Discusses Potential Design Deficiencies in Bypass,Override & Reset Circuits of Engineered Safety Features.Sys Level Annunciation of Overridden Status Should Be Provided for Every Safety Sys Imparted When Override Is Active
ML19323F423
Person / Time
Site: Summer 
Issue date: 05/14/1980
From: Schwencer A
Office of Nuclear Reactor Regulation
To: Crews E
SOUTH CAROLINA ELECTRIC & GAS CO.
References
NUDOCS 8005290013
Download: ML19323F423 (5)


Text

__

Tit p%

,1 9[g UNITED STATES

+

y 'f g

NUCLEAR REGULATORY COMMISSION g

l wasHWGTO N. D. C. 20SS5 MAY 141980 Docket No.:

50-395 Mr. E. H. Crews, Jr.

Vice President and Group Executive Engineering and Construction South Carolina Electric and Gas Company P. O. Box 764 Columbia, South Carolina 29218

Dear Mr. Crews:

SUBJECT:

POTENTIAL DESIGN DEFICIENCIES IN BYPASS, OVERRIDE, AND RESET CIRCUITS OF ENGINEERED SAFETY FEATURES i

Discussion Of Deficiencies Several instances have been reported where automatic closure of the containment ventilation / purge valves would not have occurred because the safety actuation signals were either manually overriden or bypassed (blocked) during normal plant operations.

In addition, a related design deficiency with regard to the resetting of engineered safety feature actuation signals has been found at several operating facilities where, upon the reset of an ESF signal, certain safety related equipment would return to its non-safety mode.

Specifically, on June 25, 1978, Northeast Nuclear Energy Company discovered that intermittent containment purge operations had been conducted at Millstone Unit No. 2 with the safety actuation signals to redundant containment purge isolation valves (48 inch butterfly valves) manually overriden and inoperable. The isola-tion signals which are required to automatically close the purge valves to assure containment integrity were manually overriden to allow purging of containment with a high radiation signal present.

The manual override circuitry designed by the plant's architect / engineer defeated not only the high radiation signal but also all other isolation signals to these valves.

To manually override a safety actuation signal, the operator cycles the valve control switch to the closed oosition and then to the open position.

This action energized a relay which blocked the safety signal and allowed manual operation independent of any safety actuation signal. This circuitry was designed to permit reopening of certain valves after an accident to allow manual operation of required safety equipment.

)

t Bogge og

MAY 141c80 86

.4 On September 8,1978, the staff was advised that, as a matter of routine, Salem Unit No. 1 had been venting the containment through the containment ventilation system valves to reduce pressure.

In certain instances this i

venting has occurred with the containment high particulate radiation monitor isolation signal to the purge and pressttre-vacuum relief valves overridden.

The override of this containment isolation signal was accomplished by re-setting the train A and B reset buttons. Under these circumstances, six valves in the containment vent and purge systems could be opened with the radiation isolation signal present. This override was performed after verifying that the actual containment particulate levels were acceptable for venting. The licensee, after further investigation of this practice, determined that the reset of the particulate radiation monitor alarm also overrides the containment isolation signal to the purge valves such that the purge valves would not have automatically closed on an emergency core cooling system (ECCS)safetyinjectionsignal.

A related design deficiency was discovered during a review of system operation following a recent unit trip and subsequent safety injection at North Anna No.1.

Specifically, it was found that certain equipment important to safety (for example, control room habitability system dampers) would return to its non-safety mode following the reset of an ESF signal.

In addition, many utilities do not have safety grade radiation monitors to initiata containment isolation.

Safety Significance The overriding of certain containment ventilation isolation signals could also bypass other safety actuation signals and thus prevent valve closure when the other isolation signals are present. Although such designs may be acceptable, and even necessary, to accomplish certain reactor functions, they are generally unacceptable where they result in the unnecessary bypassing of safety actuation signals. Where such bypassing is also inadvertent, a more serious situation is created especially where there is no bypass indication system to alert the operator.

Where the resetting of ESF actuation signals, such as safety injection, directly causes equipment important to safety to return to its non-safety mode, protec-tive actions of the affected systems could be prematurely negated when the associated actuation signal is reset. Prompt operator action would be required to assure that the necessary equipment is returned to its emergency mode.

The use of a non-safety grade monitor to initiate containment isolation could seriously degrade the reliability of the isolation system.

Staff Position It is our position that, in addition to other applicable criteria, the following should be satisified for all operating license applications currently under review:

6 a

Mr. E. H. Crews, Jr. MAY 141980 i

1) The overriding of one type of safety actuation signal (e.g., parti-culate radiation) should not cause the blocking of any other type of safety actuation signal (e.g., iodine radiation, reactor pressure) for those valves that have no function other than containment isolation.
2) Physical features (e.g., key lock switches) should be provided to en-sure adequate administrative controls.
3) A system level annunciation of the overridden status should be provided for every safety system impacted when any override is active.

(See Regulatory Guide 1.47).

4) The following diverse signals should be provided to initiate isolation of the containment purge / ventilation system: containment high radiation, safety injection actuation, and containment high pressure (where con-tainment high pressure is not a portion of. safety injection actuation).
5) The instrumentation systems provided to initiate containment purge ventila-tion isolation should be designed and qualified to Class lE criteria.

6)

The overriding or resetting of the ESF actuation signal should not cause any equipment to chaage position.

Accordingly, you are requested to review your protection system design to deter-mine its degree of conformance to these criteria.

You should report the results i

of your review to us sixty days after receipt of this letter, describing any i

departures from the criteria and the corrective actions to be implemented.

Design departures for which no corrective ~ action is planned should be justified.

Please advise if you have any questions on this matter.

Sincerely, 1

A. Schwencer, Acting Chief Licensing Branch No. 3 Division of Licensing cc: See next page lhe following definitions are given for clarity.

Override: The signal is still present, and it is blocked in order to perform a function contrary to the signal.

Reset:

The signal has come and gone, and the circuit is being cleared in order to return it to the normal condition.

-m,-

,w--

,w~

Mr. E. H. Crews, Jr., Vice President and Group Executive - Engineering and Construction South Carolina Electric & Gas Company P. O. Box 764 Columbia, South Carolina 29218 cc: Mr. H. T. Babb General Manager - Nuclear Operations and System Planning South Car 01:na Electric & Gas Company P. O. Box 764 Columbia, South Carolina 29218 G. H. Fischer, Esq.

Vice President & Group Executive South Carolina Electric & Gas Company P. O. Box 764 Columbia, South Carolina 29218 Mr. William C. Mescher President & Chief Executive Officer South Carolina Public Service Authority 223 North Live Oak Drive Moncks Corner, South Carolina 29461 Mr. William A. Williams, Jr.

Vice President South Carolina Public Service Authority 223 North Live Oak Drive

.Moncks Corner, South Carelina 29461 Wallace S. Murphy, Esq.

General Counsel South Carolina Public Service Authority 223 North Live Oak Drive Moncks Corner, South Car 01ina 29461 Troy B. Conner, Jr., Esq.

Conner, Moore & Corber 1747 Pennsylvania Avenue, N. W.

Washington, D. C.

20006 Mr. Mark B. Whitaker, Jr.

Manager, Nuclear Licensing South Carolina Electric & Gas Company P. O. Box 764 Columbia, South Carolina 29218 Mr. O. W. Dixon Group Manager, Production Engineering South Carolina Electric & Gas Company o

P. O. Box 764 Columbia, South Carolina 29218

t Mr. E. H. Crews, Jr.

4 cc: Mr. Brett Allen Bursey Route 1 Box 93C Little Mountain, South Carolina 29076 i

i Resident Inspcctor/Sumer Power Station c/o U. S. Nuclear Regulatory Comission P. O. Box 1047 Irmo, South Carolina 29063 O

i e

  • %e 1

4 4,

4 J

+

4 0$

~

i 1

- -, -,