Corrected Tech Specs 3.7 & 4.7 Re Spray & Sprinkler Sys for Fire Protection Sys
ML19326C180
Person / Time
Site: Arkansas Nuclear 
Issue date: 12/10/1976
From:
ARKANSAS POWER & LIGHT CO.
To:
Shared Package
ML19326C178 List:
References
NUDOCS 8004210674
Download: ML19326C180 (1)


Text

_ _ _ _ _

O

~

NOV o a 1978

_ PLANT SYSTEMS _

SPRAY AND/OR SPRIHKLER SYSTEMS j

LIMITING CONDITION FOR OPERATION 3.7.11.2 The spray and/or sprinkler systems located in the following areas shall be OPERABLE:

I a.

b.

(Plantdependent) c.

APPLICABILITY: All modes ACTIONS:

With a sirsy and/or sprinkler system inoperable establish a continuous fire watch with backup fire suppression equipment in the unprotectedarea(s),and In MODES 1, 2, 3 or 4 restore the system to OPERABLE 1.

status within 7 days or be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

2.

In MODES 5 or 6 restore the system to OPERABLE status within 7 days or prepare and' submit a Special Report to the Comission pursuant to Specification 6.9.2 within the next 10 days outlining the cause o' inoperability and the plans for restoring the system to OPERABLE status.

. SURVEILLANCE REOUIREMENTS The spray and/or spinkler systems shall be demonstrated to be 4.7.11.2 OPERABLE:

At least once per 92 days by cycling each testable a.

valve through one complete cycle.

b.

At least once per 12 months:

1.

By performing a system functional test which includes simulated automatic actunion of the system and c

verifying that the autorstic valves in the flow path actuate to their correct positions.

~ ~ By inspectWof sorav headers to verify their integrity

~

2.

3.

By inspection of each nozzle to verify no blockage.

At least once per 5 years by an air flow test of the open c.

head spray and/or sprinkler system.