TD o

UNITED sT4 TEs g

g

[ }h ', ' l NUCLEAR REGULATORY COMMISSION

-i p,

g Og REGION V 0, h' Y/

g 1990 N. CAllFORNIA BOULEVARD U

%e.,,,

o SulTE 202, WALNUT CREEK PLAZA WALNUT CREE K, CALIFORNI A 94596 June 18, 1980 1

Docket tio. 50-312 Sacramento Municipal Utility District P. O. Box 15830 Sacramento, California 95813 Attention: Mr. John J. Mattimoe Assistant General Manager Gentlemen:

EncMsed is IE Bulletin tio. 80-15 which requires action by you with regard to your power reactor facility (ies) and/or fuel facility (ies) with an operating license.

In order to assist the tiRC in evaluating the value/ impact of each Bulletin on licensees, it would be helpful if you would provide an estimate of the manpower expended in conduct of the review and preparation of the report (s) required by the Bulletin. Please estimate separately the manpower associated with corrective actions necessary following identification of problems through the Bulletin.

Should you have any questions regarding this Bulletin or the actions required by you, please contact this office.

Sincerely, yc.lli-R. H. Engelken Director

Enclosures:

1.

IE Bulletin tio. 80-15 2.

List of Recently Issued IE Bulletins cc w/ enclosures:

R. J. Rodriguez, SMUD L. G. Schwieger, SMUD puo70 8 0 //.

0

UNITED STATES SSINS No.:

6820 NUCLEAR REGULATORY COMMISSION Accessions No.:

OFFICE OF IflSPECTION AND ErlFORCEMENT 8005050072 WASHINGTON, D.C.

20555 June 18, 1980 IE Bulletin No. 80-15 POSSIBLE LOSS OF EMERGENCY NOTIFICATION SYSTEM (ENS) WITH LOSS OF OFFSITE POWER In the past year, there have been two occurrences where a loss of off-site power has resulted in a loss of communications between a power reactor facility and the NRC Operations Center via the Emergency Notification System (ENS).

The most recent occurrence was at Indian Point Unit 2 on June 3,1980.

The earlier event occurred at the Davis Besse facility on October 15, 1979 and resulted in the issuance of IE Circular 80-09.

The installation of the ENS requires a station package which operates on 110 VAC.

In some cases, the station package is located at the local telephone company which supplies the required power for normal operation and emergency power for operation during abnormal occurrences, but in many cases, the package is located at the site and is served by on-site power.

In some cases where the station package is served by on-site power, the station package has not been backed up by emergency power.

NRC data indicates that the station packages for each facility are powered in the manner described in the two enclosures.

Actions to be taken by all licensees:

1.

Within 10 days of the date of this Bul'ietin, verify by direct inspection, in conjunction with the appropriate telephone company representative, that the ENS at your facility is powered in the manner described in the two enclosures.

2.

Those facilities.which have station packages requiring on-site power, but which are not connected to a safeguards instrrentation bus which is backed up by batteries and an inverter or equally reliable power supply, shall make necessary modifications and provide such a connection.

3.

All facilities are to develop and conduct a test, within 60 days of.he issuance of this Bulletin, to verify that all extensions of the ENS located at your facility (ies) would remain fully operable from the facility (ies) to the NRC Operations Center in the event of a loss of offsite power to your facility (3s).

This is not intnnand g q p eg g.Q Q y W fryY M e W E G to mean that an actual 2

DUPLICATE LOCUMENT

_) Entire document previously entered into s stem under:

COfc5'Co7J.

ANO No. of pages:

-