISTRIBUTION 7t_ REG FILE J SYSTEMS SAFETY PLA'IT RYSTEME pmrynn Tren
/
NRG Fi)R HETNEMAN
/
Trnngrn ERNST
/
I&E (%)
SCFPonnnn
/
BENAROYA BALLARD OELD
/
LAINAS
$PXlNGLER
/
IPPOLITO GOSSICK & STAFF ENGIEEERING MIPC MAccAny SITE TECH CAS_E
/ KNIGHT OPERATING REACTORS
/
GAMMILL
__,__lMNAUER
/
SIINEIL
/
STELLO
/_. STEPP HARLESS
/
PAULICKI
+ HULMAN OPERATING TECH PROJECT MANAGEMENT REACTOR SAFETY EISENHIrr SITE ANALYSIS BOYD
/
ROSS SHA0
/
VOLI2ER P. COLLINS
/.
NOVAK EAER
/,
BUNCH J. COLLINS
/
IICUSTON
/
ROSZTOCZY SCINENCER PETERSON
/
CHECK GRIMES
/
KREGER MELTZ IIELTEMES AT & I SITE SAFETY & ENVIRC SKOV110LT SALTZMAN ANALYSIS RUTHERG DENTON & MULLER
/)
CONTROL NUMBER EXTERNAL DISTRIBUTION
/
LPDR: 17) d /0nd. /Hf NATL LAB BROOKILWEN NATL LAB
/
O I
/
NSIC LA PDR ASLB CONSULTANTS 4
/
AGRS /l, HOIMQS_E_Nr
'T D k r3 9 G a u L-Q/
i
.,..n......,,,..