Amend 19 to License DPR-51,deleting Boric Acid Mix Tank Temp & Level Channel Tech Spec Surveillance Requirements
ML19326B920
Person / Time
Site: Arkansas Nuclear 
Issue date: 02/18/1977
From: Ziemann D
Office of Nuclear Reactor Regulation
To:
Shared Package
ML19326B916 List:
References
NUDOCS 8004180640
Download: ML19326B920 (4)


Text

__

3

%,*1 o

UNITED STATES j

NUCLEAR REGULATORY COMMisslON g

t,j WASHINGTON, D. C. 20666 lr.

\\...../

ARKANSAS POWER & LIGHT COMPANY DOCKET NO. 50-313 ARKANSAS NUCLEAR ONE - UNIT NO. 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.19 License No. DPR-51 1.

The Nuclear Regulatory Comission (the Comission) has found that:

A.

The application for amendment by Arkansas Power & Light Company (the licensee) dated October 6, 1976, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Comission; C.

There is reasonable assurance (1) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations.and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and Paragraph 2.c(2) of Facility Operating License No.

DPR-51 is hereby amended to read as follows:

8004180

m

' t

, (2) Technical Specifications f

The Technical Specifications contained in Appendices A and B, as revised through Amendment No.19, are hereby incorporated in the license.

The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendnent is effective as of the date of its issuance.

FOR THE NUCLEAR REGULATORY COMMISSION

//'/

/s,u). ww,;.

A G% ~ ~

Dennis L. Ziemann, Chief Operating Reactors Branch #2 Division of Operating Reactors

Attachment:

Changes to the Technical Specifications Date of Issuance: February 18, 1977 9

i I

~

3.

o ATTACHMENT TO LICENSE AMENDMENT NO. 19 FACILITY OPERATING LICENSE NO. DPR-51 DOCKET NO. 50-313 Replace existing page 72 of the Appendix A portion of the Technical Specifications with the attached revised page 72.

The changed area 4

on the' revised page is identified by a marginal line l

e l

t

Table 4.1-1 (Cont'd)

Channel Description Check Test Calibrate Remarks 30.

Decay Heat Removal S(1)(2)

M(1)(3)

R (1)

Includes RCS Pressure Analog System Isolation Valve Channel p

Automatic Closure and Interlock System (2)

Includes CFT Isolation Valve Position (3)

Shall Also Be Tested During-Refueling Shutdown Prior to Re-

/

pressurization at a pressure greater than 300 but less than 420 psig.

31.

Turbine Overspeed Trip NA R

NA Mechanism

$3 32.

Steam Line Break W

Q R

Instrumentation And Control System Logic Test 6 Control Circuits 33.

Diesel Generator M

Q NA Protective Relaying, Starting Interlocks And Circuitry

)

34.

Off-site Power Undervoltage W

R R

And Protective Relaying Interlocks And Circuitry 35.

Borated Water Storage W

NA R

Tank Level Indicator 36.

(Deleted)

-