Amend 1 to License DPR-51,incorporating Revised Requirements for Monitoring Temp Differential Across Condenser in Tech Specs
ML19326C366
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 11/22/1974
From: Goller K
Office of Nuclear Reactor Regulation
To:
Shared Package
ML19326C364 List:
References
NUDOCS 8004220908
Download: ML19326C366 (5)


Text

.

=

l

. z.

l."

ARKAffSAS POWER A.'lD LIGHT C0P. patly DOCKET f0. 50-313

[

ARKAtlSAS fiUCLEAR OflE, UtlIT 1 AMEilD? TENT TO FACILITY OPERATIllG LICEflSE Amendment lio. 1 LicenseJ1o..DPR-51 1.

The Atomic Energy Comission (the Comission) having found that:

7 A.

The application for anendment by Arkansas Power & Light Company I-(thelicensee)datedNovember 20, 1974, complies with the standards and requirenants of the Atomic Energy Act of 1954, as amended (the Act), and the Comission's rules and regulations L

set forth in 10 CFR Chapter I; S.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Comission, g

C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in conpliance with the Commission's regulations; D.

The issuance of this anendment will not be inimical to the

[

common defense and security or to the health and safety of the public; and F

E.

Prior public notice of this anendment is not required since the anendment does not involve a sianificant hazards consideration.

2.

Accordingly, the license is amended by a c..ange to the Technical Specifications as indicated in the attachment to this license.

anendnent~and Paragraph 2.c.(2) of Facility License fio. CPR-51 is hereby amedded to read as follows:

"(2) Technical Snecifications The Technical Specifications contained in Appendices A and 8, as revised, are hereby incorporated in the license. The licensee shall operate the facility

!=

in accordance with the Technical Specifications as revised by Change No. 1."

c a.e a m.

  • 8
  • o AIC 31e t Krv. 9 53) AICM 0240 W u. a. nov:=

.e e%r paient.%s oresc as n ota.sas. nee

4 mm:nnr:

(5?

m :-

7 n+.sn

[==.

3.

This license anendment is effective as of the date of its issuance.

==3=;

~

FOR THE ATOMIC ENERGY C0i:1ISSION b

t7b-7 Af

?

fj Karl R. Goller Assistant Director for Operating Reactors Directorate of Licensing

'

Attachment:

Change No. 1 to E

'9=1

. Technical Specifications i:';...

p......

Date of Issuance: NOV 2 2 1974

~ L3*

i ms:

1; l k' '

l

ie.

l~

.l L.

-i 9

.l

=-l i

j

    • 'u*

evzuawa 7 -

1 pave w.

j.

re,rg AEC-313 (Re*,9 33) A2C4 0240

  1. u. s. ooven=w re.f PRINT 4h 3 OFFICEB 9974 326.106

s=

. ;.:.:.:g;g 4.-

f.=:[ s y

ATTACHMEllT TO LICEriSE Af1EfiDf1ENT_

.';.'.?

A!'E!!D"EilT fl0.1 TO FACILITY OPERATIflG LICENSE NO. OPR-51 ll:j-lE

=:

="

CIW4GE NO. l'TO TECH!!ICAL SPECIFICATI0tlS ARKANSAS' POWER AND LIGHT COMPAtlY

~

ARKAf{SAS NUCLEAR ONE, UNIT 1 9=

M DOCKET NO. 50-313

/

.Ed:

U Revise Appendix B as follows:

=

Renove pages 2-1 and 2-2 and insert the attached revised pages bearing the

-==

sme nurabers. The changed areas on the revised pages are shown by

ir.;=

E narginal lines.

-m

(.

['e

  • ~ ~ ~..

i._

..p rf..

.Flg:

(_

f..

b-)

i..

(.

Q (A

(;f..

.i

ll,
.g..

e-

?:

p.

.,,.u w e v== = = e

  • I:.-

..r.*

n,m ac.m m..,.m ac.u m

  • ....-~~.~.-.....u............

O

,q

+

ARKANSAS POWER AND LIGHT COMPANY DOCKETNO.50-313 ARKANSAS NUCLEAR ONE, UNIT 1 AMEN 0 MENT TO FACILITY OPERATING LICENSE Amendment No. 1 c

License No. DPR-51 1.

The Atomic Energy Commission (the Commission) having found that:

A.

The application for amendment by Arkansas Power & Light Company i-(thelicensee)datedNovember 20, 1974, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; I

C.

T"ere is reasonable assurance (i) that the activities authorized l

by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D. -The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the a

public; and.

I E.

Prior public notice of this amendment is not required since the amendment does not involve a significant hazards consideration.

2.

Accordingly, the license is, amended by a change to the Technical Specifications as incicated in the attachment to this license amendment and Paragraph 2.c.(2) of Facility License No. DPR-51 is hereby amended to read as foilows:

"(.2) Technical ~Scecificationr The Technical Spacifications contained in Appendices A and B, as revised,'are hereby incorporated in the license.

The licensee shall operate the facility in accordance with the Technical Specifications as revised by Change No. 1."

'I F

Tj

'N 3

. 3.

This license amandment is effective as of the date of its issuance.

FOR THE ATOMIC ENERGY COMMISSION

,r'_

~

Karl R. Galler, Assistant Director for Operating Reactors Directorate of Licensing 0

Attachment:

Change No. 1 to Technical Specifications Date of Issuance: NOV 2 2 1974 t

1 M,*

a y

w.

-y gi y

y-

=w r

e

-w up-

- - - '-T vgy9 v-+,

m ATTACHMENT TO LICENSE AMENDMENT AMENDMENT NO.1 TO FACILITY OPERATING LICENSE NO. DPR-51 CHANGE NO. 1 TO TECHNICAL SPECIFICATIONS ARKANSAS POWER AND LIGHT COMPANY ARKANSAS NUCLEAR ONE, UNIT 1 DOCKET NO. 50-313 Revise Appendix B as follows:

Remove pages 2-1 and 2-2 and insert the attached revised pages bearing the same numbers.

The changed areas on the revised pages are shown by marginal lines.

i T)llPE OE p pce t,(N6

2-1 2.0

. LIMITING CONDITIONS FOR OPERATION t

2.1 Thermal 2.1.1 Maximum AT Across Condenser 3

Objective To limit thermal stress to the aquatic ecosystem by limiting the 1

maximum AT across the condenser during operation.

4-i Specification:

a.

The maximum differential temperature across the condenser shall not exceed 15'F during normal operation with all four circulating l

water pumps in operation.

b.

If one or two circulating water pumps are out of service at any given time the maximum condenser AT shall not exceed 30*F; and Specification 2.1.2 of this Appendix shall be met.

Monitoring Requirement The temperature differential across the condenser shall be monitored every hour utilizing the computer output of the condenser inlet and y

outlet temperature measurements.

The range of these measurements shall be 0-150*F and their accuracy shall be 0.5%.

If the plant computer is inoperable and until the condenser outlet-temperature sensor is relocated in the discharge canal, the condenser AT shall be monitored at least once each shift when the plant y

,is operating at steady state power levels.

The condenser AT shall be i

measured within two (2) hours af ter a change in power level has been.

stabilized 'and at least once each shif t thereafter.

The condenser AT i

shall be determined using measurements at the condenser inlet and in the discharge canal.

Bases Maximum AT's of 15*F with 4 circulating water pumps operating

(%1700 cfs flow). and 30?F -with 2 circulating water pumps. operating will: insure that the limits of the applicable water quality criteria will not be exceeded. The difference in temperature readings of the RTD's at the inlet and outlet of the condensers provides the AT across J

)

the condensers.

Specification 2.1.1'.b allows maintenance to be performed on circulating

' water pumps when the Dardanelle Reservoir ambient temperature is such that Specification :2.1.2 will not be exceeded. Hydraulic model studies have shown that a 30*F AT at 850 cfs circulating waterflow will not result -in adverse' changes in the Dardanelle Reservoir isothenns when

~).

2-2 compared-to the isotherms resulting from a 15'F AT at 1700 cfs except on the surface of the discharge embayment.

2.1.2 Maximum Discharge Temperature Obiective L

To limit thermal stress to the aquatic ecosystem by limiting the plant's maximum discharge water temperature.

Specification The condenser discharge water temperature shall not exceed 105*F for more than two consecutive hours.

If the water temperature exceeds 105*F for two hours an investigation of the situation will be undertaken and corrective action shall be taken to main-l tain the discharge water temperature at 105*F or less. One such corrective action would be a reduction in the plant power level unless there is an emergency need for the lost power. This emergency need would exist when a reduction in power would mean cutting off firm customers.

If monitoring (see below) indicates that the temperature at the mouth of the discharge embayment is j$ 105'F, the plant load will not be reduced.

Monitoring Requirements p

Condenser discharge water temperature shall be monitored every hour

^

utilizing the average of the computer output of the condense: dis-charge RTD readings.

The RTD's have a 0-150*F range and an accuracy of i0.5%.

If the plant computer is inoperable and until the condenser outlet temperature sensor is relocated in the discharge canal, the

- condenser discharge temperature shall be measured at least once each 1

shift.

If the condenser inlet temperature exceeds 85'F with all four circulating water pumps running or 70*F with less than four circulating water pumps running, the condenser outlet temperature shall be monitored every two (2) hours.

If the condenser discharge water temperature exceeds 105*F, plant personnel will be dispatched to the mouth of the discharge embay-ment to monitor the exit temperature from the embayment.

Monitoring of the embayment will continue every two hours as long as the con-denser outlet temperature remains at 105*F.

Bases 4

\\

The 105'F maximum discharge water temperature limit is set to assure that the Dardanelle Reservoir temperature does not exceed t

g-e e--