ML19327B305

From kanterella
Jump to navigation Jump to search
Corrected Amend 111 to License DPR-79,revising Pages 3/4 3-82,3/4 7-20 & 3/4 9-15 Re Surveillance Requirements
ML19327B305
Person / Time
Site: Sequoyah  
Issue date: 10/18/1989
From:
NRC
To:
Shared Package
ML19327A950 List:
References
NUDOCS 8910300129
Download: ML19327B305 (4)


Text

7 j

i j

CORRI?CTE) PAGES

. FACILITY Ort uT on.ntna NO. OPR-79 j

Lu Kt' NU. 50-325 1

Revise the Appendix A Technical Specifications by removing the pages identified below anc inserting the encloseo pages.

The revised pages are

)

identified by the captioned amendnent number and contain marginal lines i

indicating the area of change, j

i REMOVE INSERT

~:

3/4 3-82 3/4 3-82 3/4 7-20 3/4 7-20 l

3/4 9-15 3/4 9-15 i

f 7

3 i

t f

a

?

l t

s 8910300129 891010 PDR ADDCK 05000327 PDR P

j a

.T #

TABLE 4.3-9 (Co,n.tinued)

A Ba.

1 TABLE NOTATION j

i At all times.

l k'i f

- During wate gas disposal system operation.

i During shield building exhaust system operation.

e i

8*** During warte gas. releases.

I (1): The CHANNEL FUNCTIONAL TEST shall also demonstrate that automatic isolation of this pathway and control room alarm annunciation occurs if any of the m

i following conditions exists:

w 1.

Instrument indicates measured levels above the alarm / trip setpoint.

2.

Circuit. failure.

3.

Duwnscale failure.

(2) The CHANNEL FUNCTIONAL TEST shall tiso demonstrate that control room alar'n annunciation occurs if any of the following conditions exists:

1.

Instrument indicates measured levels above the alarm setpoint.

2.

Circuit failure.

4 t

3.

Downscale failure.

For the auxiliary building ventilation system, at least once every 18 months, the CHANNEL FUNCTIONAL TEST shall.also demonstrate automatic j'

isolation of this pathway.if the following condition exists:

1 Instrument indicates measured levels above the alarm / trip setpoint.

'(3) The initial CHANNEL CALIBRATION shall be performed using one or more of y

the reference standards certified by the National Bureau o! Standards or usir.g standards that have been obtained from suppliers that participate e

i in measurement assurance activities with NBS.

These standards shall permit calibrsting the 3ystem over its intended range of energy and 11 measurennent range.

For subsequent CHANNEL CALIBRATION, sources that have L

been related to the initial calibration shall be used.

(4)

The CHANNEL CALIBRATION shall include the use of standard gas samples 1

L cc1taining a nominal:

1.

One volume percent hydrogen, balance nitrogen, and 2.

Four volume percent hydrogen, balance nitrogen.

l.

(5).The CHANNEL CALIBRATION shall include the use of stanoard gas samples i.

containing a riominal:

1 L

1.

One volume percent oxygen, balance nitroger., and i

L 2.

Four volume percent oxygen, balance nitrogen.

l f

SEQUCYAH - UNIT 2 3/4 3-02 Amendment No. 13, 111 1, '

f,

h.

E :

t

~

c 1

7 L

y;,+.,

hi PLANT SYSTEMS F..

p-

[,H SURVEILLANCE REQUIREMENTS (Continued)

?

1' After every 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of charcoal adsorber operation by verifyin i

c.

within 31 days after removal that a laboratory' analysis of repreg sentative carbon sample obtained in accordance with Regulatory.

Position C.6.b of: Regulatory Guide. l.52, Rwision 2, March 1978, meets the laboratory testing criteria of Regulatory Position C.6.a

.of Regulatory Guide 1.52, Revision 2, March 1978.

1' L

d.

At least once per 18' months by:

J 1.

Verifying that.the pressure drop across the combined HEPA filters and charcoal adsorber banks is less than 3 inches Water r"

Gauge while operating the filter train at a flow rate of 9000 cfm i 10%.

D 2.

Verifyin that the filter trains start on a Containment Phase

'A isclat on test signal.

3.

Verifying that the. system maintains'the spent fuel storage area and the ESF.pum rooms at a pressure equal.to or more negative than j

e

.minus 1/4-inch water gauge relative the outside atmosphere while maintaining a vacuum relief flow greater than 2000 cfm and a total system' flow of 5000 cfm i 10%.

4.

Verifying that the heaters dissipate 32 i 3.2 kw when tested in accordance with ANSI N510-1975.

After each complete or partial replacement of a HEPA filter bank by e.

verifying that the HEPA filter banks remove greater than or equal to g

99.95% of the DOP when they are tested in place in accordance with ANSI N510-1975 while operating th9 system at a flow rate of 9000 cfm i 10%.

f.

After each complete or partial replacement of a charcoal adsorber

. bank by verifying that the charcoal adsorbers remove greater than or equal to 99.95% of a halogenated hydrocarbon refrigerant test gas when they are tested in place in accordance with ANSI N510-1975 while operating the systen at a flow rate of 9000 cfm i 10%.

SEQUOYAH - UNIT 2 3/4 7-20 Amendment No. 77, 111 t

4 n.e w

-..w

--ev

m:;

x.

i m_,,

y rp q

(

'+

i l..,.

i l

.' REFUELING OPERATIONS.

y o3

~* '*

g

~ SURVEILUNCE REQUIREMENTS (Continued)

)

-l L

c.

After every 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of charcoal adsorber cperation by verifying within 31 days after removal that a laboratory analysis of representa-tive carbon sample obtained in accordance with'. Regulatory Position-i C.6.b of Regulatory Guide 1-52, Revision 2, March 1978, meets the laboratory.esting criteria of Regulatory Position C.6.a of Regulatory y

Guide 1.52, Revision 2,< Mar:.h 1978.

d.

.At least once per 18 months by:

1..

Verifying that the pressure drop across the con:bined HEPA filters and charcoel adsorber banks is less than 3 inches Water Gauge while operating the filter train at a flow rate of 9000 cfm i 10%.

2.

t l=rifying that the filter train starts on a high radistion signal from the fuel pool radiation monitoring system.

i

3..

Verifying that the heaters dissipate 32 1 3.2 kw when tested in accordance with ANSI.N510-1975.

After each complete or partial replacement of a HEPA filter bank by e.-

i 1

verifying that the HEPA filter banks remove greater than or equal to

/

99.95% of the 00P when they are tested in place in accordance with ANSI H510-1975 while operating the systera at a fiow rate of 9000 cfm t

i 10%.

f.'

Afterfeach complete or partial replacement of a charcoal adsorber bank by verifying that the charcoal adsorbers remove greater than or r

equal. to 99.95% of a halogenated hydrocarbon refrigerant test gas when they are tested in place in accordance with ANSI N510-1975 h

while operating the system at a flow rate of 9000 cfm i 10%.

'3; t

)

L i

i

\\,'

i I

i SEQUOYAH - UNIT 2 3/4 9-15 Amendment No. 77, 111 3,.

t

- -..