ML19329A585

From kanterella
Jump to navigation Jump to search
Summarizes 720307 Telcon W/Util Re CT-4 Transformer in Switchgear Block House
ML19329A585
Person / Time
Site: Oconee 
Issue date: 03/08/1972
From: Peltier I
US ATOMIC ENERGY COMMISSION (AEC)
To:
US ATOMIC ENERGY COMMISSION (AEC)
References
NUDOCS 8001070581
Download: ML19329A585 (1)


Text

V, 3b

.Q ( c; l~

N'

(}Q[g

- NOTE TO FILE GELECON WITH aJKE ON OCONEE CT-4 TRANSFORME2 f

On March 7,15r(2, Bob Pollard and 7. discussed the CT-4 transforme.r in the switchgear block house at OqGnee with Ken Canady and Chuck Wylie The following infornr tion was given by Duke.

a of Duke.

1.

The transformer (.-4) is separated from the switchgear in the block house 'oy a firewall of reinforced concrete block and a steel r..Lidown door normally closed by administrative

-procedures.

2.

The transformer is an oil filled transformer but the trans-former room has a drain under the transforter and a trench or sill preventing the flow of oil into the switchgear room.

The transformer room is vented against explosion, and protected 3

Ggainst tornado missiles.

The transformer has emulsifier fire protection tripped by 4..

shorteircuit and no switchgear cables pass through the trans-former room.

I. A. Peltier ec:

A. Schwencer I. Peltier (2)

R. Pollard

./!bb.

5*

t l'

.A

%e \\

txt l:

8o0107oggj