Notice of Deviation from Insp on 800318-21
ML19323H898
Person / Time
Site: Sequoyah  
Issue date: 04/11/1980
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML19323H880 List:
References
50-327-80-10, 50-328-80-06, 50-328-80-6, NUDOCS 8006170222
Download: ML19323H898 (1)


Text

a-(~)

y APPENDIX A NOTICE OF DEVIATION Tennessee Valley Authority License No. DPR-77 Sequoyah Based on the results of the NRC inspection conducted on March 18-21, 1980, certain of your activities appear to deviate from your commitments co the Commission as indicated below:

A.

TVA's response to NRC question No. 2 on the Fire Protection Program Reeval-uation states that the administrative procedures, controls and fire brigade prograri at Sequoyah would be revised to meet the NRC fire protection guidelines contained in " Nuclear Plant Fire Protection Functional Responsi-bilities, Administrative Controls, and Quality Assurance" doted June 14, 1977.

Contrary to the above, the fire protection administrative procedures do not meet the NRC guidelines in the following areas:

1.

Fire fighting procedures are not provided for all safety-related areas i

as required by Paragraph d of Attachment No. 5 of the NRC fire protec-tion guidelines.

j 2.

Fire brigade classroom instructions and lectures are not conducted for the brigade members each quarter as required by Paragraph 1.0.d of of the NRC fire protection guidelines.

3.

The procedures do not require at least one fire brigade drill per year per shift to be conducted on the back shift as required by Paragraph 3.0.e of Attachment 2 of the NRC fire protection guidelines.

4.

The procedures do not require all wood used within safety-related areas of the plant to be of the pressure fire retardant treated type as required by Paragraph e of Attachment 3 of the NRC fire protection

. guidelines.

B.g, secti.on A.3(b) of TVA's Fire Protection Program Reevaluation states that all valves in the fire protection system will be mechanically locked in their normal position.

.ss,.,

Contrary to the above, none of the interior fire protection control valves were mechanically locked in their normal position.

4 e

8 C0617 0 Q

---