Forwards IE Circular 80-12, Valve-Shaft-To-Actuator Key May Fall Out of Place When Mounted Below Horizontal Axis. No Written Response Required
ML19323F630
Person / Time
Site: Yankee Rowe
Issue date: 05/14/1980
From: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Kay J
YANKEE ATOMIC ELECTRIC CO.
References
NUDOCS 8005290249
Download: ML19323F630 (1)


Text

5C

  1. o, UNITED STATES 7.

NUCLEAR REGULATORY COMMISSION REGION I o,

g 631 PARK WENUE

,e KING OF PRUSSIA, PENNSYLVANIA 19406 May 14, 1980 Docket No. 50-29 Yankee Atomic Electric Company ATTN:

Mr. James A. Kay Senior Engineer - Licensing 25 Research Drive Westborough, Massachusetts 01581 Gentlemen:

The enclosed IE Circular No. 80-12, " Valve-Shaft-To-Actuator Key May Fall Out of Place When Mounted Below Horizontal Axis," is forwarded to you for infor-mation.

No written response is required.

If you desire additional infor-mation regarding this matter, please contact this office.

Sincerely, a

oyce H. Grier Director

Enclosures:

~

1.

IE Circular No. 80-12 with Attachments 2.

List of Recently Issued IE Circulars CONTACT:

0. L. Caphton (215-337-5346) i cc w/encis:

H. Autio, Plant Superintendent J. E. Tribble, President j

8006290249

ENCLOSURE 1 SSINS No.: 6830 UNITED STATES Accession No.:

NUCLEAR REGULATORY COMMISSION 8005050052 0FFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 IF Circular No. 80-12 Date:

May 14, 1980 Page 1 of 2 VALVE-SHAFT-TO-ACTUATOR KEY MAY FALL 0U1 0F PLACE WHEN MOUNTED BELOW HORIZONTAL AXIS Description of Circumstances:

Tennesdte Valley Authority has identified and reported to the NRC a non-conformance on a Bettis Robot-Arm actuator installed on a Pratt butterfly valve at the Sequoyah nuclear plant.

It is reporte1 (ref attached 10 CFR 50.55(e) report) that a valve became inoperable whan ti> valve-shaft-to-actuator key fell out of place.

It is further noted that 1 e orientation of this valve assembly was such that the 5

operator was on the bottom of the valve (below the horizontal axis).

The Pratt butterfly valve furnished with Bettis actuatcr is designed with a press-fit keyway connection valve / actuator.

We believe other manufacturers' connections may be of similar construction and therefore subject to this failure mode.

On May 1,1980, Pratt Company sent letters to their customers who have these connections (attached list).

They recommended that their customers review their installation of such connections, and if the keyway is oriented below horizontal, make one o'l the following field modifications:

1.

Add a spacer bushing, or shim plate to fill the void between the top of the shaft and the indicating plate on trae actuator.

2.

Locally upset the end of the valve shaft in the area of the keyway using a hand punch in such a way that the key could not work loose.

3.

Install new keys of longer length which extend above the end of the valve shaft whereby the key is up to the actuator plate and could not slip down if inverted.

Recommended Action for Licensee Consideration:

l l

We request that all plants make the i

connections similar to the above des DUPLICATE DOCUMENT

[

not supplied by those particular ma are susceptible to failure, one of Entire document previcusly appropriate action should be taken entered into system under: