ML19323E938

From kanterella
Jump to navigation Jump to search
Responds to Re Apparently Differing Info Provided by NRC in Washington,Dc & by NRC in Middletown,Pa.Forwards Sequence of Events & Notification for 800211 Event
ML19323E938
Person / Time
Site: Crane 
Issue date: 05/02/1980
From: Dircks W
NRC OFFICE OF THE EXECUTIVE DIRECTOR FOR OPERATIONS (EDO)
To: Ertel A
HOUSE OF REP.
Shared Package
ML19323E939 List:
References
NUDOCS 8005280127
Download: ML19323E938 (4)


Text

.

1 l*

[

Docket No. 50-320 l

The Honorable Allen E. Ertel United States House of Representatives Washington, D. C.

20515

Dear Congressman Ertel:

I am writing in response to your letter of February 25, 1980, to Chairman Ahearne in which you expressed your concern over apparently differing information given to you by the NRC in Washington and that given you by the NRC office in Middletown during your visit on February 14. You further indicated that the Middletown office has refused to provide information to the public concerning the status of events at the plant. This resulted in your reconnendation tut the Middletown office have daily updates on the conditions at Three Mile Island available for review by the interested public.

l We have not been able to identify what information given to you by the NRC in l

Washington was in conflict with that given to you at the NRC office in Middletown.

However, we agree with you that differing sources and presentation of factual material does lead to confusion and anxiety, and we have taken steps to assure that such occurrences are not repeated.

In an attenpt to provide you with an accurate account of the February 11 incident, I have had the NRC staff review the pertinent records relating to this event. Attached to this letter is a sunnary of the sequence of events and notifications which occurred on February ll,1980, during this incident.

I trust this information will eliminate any misinformation about this incident which may still exist.

With regard to your concern that information about the plant status is not readily available for public review at the Middletown office, we have taken steps to assure that such information will be available. Daily plant status sheets are available at the Middletown office for public inspection and posting of radiation monitoring results has been initiated. All of this information is open to the public and may be reviewed without going through the Freedom of Information Act procedures. We believe that your reference to disclosure of information via the l

00l OFFICE h.

SURNAMEk.

DATE NQC FORM 318 (9 76) NRCM O240 DU.S. GOVERNMENT PRINTING OFFICE: 1979 289-369

Congressman Allen E. Ertel 2

Freedom of Information Act procedures sas based on a discussion between members of the HRC staff and the public in which various NRC procedures for dissemination of information to the public were reviewed, including the Freedom of Infomation Act.

Please be sure that both we and EPA will make every effort to assure that information on plant status, radiation releases to the environment and results of radiation ~ monitoring measure-ments in locations surrounding the plant are made available to the public.

I trust this information is responsive to the concerns expressed in your letter.

Sincerely.

(Signed) William j,Diltkij William J. Dircks Acting Executive Director for Operations

Enclosure:

Sequence of Events and Hotification for 2/11/80 Event l

i l

l

[

l SEE PREVIOUS YELLOW FOR CONCURRENCES OrnCcyT,g,.Suppp,r,t,

,,E.00,.,,

. 0.CA,

[ 47,nkman WJD,i rc ks,

DBri SURNAME 780 47 /80

,57,,780,,,

DATE,,,,

N *.C FO R M 318 (9-76) NRCM 0240 U U.S. GOVERNMENT PRINTING OFFICER 1979 289 369

f ATTACHMENT SEQUENCE 0F EVENTS AND NOTIFICATION FOR 2/11/80 EVENT TIME EVENT 1220 Initial conditions "B" makeup pump in operation maintaining reactor coolant system pressure while in natural circulation cooling mode.

1220 Started "A" makeup pump to test pump operability.

1221 Received 'iow discharge pressure alarm on "B" makeup pump.

1237 Stopped "A" makeup pump.

Makeup tank level was dropping.

1240 Calculated leak rate based on level drop - approximately 9 gpm.

1250 Shift Supervisor ordered evacuation of Auxiliary Building.

NRC/TMI staff members dispatched to Unit 2, based on public address announcement.

1258 Shift Supervisor declared a local emergency.

1310 Increased radiation levels reported on radiation air monitors on the 281 foot elevation of the Auxiliary Building.

1310 Local NRC/TMI staff notified.

1315 Licensee senior management and connunications personnel notified of local emergency.

1320 NRC Senior Resident Inspector briefed of situation by the licensee's Emergency Director and Shift Supervisor.

1320 J. T. Collins (NRC) discussed the information available to the NRC approx.

with the Pennsylvania Bureau of Radiatior. Protection.

At that time, the final effluent monitors did not show any noticeable increases from readings taken previous to the event.

However, several hours after the incident was over, the licensee made an examination of these monitors' strip charts and then calculated that approximately 300 mci of noble gases had been released.

At no time were any of these releases detected off-site.

Once this information was available from the licensee, it was transmitted to the Pennsylvania Bureau of Radiation Protection.

e,

TIME EVENT 1340 Licensee noLified the Pennsylvania Department of Environmental Resou rces.

It was discovered that they had already been notified by the NRC.

1428 First press release issued by Communication Services.

1520 Pennsylvania Department of Environbntal Resources notified of updated plant status.

1700 Second press release issued.

aporox.

2030 Final press release issued.

I 1