MCGUIRE NUCLEAR STATION REPORT NO.-
SD-369/80-05
_ REPORT DATE:
May 15, 1980 FACillTY:
McGuire Nuclear Station - Unit i IDENTIFICATION OF DEFICIENCY:
Cutler-Hammer Relay Contact Blocks - Oversized Contact Compression Springs INITIAL REPORT:
On April 15, 1980, John Rausch, NRC Region II, Atlanta, Georgia was notified of the deficiency by J. R. Wells, T. C. McMeekin, J. E. Thomas and B. M. Rice of Duke Power Company, Charlotte, North Carolina.
SUPPLIER AND/OR COMPONEffT:
The components identified as having the deficiency are Cutler-Hammer relay i
contact blocks Types 023MF, and D26MF with date codes of 775, 875, 975, and 1075.
The date codes represent July, August, September, and October manufacturing runs in 1975.
DESCRIPTION OF DEFICIENCY:
During testing of the McGuire Unit I diesel generator sequencer, a Cutler-1 Hammer relay failed causing a safety-related circuit not to function as designed.
An investigation of the failure revealed that the relay coil operated properly; however, a malfunction did occur in the thi-d contact block of the relay. The contact block in question was a Type 026MF from a batch labeled 975.
Preliminary Indications were that the failure of the walls of the contact channel carrier. contacts to close resulted from the contact co Seven other 026MF contact blocks were taken apart and inspected.
Of the seven, two contact blocks also from a batch labeled 975 exhibited binding characteristics similar to the failed block The other five blocks were from different batches and did not exhibit binding characteristics.
Eight contact blocks (the failed block plus the other seven blocks inspected) were forwarded to Cutler-Hammer for evaluation.
Cutler-Hammer subsequently confirmed that the malfunction was caused by the contact compression' spring binding on the channel carrier wall. The binding was determined by Cutler-Hammer to be caused by oversized contact compression springs.
has traced the oversized springs to a shipment received on JulyCut l er-Hamme r 23, 1975 from the spring supplier.
Some of the springs in this shipment were found to be slightly oversized according to manufacturing rpecifications.
The oversized s,
=
8005210 M
a
-2 DESCRIPTION OF DEFICIENCY: (Con ' t. )
springs were determined to have been used in the manufacture of Type D26MF, D23MF, and 021MF contact block bearing the date code of 775, 875, 975, and 1075.
_ ANALYSIS OF SAFETY IMPLICATIONS:
The Cutler-Hanmer 026MF and D23MF contact blocks are used in various safety-related applications at McGuire. As stated previously, the failure mechanism of the contact blocks results in contacts potentially not closing when the relay 1s energized.
Depending on the specific application of the relay, the failure of 1
the contact ~ block could result in the loss of a safety function (s).
CORRECTIVE ACTION:
Approximately 218 Cutler-Hammer relays equipped with D26MF and 023MF contact blocks have been identified as installed in safety-related circuits on McGuire Unit 1.
(Note that Type D21MF contact blocks are not used at McGuire).
These contact blocks will be inspected and all blocks with date codes 775, 875, 975, and 1075 will be replaced. This corrective action is schaduled for completion prior to McGuire Unit I fuel loading.
9 9
.