SACRAMENTO MUNICIPAL UTILITY DISTRICT C 6201 S Street, Box 15830, Sacramento, California 95813; (916) 452-3211 RJR 77-540 November 21, 1977' k

-F 'b'\\

d Director of Regulatory Operations ATTN:

Mr. R.11. Engelken f!

NRC Operations Office,

^

p,,-

.!'/

Region V

,T-Q;x'

,C' 1990 N. California Boulevard Walnut Creek, California 94596 Walnut Creek Plaza, Suite 202

_l Re: Operating License DPR-54 Docket No. 50-312 g

Reportable Occurrence 77-18 ry

Dear Sir:

y In accordance with Technical Specifications for Rancho Seco Nuclear 7

Cencrating Statica, Section 6.9.1, and Regulatory Guide 1.16, Revision 4, e-

[

Section C.2.a.(2), the Sacramento Municipal 'Jtility District hereby notifies the NRC of the following Reportable Occurrence.

m,-

During reactor startup and ascension to 92% full power operation af ter -

a brief shutdown to repair a leaking valve in the Reactor Building, the resulting Xenon transient caused considerable rod movements.

The resulting rod moveme46s exceeded time limitations of Technical Specifications Sections 3.5.2.5C and j.5.2.6 for rod posicions designated within Figure 3.5.2-1 and imbalance limits as defined in Figure 3.5.2-5.

All other operating parameters were within the prescribed limits and no safety limits or limiting safety system settings were exceeded.

A written report will be submitted to your office within fourteen days.

This occurrence has been discussed with Mr. Malmros of your office on November 18, 1977.

spectf lly submitted, x

h t\\ 4

)

R. J.

odriguez Manager, Nuclear perations

[~

RJR: sal es: Director, MIPC 800407057[

y-