'(1)
VIRGINIA ELECTRIC AND POWER COMPANY DOCKET NO. 50-338 NORTH ANNA POWER STATION, UNIT NO. 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.17 License No. NPF-4 1.
The Nuclear Regulatory Commission (the Commission) has found that:
A.
The application for amendment by the Virginia Electric and Power Coapany (the licensee) dated March 27, 1980 conplies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.
Tha facility will operate in conformity with the applica-tion, the provisions of the Act, and the rules and regula-tions of the Commission; C.
There is reasonable assurance (i) that the activities authorized hy this amendment can be conducted without endargering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.
The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.
i 8005E 00 (2 57$7s
1 2.
Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.D.(2) of Facility Operating License No.
NPF-4 is herehy amended to read as follows:
2.D.(2) Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No.17, are hereby incorporated in the license.
The licensee i
shall operate the facility in accordance with the Technical Specifications.
3.
The license amendment is effective as of the date of issuance.
FOR THE NUCLEAR REGULATORY COMMISSION NM 4
Robert A. Clark, Chief Operating Reactors Branch #3 Division of Licensing
Attachment:
Changes to the Technical Specifications Date of Issuance: May 19, 1980
ATTACHMENT TO LICENSE AMENDMENT NO.17 FACILITY OPERATING LICENSE NO. NPF-4 DOCKET NO. 50-338 Replace the following pages of the Appendix "A" Technical Specifications with the enclosed pages as indicated.
The revised pages are identified by Amendment number and contain vertical lines indicating the area of change. The corresponding overleaf pages are also provided to maintain document completeness.
Pages 6-2 6-3 6-5 6-7 6-8 6-11 6-12 i
i NORTH ANNA-UNIT 1 i
I l
e
6.0 ADMINISTRATIVE CONTROLS 6.1 RESPONSIBILITY 6.1.1 The Station Manager shall be responsible for overall facility operation and shall delegate in writing the succession to this responsibility during his absence.
6.2 ORGANIZATION OFFSITE 6.2.1 The offsite organization for facility management and technical support shall be as shown on Figure 6.2-1.-
FACILITY STAFF 6.2.2 The Facility organization shall be as shown on Figure 6.2-2 and:
a.
Each on duty shift shall be composed of at least the minimum shift crew composition shown in Table 6.2-1.
b.
At least one licensed Operator shall be in the control room when fuel is in the reactor.
c.
At least two licensed Operators shall be present in the control room during reactor start-up, scheduled reactor shutdown and during recovery from reactor trips.
d.
An individual qualified in radiation protection procedures shall be on site when fuel is in the reactor.
e.
All CORE ALTERATIONS shall be directly supervised by either a licensed Senior Reactor Operator or Senior Reactor Operator Limited to Fuel Handling who has no other concurrent responsibilities during this operation.
f.
A Fire Brigade of at least 5 members shall be maintained onsite l
at all times'.
The Fire Brigade shall not include the minimum I
shift crew shown in Table 6.2-1 or any personnel required for other essential functions during a fire emergency.
l
- Fire Brigade composition may be less than the minimum requirement for a period of time not to exceed 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> in order to accommodate unexpected absence of Fire Brigade members provided immediate action is taken to restore the Fire Brigade to within the minimum requirement.
NORTH ANNA - UNIT 1 6-1 Amendment No. 3, 16
ZO N
D E X E CUllVE Z
VICE press 0E NI 2
p POWER
- C
.X
-e H
w EXECullVE MANAGER MANAGER MANAGER LICENSING AND NUCE E AR NUCLEAR QUAllIV ASSURANCE OPERAil0N5 8 MAINT.
TECHNIC AL SE RVICES 575f EM NUCLE AR SAIEIYAND OPE RATING COMMITIE E m
NUCLEAR OIRECTOR DIRE CTOR OIRECTOR DIRE CTOR e
ST All0N OPERAll0N AND SAf ETV EVALUAT60N IECHNICAL ANALYSIS CHEMISIRV ANO N
MANAGERS MAINTEN ANCE SE RVICES ANO CONTROL HE ALIH PHV51CS SI AIION SUPE Rvl50R S4f ETY ENGINEERING i
SE CTION SUFV SE CliON SUVP SECil0N SUPV OPERAll0N AND ADMINisiRAllVE TRAINING MAINTENANCE SUPPORT SE RVICE S
'RESPON518tt FOR CORPOR AIE 5.3E PR0f ECil0N PROGRAM o.
9 tu
- 3 Figure 6 21 Of f aite Organization for Fac6lity Management an<l Technical Fupport 2:
O N
H w
a==D N
O o
Z O
A3
-4C M AN ACE R NUCLEAR OPE RAf t04 & M414E.
3 SUPERV!50R 0 A I
OPE RAI8045 AND MAINIE N A NCE SI AIION NUCEE AR C"
51 A1404 MAN AGE R Z
5AI EIV & OPE RAIING
= = = = = =
COMMilit t R Elsal N T GU AlliV CONIROL E NGINE E R I
I I
I IU#I N' Surf RINIENDENI 1 H AINING 5UPE RINIE mpt N T
$UPE RVISOR IEC t cat DFF R All0 NS SUPE RVt50 R MAINT E N ANCE HE AL1H PHYSICS SE R vlCE S SL E
8 1
.3 56esf I SUPE Rve50R IIA
l
~
SUPE RVISOR SIAff SUPE R VISOR I
CHEMI51RY ADMemt1IR AllVE I
SE nVICE S g',f,'. y I
MI CH ANIC AL ELECIROCAL SUPE Rv450R SUPE RVISOR 5t SUPE Rbe50R l
l
$UPE RV OR
~
AII
~
~
MA 44 AL CONIROL ROOM UL E
51 AI40N b
CON 1ROL ROOM l~
E N GINE E R6N G SIAff Si tuRaiv AS$151 ANI SUPE R VISO R SUPERv&50R g
og nPERAIOR g
I 3
AE0I NO CL AUAlttARY OPEAAIUR L.
Su m iSOR 3'
5Af EIV E NCINE ERING SL-5E450R LICEN!E OL OPE R ATOR'S L6CE NSE
--- COMMuNeCA1:0N5 ZO Figure 6.2 2 Facehty Organaratum - Nosth Anna - Units 1 arul 2 ha M
unend N
~
_ TABLE 6.2-1 MINIMUM SHIFT CREW COMPOSITION #
APPLICABLE MODES LICENSE CATEGORY 1, 2, 3 & 4 5&6 SOL 1
1*
4 OL 2
1 1
Non-Licensed 2
1 l
- Does not include the licensed Senior Reactor Operator or Senior-Reactor Operator Limited to Fuel Handling, supervising CORE ALTERATIONS.
- Shift crew composition (including an individual qualified in radiation protection procedures) may be less than the minimum requirements for a period of time not to exceed 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> in order to accommodate unexpected absence of on duty shift crew members provided immediate action is taken to restore the shift crew composition to within the i
minimum requirements of Table 6.2-1.
NORTH ANNA - UNIT 1 6-4
ADMINISTRATIVE CONTROLS 6.3 FACILITY STAFF QUALIFICATIONS 6.3.1 Each member of the facility staff shall meet or exceed the minimum
)
qualifications of ANSI N18.1-1971 for comparable positions, except for the Supervisor-Health Physics who shall meet or exceed the qualifica-i tions of Regulatory Guide 1.8, September 1975.
6.4 TRAINING 6.4.1 The Station Manager is responsible for ensuring that retraining and replacement training programs for the facility staff are maintained and that such programs meet or exceed the requirements and recommendations of Section 5.5 of ANSI N18.1-1971 and Appendix "A" of 10 CFR Part 55.
i 6.5 REVIEW AND AUDIT 6.5.1 STATION NUCLEAR SAFETY AND OPERATING COMMITTEE (SNSOC)
FUNCTION 6.5.1.1 The SNSOC shall function to advise the Station Manager on all r related to nuclear safety.
COMPOST..sN 6.5.1.2 The SNSOC shall be canposed of the:
Chainnan:
Station Manager Vice-Chairman:
Superintendent - Operations 1
Member:
Superintendent - Maintenance Member:
Superintendent - Technical Services J
ALTERNATES l
6.5.1.3 All alternate members shall be appointed in writing by the SNSOC Chairman to serve on a temporary basis; however, no more than one alternate shall participate as a voting member in SNSOC activities at any one time.
l NORTH ANNA - UNIT l 6-5 Amendment No. 3, JJ, 17
ADMINISTRATIVE CONTROLS MEETING FREQUENCY 6.5.1.4 The SNSOC shall meet at least once per calendar month and as convened by the SNSOC Chairman or his designated alternate.
OUORUM 6.5.1.5 A quorum of the SNSOC shall consist of the Chairman or Vice-Chairman and two members including alternates.
RESPONSIBILITIES 6.5.1.6 The SNSOC shall be responsible for:
Review of 1) all procedures required by Specification 6.8.1 and a.
changes thereto, 2) any other proposed procedures or changes thereto as determined by the Station Manager to affect nuclear safety.
b.
Review of all proposed tests and experiments t'a! affect nuclear safety.
Review of all proposed changes to Appendix ' A" Technical c.
Specifications.
d.
Review of all proposed changes or modificat*ons to plant systems or equipment that affect nuclear safety, Investigation of all violations of the Tectcical Specifications e.
including the preparation and forwarding o reports covering evaluation and recommendations to prevent ecurrence to the Director, Nuclear Operations and to the Chairman of the System Nuclear Safety and Operating Commite.ee.
Review of events requiring 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> writte'i notification to the i
f.
Commission.
Review of facility operations to detect totential nuclear l
g.
safety hazards.
l Amendment No. 11, 17 6-6 NORTH ANNA - UNIT 1
= = -
ADMINISTRATIVE CONTROLS h.
Performance of special reviews, investigations or analyses and reports thereon as requested by the Chairman of the Station Nuclear Safety and Operating Committee.
i.
Review of the Plant Security Plan and implementing procedures and shall submit recommended changes to the Chairman of the Station Nuclear Safety and Operating Committee.
J.
Review of the Emergency Plan and implenenting procedures and shall submit recmunended changes to the Chairman of the Station Nuclear Safety and Operating Committee.
AUTHORITY 6.5.1.7 The SNSOC shall:
a.
Recommend to the Station Manager written approval or disapproval of items considered under 6.5.1.6(a) through (d) above.
b.
Render determinations in writing with regard to whether or not each itsn considered under 6.5.1.6(a) through (e) above constitutes an unreviewed safety question.
Provide written notification within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> to Manager, Nuclear c.
Operations and Maintenance and the Chainnan of the System Nuclear Safety and Operating Committee of disagreement between the SNSOC and the Station Manager; however, the Station Manager shall have responsibility for resolution of such disagreements pursuant to 6.1.1 above.
RECORDS 6.5.1.8 The SNSOC shall maintain written minutes of each meeting and copies shall be provided to the Manager, Nuclear Operations and Main-tenance and Chairman of the System Nuclear Safety and Operating Committee.
6.5.2 SYSTEM NUCLEAR SAFETY AND OPERATING COMMITTEE (SyNSOC)
FUNCTION 6.5.2.1 The SyNS0C shall function to provide independent review and audit of designated activities in the areas of:
I NORTH ANNA - UNIT 1 6-7 Amendment No.17 I
i I
i i
ADMINISTRATIVE CONTROLS a.
Muclear power plant operations b.
Nuclear engineering Chemistry and radiochedistry c.
d.
Metallurgy e.
Instrumentation and control f.
Radiological safety Mechanical and electrical engineering g.
h.
Quality assurance practices i.
Other appropriate fields associated with the unique char-acteristics of the nuclear power plant COMPOSITION 1
6.5.2.2 The SyNSOC shall be composed of the Chairman and four other j
members. Membership shall be composed of the Managers or Directors of the Power Station Engineering, Fuel Resources, Nuclear Operations, and Licensing and Quality Assurance Departments or qualified designees from these departments and a sixth qualified member selected by the five other members. Members of the SyNSOC shall have an academic degree in an engineering or physcial science field and, in addition, shall have a minimum of five years technical experience, of which a minim"m of three years shall be in one or more areas given in Section 6.5.2.1.
ALTERNATES 6.5,2.3 All alternate members shall be appointed in writing by the SyNS0C Chairman to serve on a temporary basis.
CONSULTANTS 6.5.2.4 Consultants shall be utilized as determined by the SyNS0C Chaircan to provide expert advice to the SyNSOC.
NORTH ANNA - UNIT 1 6-8 Amendment No. J7,17
ADMINISTRATIVE CONTROLS g.
Any other area of facility operation considered appropriate by the SyNSOC or the Executive Vice President-Power.
h.
The Station Fire Protection Program and implementing procedures at least once per 24 months.
1.
An independent fire protection and loss prevention program inspection and audit shall be performed at least once per 12 months utilizing either qualified offsite licensee personnel or an outside fire protection firm.
J.
An inspection and audit of the fire protection and loss prevention program shall be performed by a qualified outside fire consultant at least once per 36 months.
AUTHORITY 6.5.2.9 The SyNSOC shall report to and advise the Executive Manager -
'.icensing and Quality Assurance, who shall advise the Executive Vice President - Power on those areas of responsibility specified in Sections 6.5.2.7 and 6.5.2.8.
RECORDS 6.5.2.10 Records of SyNSOC activities shall be prepared, maintained and disseminated as indicated below within 14 working days of each meeting or following completion of the review or audit.
1.
Executive Vice President-Power 2.
Nuclear Power Station Managers 3.
Manager, Nuclear Operations and Maintenance 4.
Members of the SyNSOC 5.
Others that the Chairman of the SyNSOC may designate.
l l
Amendment No. 3, 5,17 MORTH ANNA - UNIT 1 6-11
f ADMINISTRATIVE CONTROLS 6.6 REPORTABLE OCCURRENCE ACTION 6.6.1 The follcwing actions shall be taken for REPORTABLE OCCURRENCES:
a.
The Cannission shall be notified and/or a report submitted pursuant to the requirements of Specification 6.9.
b.
Each REPORTABLE OCCURRENCE requiring 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> notification to the Camnission shall be reviewed by the SNSOC and subnitted to the SyNSOC and the Manager, Nuclear Operations and Maintenance.
6.7 SAFETY LIMIT VIOLATION 6.7.1 The following actions shall be taken in the event a Safety Limjt is violated:
a.
The facility shall be placed in at least HOT STANDBY within one hour.
b.
The Safety Limit violation shall be reported to the Commission, the Manager, Nuclear Operations and Maintenance and to the SyNS0C within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
c.
A Safety L'. nit Violation Report shall be prepared. The report shall be reviewed by the SNSOC. This report shall describe (1) applicable circumstances preceding the violation, (2) effects of the violation upon facility components, systems or structures, and (3) corrective action taken to prevent recurrence.
I d.
The Safety Limit Violation Report shall be submitted to the Commission, the SyNSOC and the Manager, Nuclear Operations l
and Maintenance within 14 days of the violation.
i NORTH ANNA - UNIT 1 6-12 Amendment No. 3, 5, l'
t ATTACHMEtlT TO LICENSE AME!!CMENT NO.17 FACILITY OPERATIflG LICENSE NO. NpF-4 00CXET 10. 50-338 Replace the following pages of the Appendix "B" Tech'nical Soecifications with the enclosed pages as indicated.
The revised pages are identified by Amendment number and contain vertical lines indicating the area of change.
q '/, '
Pages 5-1 5-2
$y c-
/
1 j
e l
NORTH ANNA-UNIT 1 i
Amendment No. 17 1
s
~
5.0 ADMINISTP.ATIVE CONTROLS Administrative controls established below are desced adequate to implement the Environmental Technical Specifications which provide continuing protection to the enviren=ent-5.1 Resoonsibility
~
The responsibility for implementing the Environmental Technical Speci-fications is assigned to the Manager-Nuclear Operations and Maintenance
,at the corporate level and to the Station Manager at the station level l
The Superintendent-0perations shall be responsible for ensuring that the station is operated in accordance with the Limiting Conditions for
' Operation. The Station Supervisor-Health Physics shall be responsible for the radiological environmental surveillance requirements. The
' executive Manager of Environmental Services shall be responsible for
'providing services which will fulfill the non-radiological environ-mental surveillance requirements.
5.2 Oreaniaation.
~
The relatic'nship between the Nuclear Operations l
Depart =ent and the Environ =enthil Services Department is shown in Figure 5.2-1.
3 5 '.3 Review and Audit 5.3.1 Station Nuclear Safety and coeratine Committee (SNSOC)
(
5.3.1.1 Function The SNSOC, as described in Section 6.5.1 of Appendix A of this license
- shall function to advise the Station Manager en matters related to the environmental impact of the station. When the SMSOC is exercising its responsibility for;non-radiological aspects of the ETS, the Station Biologist or his altamate shall be. consulted.
5.b.l.'2
'ResoonsibiTig
~
The SNSOC shall be respcnsible for:
Coordination of the Environmental Technical Specifications with a.
the Safety Technical Specifications (Appendix A).to avoid con-
.flicts and maintain consistency.
i b.
Review of chan5es to the Environmental Technical Specifications and the evaluation of the environmental impact of the cNng.
NOR'IH NETA - UNIT 1 5-1 Amendment No. 17 s
-->m
j Figure 5.2-1 ORGAllI7AT10ll' tilART '
ENVIRollHEllTAl. TECll SPEC IMPLEMENTATION i
bt C
M
! h Ei
-[,.
s EXECUTIVE VICE PRESIDENT FotJER A
.e 1
EXECUTIVE HANAGER EXECUTIVE HANAGER EllVIRONMENTAL, LICEN ALITY SERVICES e..
~
1 I
~~
HANAGER HANAGER i,,
WATER QCli.ITY
__ AIR QUALITY 3
MANAGER DIlECTOR i4
' " ~ ~
wuctE4x QUALITY orERATIons s MAINT.
ASSURAllCE t
hLOIC S. TAIL 0f{.liA.jh0ER OPEilATIONS p
SUPERINTENDENT SUPERINTENDENT t
g l
_0PERATIONS TECllNICAL SERVICES SUPERVISOR s0PEAV150R SUPERVISOR HETEOR0 LOGICAL AIR QUALITY ASSURANCE
~
03lI j.
OPEMTl0NS
_.ORTO?J#G
-M
'SUPERVIS0ft 3raitoit ilEALTil
,' G BIM0cisT.
i
..PilVSJCS ___
I j
- j,
5.3.3.3 Resconsibility The SyNSOC has the responsibility for ensuring that the station is operated in accordance with the requirements of this license and applicable NRC regulations.
5.3.3.4 Authority
~
The. syn 50C sh'all' report to and advise the Executive Manager-Licensing and Quality Assurance, who shall advise the Executive Vice President-Power on those areas relating to the environmental impact of the station.
5.3.3.51 Records
~
.ine SyNSOC shall maintain written minutes of each mee'tiTig and a copy shall be provided to the committee members and the Executive Vice President-Power on those areas relating to the~
{
environmental impact of the station.
5.4
- State and Federal Permits and Certificates The licensee shall comply with' the provisions of the permits and -
certificates issued by the Comonwealth of Virginia to North Anna Power Station under the provisions of Section 401 and 402 of the Federal Water Pollution Control Act, as amended.
5.5 Procedures 5.5.1 Written Procedures Detailed written procedures, including applicable checklists and instructions, shall be prepared and followed for all activities involved in carrying out the Environmental Technical Specifications as defined in Sections 5.5.2, 5.5.3, and 5.5.4 below.
Procedures shall include sampling, data recording and storage, instrument calibration, measure ments-and analyses, and actions to be taken when limits are approached or exceeded. Testing frequency of any alarm shall be included.
These frequencies shall be detennined from experience with similar instru-ments in similar environments and frcm manufacturer's technical manuals.
~
5.5.2 Operating Procedures Plant standard operating procedures shall include provisions, in addition to the procedures specified in Section 5.5.1, to ensure that all plant systems and components are operated in compliance with the Limiting Conditions of Operations established as pa.>t of the Environ-l menf:al Technical Specifications.
NORTH ANNA-UNIT 1 5-5 Amendment No. 17
. - - -. - -