ML19329E327
| ML19329E327 | |
| Person / Time | |
|---|---|
| Site: | Midland |
| Issue date: | 03/04/1977 |
| From: | James Keppler NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
| To: | Howell S CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.) |
| References | |
| NUDOCS 8006120635 | |
| Download: ML19329E327 (1) | |
Text
- -.
m g
^
CENTRAL FILES t
t i
@4 1977 l
Consa2 : s Ucuer Coopt.ny
- ]cchet lio. 50-329 ATT i:
Mr. Stephen ;i. i:cuall Jceket L'o. 50-330 Vice frasident 1943 West Parnall Road Jachaca, til 49201 Centlemen:
The enclosed IE Circulcr 77-03 in forwarded to you for inforua-i tion, ilo written responsa is required. :ihould you 1: ave any questions concernin.g thic raatter contact the Director of thic iiaC Rer,ional office.
Sincerely, Janco G. Icppler feirector D.clocura:
IE Circular lio. 77-03, I' ire II: side a i'otor control Ce:tter cc w/cecl:
i Central Files neproductica tinit JAC 20b Pa?,
Loca.t Paa THIS DOCUMENT CONTAINS Ronald Callen, Michigan l
Public S erico Ccuniablon P0OR QUAL.lTY PAGES i
j Dr. tiaytw T.. Murth l
i!yron li. Cherry, Chiccxo 1
i i
N F
J
- I th orr.c
- RIII.
'f.
RIII _
jf... "
lleishraan/jE p.Keppler 3/1/77
. jjkJf[_
o.,,,
Tosis Atc.318 (Rev. 9 53) AICM 0240
/
- u. s. oovranusar rmurina arrects is74.sas.ese 80 06 1 S0 b.)
~'k
9 O
O C
e, March 4, 1977 IE Circular No. 77-03 FIRE ~INSIDE A MOTOR CONTROL CENTER
~
DESCRIPTION OF CIRCUMSTANCES On November 22, 1976, a fire occurred in a safety-related ITE Imperial Series 5600 Motor' Control Center (MCC) at the Three Mile Island Unit No. 2 facility. The fire was caused by partial engagement of the plug-in connector assembly of a combination circuit breaker / starter unit with the vertical bus. This resulted in a high resistance contact between one connector stab and a vertical bus bar with localized overheating of the stab. The hot stab ignited a vertical insulation backwall which was made of a fiberglass polyester. This backwall was provided as a personnel cafety feature by the vendor to provide a barrier between the normally energized vertical bus and the breaker / starter unit compartments.
A similar fire occurred in an ITE Series 5600 Motor Control Center at the Trojan Nuclear Station on March 4,1976, as a result of a mis-stab of the plug-in connector assembly to the vertical bus.
Subsequent to this fire at the Trojan facility, ITE reportedly issued a technical
' instruction letter to nuclear power plant licensees using these motor control centers to advise them of the potential connector misalignment problem and recommended procedural steps to preclude future occurrences.
This instruction was received by the Three Mile Island Unit No. 2 licensee and was in the process of being implemented; however, the breaker / starter unit which caused the fire at that facility had not yet been checked as recommended in the ITE Instruction Letter. A copy of ITE's technical instruction letter is attached.
The MCC fire at the Three Mile Island Unit No. 2 facility essentially destroyed the entire motor control center. The insulation backwall continued to burn af ter the MCC was de-energized and the fire pro-gressed upward and ignited a similar plastic barrier near the top of the MCC which was provided to separate the horizontal bus from the wire-way. The fire apparently continued along the horizontal barrier igniting the other vertical backwall barriers and destroyed most of the breaker /
starter unit in the MCC.
f5 c/
~{o jQ
'7 Af g
- 1) \\
04(
~
Tn U
i I e
f e
l
z
.- s}.
a.*
g
-}
c l,
-Q ?,
c y(
f, e,
4 s
y IE Circular No. 77-03 2-March 4, 1977 i
RECOMMENDED ACTIO'J TO LICENSEES:
If motor control centers similar to those described are in use in safety-
, l related systems or in proximity to safety-related systems, you should 1
verify that your maintenance procedures contain adequate provisions to insure that the electrical stab connection in these units are properly
.. aligned to their respective vertical bus bars to assure that a positive and full engagement exists between the connector stab and its associated vertical bus bar.
Specifically you should review the ITE technical instruction letter and follow the recommended procedure outlined in this
,j letter.
ij You should also determine if~the materials which are used for bus insulation and supports in these motor control centers have flame retardant ratings equal to or.better than a 94 V-0 classification as I
covered in UL Standard No. 94. entitled, " Tests For Flammability Of I.
Plastic Materials."
I l
No written response to this Circular is required.
If you require additional information regarding this matter, contact the Director of the appropriate NRC Regional. Office.
l Attachments:
1.
ITE's Technical i
'N Instruction ltr i
2.
Instruction Procedure for ITE 5600 Motor Control Center Units 1.
e l
l "t
s l
~t.
i 1
t 9:,.
t
9,
.x... _., _..
- 9....
3, e-
~
C -
- 9
1
?
l COPY OF ITE TECHNICAL INSTRUCTION LETTER
,i
?
I j
Gentlemen:
I j
All Motor Control Centers, 5600 Series, are built and factory inspected l
to Class IE specifications to insure that when shipped to the jobsite they will function as intended.
l i
In spite of the rigorous and thorough inspection of Class IE equipment i
.by I-T-E, as well as, the separate inspection group contracted by the buyer, a malfunction occurred at the Trojan Nuclear Facility of Portland i
General Electric on March 1976 - MCC #B56 shipped on December 15, 1972.
~
The malfunction appears to be due to an apparent mis-stab of the plug-in connector assembly to the vertical bus on a Size 4 combination circuit breaker starter.
i
~
All front mounted control centers having rear access are visually inspected to insure proper engagement of stabs on the bus. While the thorough final inspection made, just prior to shipment are documented, the validity of such factory inspections are destroyed i
l whenever starter units are moved from one compartment'to another'at j
the jobsite due to layout or viring changes or when starters are removed for ease of pulling load cables oi maintenance of the unit.
Motor Control Centers, in accorda,nce with the state-of-the-art.
are designed to have plug-in capabilities for case of changes or maintenance. However, it cannot be assumed that the plug-in units
,can be treated without regard to strict attention to handling and protecting while it is removed from the vertical sections. Deforma-tion of stabs can occur if units are not protected against I
mechanical damage. For your field inspection of units, we can supply you with a bus stab guage and instructions which will insure that the units are reinstalled correctly.
Due to the critical loads involved on Class IE equipment, we suggest
- that stabs be visually inspected where possible. Motor Control Centers with-front counted units only, 20" deep, can be visually in-spected by merely opening the two hinged, half height rear doors.
~
However, with back-to-back mounted units, or Motor Control Centers mounted against the wall, the inspection of the stabs can only be l
performed with the use of special equipment.
If there is any doubt as to the thoroughness of such field inspection on units now installed, an inspection should be performed at the earliest possible time for possible mis-stab of the plug-in connec-tor assembly to the veritcal bus.
4 l
1
u._.
_. = =. -
c.
n
,3
.=
-7.. i, C
4-r t
l 1
t t
Copy of ITE Technical,
Instructiot Letter-I t
.t 4
i With respect to the bus stab gauge referenced to in Paragraph 4, one
'of these bus stab guages will be forwarded to you on a "ro charge" basis as soon as you can advise us the exact shipping address and to whose attention is should be shipped.
s
~
4
- h '*
0 e
4 e
e e
D e
8 e
3 t
t 4
7,=
4
' e's
--ea
-m, g
5 e,w-
_2 u
~
r.
e
.m
.s
^
. y.-
INSTRUCTION PROCEDURE FCR FIELD VERI.?ICATION OF PROPER f' '
BUS PLUG-IN FINGER ALICM::ENT
- ~
FOR I-T-E 5600 MOT,0R CD:iTROL CENTER UNITS y
CAUTION: Whenever a starter plug-in unit has been re=oved from the Motor Control Center the bits plug-in feature =ust be verified for correct alignment of the bus plug-in fingers using I-T-E Gauge No. PB-2104-lc as follows:
(1) Slide alignment gauge over the rear flanges of the starter r.ounting panel.
Left to right orientation of the fixture must match the i
plug-in assembly on the rear of the panel.
]
(2) Seat the stops on the inside of the ends of the align =ent gauge
~
against the flanges of the starter mounting panel as illustrated.
@) The 1/4" round b'ars velded to the gauge approximate the vertical bus positions in the MCC. These bars should be within the flared ends of the plug-in fingers, allowing the fingers to scif-center themselves lightly around the bars.
If fingers are not defor=ed, l
there vill be no problem visually verifying correct self-centering engagement as illustrated below.
s l
3 (4) If the self-centering action is not properly achieved, the plug-in nosembly must be repaired or replaced.
(S) After correct gauging, the starter should be handled with care and immsdiately installed into the Motor Control Center.
3
' ~
TOP VIEW OF STARTER REAR STARTEF.
~
t--
PANEL
- - s' U,
i
-B U S P L U G.[ N l
(
Yl(
)[
,.. ASSEMBLY
/
BUS PL0G.lN ALIGNMENT GAUGE IN FINGERS (3}
GAUGING FCS:T:GN CORRECT SELF CENTERING
'I.
I(
- ENGAGEMEhe
- 7. t
+
~
.