_.

MAR 161972 57 - M /

I. A. Peltier, PWR Branch 74. DEL RADIATION MONITORING EQUIPMENT FOR OCONEE NUCLEAR POWER STATION Based on the estimated release of radiciodine it is questionable that

[

the monitoring device (IRIA-44, FSAR 11-17) to be installed in the unit vents will have the required sensitivity for measuring the anticipated levels either for a continuous or instantaneous release.

The applicant should be requested to verify the capability of this particular monitor.

In addition the Techn4e=1 Specification should require the applicant to : meet the criteria set forth in Safety Guide 21 - Measuring and Reporting of Effluents from Nuclear Power Plants.

De applicant should also be requested to verify tha': the charcoal to be used in the monitor is impregnated (i.e. KI) to assure collection of both elemental and non-elemental forms of iodine. Since the charcoal cartridge is a fixed sampler the applicant should provide information as to the frequency at which the charcoal will be changed (or included in the Technical Specifications.).

\\

We have no additional questions on the radweste sections.

l 1

V. Benaroya, Chief Effluent Treatment Systems Branch Division of Reactor Licensing l

cc: H. R. Denton A. Schwencer l

V. Benaroya J. T. Collins DISTRIBUTION M RL - Rdg.

d RL - Suppl.

S&RS - Rdg.

Effl. Treat. - Rdg.

omcx p DEL

........pgL

, j,,.,

g sunnaar > JIC.0LLINS:mj YBENAROYA part > 34.........D2...

... 3/..lb.D2 _................

Form AEC-518 (Rev. 9 53) ABCM 0240

c. s covrnuzNT PaceT:No orrtcz isto o. os.us 8001070 E M

[

_