ML19327B305
| ML19327B305 | |
| Person / Time | |
|---|---|
| Site: | Sequoyah |
| Issue date: | 10/18/1989 |
| From: | NRC |
| To: | |
| Shared Package | |
| ML19327A950 | List: |
| References | |
| NUDOCS 8910300129 | |
| Download: ML19327B305 (4) | |
Text
7 j
i j
CORRI?CTE) PAGES
. FACILITY Ort uT on.ntna NO. OPR-79 j
Lu Kt' NU. 50-325 1
Revise the Appendix A Technical Specifications by removing the pages identified below anc inserting the encloseo pages.
The revised pages are
)
identified by the captioned amendnent number and contain marginal lines i
indicating the area of change, j
i REMOVE INSERT
~:
3/4 3-82 3/4 3-82 3/4 7-20 3/4 7-20 l
3/4 9-15 3/4 9-15 i
f 7
3 i
t f
a
?
l t
s 8910300129 891010 PDR ADDCK 05000327 PDR P
j a
.T #
TABLE 4.3-9 (Co,n.tinued)
A Ba.
1 TABLE NOTATION j
i At all times.
l k'i f
- During wate gas disposal system operation.
i During shield building exhaust system operation.
e i
8*** During warte gas. releases.
I (1): The CHANNEL FUNCTIONAL TEST shall also demonstrate that automatic isolation of this pathway and control room alarm annunciation occurs if any of the m
i following conditions exists:
w 1.
Instrument indicates measured levels above the alarm / trip setpoint.
2.
Circuit. failure.
3.
Duwnscale failure.
(2) The CHANNEL FUNCTIONAL TEST shall tiso demonstrate that control room alar'n annunciation occurs if any of the following conditions exists:
1.
Instrument indicates measured levels above the alarm setpoint.
2.
Circuit failure.
4 t
3.
Downscale failure.
For the auxiliary building ventilation system, at least once every 18 months, the CHANNEL FUNCTIONAL TEST shall.also demonstrate automatic j'
isolation of this pathway.if the following condition exists:
1 Instrument indicates measured levels above the alarm / trip setpoint.
'(3) The initial CHANNEL CALIBRATION shall be performed using one or more of y
the reference standards certified by the National Bureau o! Standards or usir.g standards that have been obtained from suppliers that participate e
i in measurement assurance activities with NBS.
These standards shall permit calibrsting the 3ystem over its intended range of energy and 11 measurennent range.
For subsequent CHANNEL CALIBRATION, sources that have L
been related to the initial calibration shall be used.
(4)
The CHANNEL CALIBRATION shall include the use of standard gas samples 1
L cc1taining a nominal:
1.
One volume percent hydrogen, balance nitrogen, and 2.
Four volume percent hydrogen, balance nitrogen.
l.
(5).The CHANNEL CALIBRATION shall include the use of stanoard gas samples i.
containing a riominal:
1 L
1.
One volume percent oxygen, balance nitroger., and i
L 2.
Four volume percent oxygen, balance nitrogen.
l f
SEQUCYAH - UNIT 2 3/4 3-02 Amendment No. 13, 111 1, '
f,
- h.
E :
t
~
c 1
7 L
y;,+.,
hi PLANT SYSTEMS F..
p-
[,H SURVEILLANCE REQUIREMENTS (Continued)
?
1' After every 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of charcoal adsorber operation by verifyin i
c.
within 31 days after removal that a laboratory' analysis of repreg sentative carbon sample obtained in accordance with Regulatory.
Position C.6.b of: Regulatory Guide. l.52, Rwision 2, March 1978, meets the laboratory testing criteria of Regulatory Position C.6.a
.of Regulatory Guide 1.52, Revision 2, March 1978.
1' L
d.
At least once per 18' months by:
J 1.
Verifying that.the pressure drop across the combined HEPA filters and charcoal adsorber banks is less than 3 inches Water r"
Gauge while operating the filter train at a flow rate of 9000 cfm i 10%.
D 2.
- Verifyin that the filter trains start on a Containment Phase
'A isclat on test signal.
3.
Verifying that the. system maintains'the spent fuel storage area and the ESF.pum rooms at a pressure equal.to or more negative than j
e
.minus 1/4-inch water gauge relative the outside atmosphere while maintaining a vacuum relief flow greater than 2000 cfm and a total system' flow of 5000 cfm i 10%.
4.
Verifying that the heaters dissipate 32 i 3.2 kw when tested in accordance with ANSI N510-1975.
After each complete or partial replacement of a HEPA filter bank by e.
verifying that the HEPA filter banks remove greater than or equal to g
99.95% of the DOP when they are tested in place in accordance with ANSI N510-1975 while operating th9 system at a flow rate of 9000 cfm i 10%.
f.
After each complete or partial replacement of a charcoal adsorber
. bank by verifying that the charcoal adsorbers remove greater than or equal to 99.95% of a halogenated hydrocarbon refrigerant test gas when they are tested in place in accordance with ANSI N510-1975 while operating the systen at a flow rate of 9000 cfm i 10%.
SEQUOYAH - UNIT 2 3/4 7-20 Amendment No. 77, 111 t
4 n.e w
-..w
--ev
m:;
- x.
i m_,,
y rp q
(
'+
i l..,.
i l
.' REFUELING OPERATIONS.
y o3
~* '*
g
~ SURVEILUNCE REQUIREMENTS (Continued)
)
-l L
c.
After every 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of charcoal adsorber cperation by verifying within 31 days after removal that a laboratory analysis of representa-tive carbon sample obtained in accordance with'. Regulatory Position-i C.6.b of Regulatory Guide 1-52, Revision 2, March 1978, meets the laboratory.esting criteria of Regulatory Position C.6.a of Regulatory y
Guide 1.52, Revision 2,< Mar:.h 1978.
d.
.At least once per 18 months by:
- 1..
Verifying that the pressure drop across the con:bined HEPA filters and charcoel adsorber banks is less than 3 inches Water Gauge while operating the filter train at a flow rate of 9000 cfm i 10%.
2.
t l=rifying that the filter train starts on a high radistion signal from the fuel pool radiation monitoring system.
i
- 3..
Verifying that the heaters dissipate 32 1 3.2 kw when tested in accordance with ANSI.N510-1975.
After each complete or partial replacement of a HEPA filter bank by e.-
i 1
verifying that the HEPA filter banks remove greater than or equal to
/
99.95% of the 00P when they are tested in place in accordance with ANSI H510-1975 while operating the systera at a fiow rate of 9000 cfm t
i 10%.
f.'
Afterfeach complete or partial replacement of a charcoal adsorber bank by verifying that the charcoal adsorbers remove greater than or r
equal. to 99.95% of a halogenated hydrocarbon refrigerant test gas when they are tested in place in accordance with ANSI N510-1975 h
while operating the system at a flow rate of 9000 cfm i 10%.
'3; t
)
L i
i
\\,'
i I
i SEQUOYAH - UNIT 2 3/4 9-15 Amendment No. 77, 111 3,.
t
- -..