l DISTRIBITTIOM Docket DRL/PWR BCs PWR #4 Reading A. Schwencer DRL Reading H. Faulkner DR Reading F. W. Karas F. Schroeder DRS BCs T. R. Wilson R. DeYoung R. S. Boyd f

DEC 7 Ell R. W. Klecker t

S. H. Hanauer H. Denton OGC (Knotts)

E. G. Case. Director Division of Reactor Standards TECHNICAL ASSISTANCE We are in the final stage of processing Oconee Unit i for licensing and request your assistance in resolving the following problems:

1. Establish the basis for acceptability for instru.mantatirin and control cabling for Unit 1 and separately for Units 2 and 3.
2. Establish the basis for acceptability for the Oconee Unit 1 integrated leak rate test..

Original Signed l[]

Peter 6.M_g!I)J P. A. Morris, Director Division of Reactor Licensing

Enclosures:

As stated 1

1' I

l o,ncr >

rfp,-g' PWR f AD/PWRs.

DRL: R A. Se cer P.

Morrin SURNAhnt>

~

Il'.*

12/6/71 12/4/71 12/_h/71_

h.

%n>

t;,

ac. min..-m acx om

. n

c..

.o. - - -,o

~ ~ '

8001070 8 b ma w-y-

+

REQUEST FOR DRS ASSISTANCE Proj ect: Oconee Units 1, 2 & 3 Docket Nos.: 50-269, 50-270 &

Project Leader:

A. Schwencer 50-287 Type of Review:

Operating License REQUESTED WORK Determine minimum acceptable physical separation Gn inches or otherwise) for redundant I & C cables in cable trays.

FSAR Revision 16 Figure 8-7 depicts Duke's solution to an overfill problem discovered by Compliance prior to July,1971.

Since then additional cables were added causing additional overfilling.

Determination on separation is required on Units 1, 2 and 3.

On Unit 1 essentially all cables are now in place.

On Units 2 & 3 very little cable pullinghas been accomplished. To assure that minimum acceptable corrective action is taken on Unit I and maximum practical preventive action is taken on Units 2.and 3, it is requested that the determination of minimum acceptable separations be addressed separately.

Slides of Unit 1 cable overloading are available.

REQUESTED COMPLETION DATE A site visit to observe the extent of cable overfill was made November 30, 1971. The applicant is in the final stag of preoperational testing on Unit 1 and should be notified as soon as possible whether corrective at-ion will be required. Therefore a completion date of December 10, 1971 is requested.

Requested by RP Branch Chief Approved by DRL/AD Signed:

.dD/

b. j'~ h -

,/

Signed:./

,r

,s

[f

/

t REQUEST FOR DRS ASSISTANCE A. Schwencer Project Leader:

Docket No.: 50-269 Project: Oconee Unit 1 Type of Review: Operating License 71 REQUESTED WORK ned R. T. Carlson memo dated November 17,19 The Duke Power Company Integrated t

Determine whether test procedure deficiencies noted in at a_

Leak Rate Test.

b 1, 1971. -

warrant rejection of the Oconee Unit 1 Containmentwas distributed within AEC on Novem er Dated October 29, 1971 Leak Rate Test Report, REQUESTED COMPLETION DATES _

The applicant currently has a window of time 10, 1971.

h d if AEC so requires. Applicant believes

_As soon as possible, but prior to Decemberin which a retest can be accomplis e by conference (now to December 24, 1971) he can justify not repeating tests and wishes to present reasons 6-10, 1971.

Bethesda (if need be) the week of December Approved by DRL/AD Recuested by RP Branch Chief f,

i l

/

em o Signed:

?

- ! / l O '

~

Signed: -

y v