ML19323F944
| ML19323F944 | |
| Person / Time | |
|---|---|
| Site: | Midland |
| Issue date: | 05/22/1980 |
| From: | Schwencer A Office of Nuclear Reactor Regulation |
| To: | Howell S CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.) |
| References | |
| NUDOCS 8005300019 | |
| Download: ML19323F944 (5) | |
Text
.
4cP "Ecuq'o UNITED STATES
+
'g'g NUCLEAR REGULATORY COMMISSION E \\*
,a b)#(
WA$mNGTON, D. C. 20555
, y;M /,... C g
\\-
.MY 2 21980
+....
Docket Nos.: 50-329/330 Mr. S. H. Howell Vice President Consumers Power Company 212 West Michigan Avenue Jackson, Michigan 49201
Dear Mr. Howell:
SUBJECT:
STAFF POSITION FOR INSPECTION AND TESTING OF REMAINING SAFETY RELATED STRUCTURAL CONCRETE INSTALLATION We have reviewed your response to our request 421.6 provided by FSAR Revision 26 regarding certain exceptions to Regulatory Guide 1.94, entitled
" Supplementary Quality Assurance Requirements for Installation, Inspection, and Testing of Structural Concrete and Structural Steel During the Construc-tion Phase of Nuclear Power Plants". Your exceptions regard the location at which concrete test samples are taken, and the frequency at which the i
correlation strength test sampling is performed. The enclosure provides our position for these matters for all remaining safety related structural concrete installations, and in particular, that associated with any future modifications or additions to Q-listed structural concrete presently in place.
You are requested to advise us within seven days of receipt of this letter as to your intentions regarding conformance to our position and to amend your FSAR responses and construction procedures within 20 days from this receipt.
Contact us should you require any clarification of this position.
Sincerely, WAW't-
,/
A. Schwencer, Acting Chief Licensing Branch No. 3 Division of Licensing
Enclosure:
As stated cc: See next page l
8005300ofq
I 4
Censurer s Power Corrany ces:
Michael 1. Miller, Esq.
Isham, Lincoln & Beale Suite 4200 One First National Plaza Chicago, Illinois 60603 Judd L. Bacon, Esq.
Panaging Attorney Consumers Power Company 212 West Michigan Avenue Jackson, Michigan 49201 Mr. Paul A. Perry Secretary Consumers Power Company 212 W. Michigan Avenue Jackson, Michigan 49201 Myron M. Cherry, Esq.
One IBM Flaza Chicago, Illinois 60611 Mary Sinclair 5711 Summerset Drive Midland, Michigan 48640 Frank J. Kelley, Esq.
Attorney General State of Michigan Environmental Protection Division 720 law Building Lansing, Michigan 48913 P
Mr. Wendell Marshall Route 10 Midland, Michigan 48640 Grant J. Merritt, Esq.
ThomDson, Nielsen, Klaverkamp & James 4444 105 Center 80 South Eighth Street Minneapolis, Minnesota 55402 Mr. Don van Farewe, Chief Division of Radiological Health Departrent of Public Health P. 0... Box 33035 Lansing, Michigan 48909 F
4 Consumers Peser Corrany ces (centinued):
Resident inscector/ Midland NPS c/o U.S. Nuclear Regulatory Commission P. O. Box 1927 Midland, Michigan 48640 William J. Scanlon, Esq.
2034 Pauline Boulevard Ann Arbor, Michigan 48103 Commander, Naval Sur face Weapons Center ATTN:
P. C. Huang G-402 White Oak Silver Spring, Maryland 20910 Mr. L. J. Auge, Manager Facility Design Engineering Energy Technology Engineering Center P. O. Box 1449 Canoga Park, California 91304 Mr. William Lawhead V. S. Corps of Engineers NCEED - T 477 Michigan Avenue i
7th Floor Detroit, Michigan 48226 I
e i
4 995 J
9 e
e
--+am.
i ENCLOSURE 421.0 QUALITY ASSURANCE BRANCH 421.7 We have reviewed your response to Request 421.6 in FSAR Revision 26 and (17.1.1) find your proposed exceptions to Regulatory Guide 1.94, April 1975, (RSP)
" Supplementary Quality A:;surance Requirements for Installation, Inspec-tion, and Testing of Structural Concrete and Structural Steel During the Construction Phase of Nuclear Power Plants" are not justified.
It is our position that for all remaining and future modification activities related to the subject matter of this guide, you should comply with the present quality control / assurance requirements developed by the industry, which have been adopted in the professional community. Specifically, your exceptions can be classified into two categories, (1) the point at which the samples of concrete should be taken, and (2) the frequency at 4
which the correlation samples are taken:
1.
Location of Sample Section 6.11 of ANSI N45.2.51978 states that test samples should be taken at the placement point, unless concrete is pumped from the delivery point to the placement point in which case correlation tests of air content, slump and temperature should be performed.
The delivery point is defined in Section 1.4 of the same standard and states that... " delivery point and the mixing point are con-sidered coincident when:
(1) the delivery point is not more than a distance of two miles and an average time of one-half hour in transit from the mixing point, and (2) the delivered concrete connences to be placed within an average time of one-half hour from the cime the transporting vehicle arrives at the delivery point".
l l
FSAR Section 7.1.1.13 states that " Compressive strength test cylinders are cast from representative samples taken from the dis-charge of the batch plant stationary mixer or the discharge chute of the truck mixer, when applicable"... without stating how the sampling point is related to the delivery point.
We require that you take any further samples according to the requirements of the generally accepted standards, i.e., at the point of placement or point of delivery, as defined above, in which case appropriate correlation samples, shall be taken.
2.
Frequency of Correlation Strength Testing ANSI N45.2.5 1978, Section 6.11 states that unless the mixing and the delivery points are considered coincident, correlation strength I
tests are required. Frequency of such sampling, taken at the de-livery point should be each 500 cubic yards of concrete or twice 1
each week, whichever provides the greater number of samples.
Your response to Request 421.6 in FSAR Revision 26 states that the Q-concrete is placed in such a small quantity that once-a-week test-ing frequency becomes the controlling criterion. We find that l
2 because of the small quantity of concrete placed, the frequency of testing should be increased to at least twice a week according to the requirements of the standard.
Revise your FSAR discussion and contruction procedures to reflect confonnance with our above positions.
t t
l
)
i s
1
-