ML19322E073
| ML19322E073 | |
| Person / Time | |
|---|---|
| Site: | Crane |
| Issue date: | 03/07/1980 |
| From: | Grier B NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I) |
| To: | Arnold R METROPOLITAN EDISON CO. |
| References | |
| NUDOCS 8003180037 | |
| Download: ML19322E073 (1) | |
Text
-.
neu f%
o o
UNITED STATES
[
NUCLEAR REGULATORY COMMISSION 3
E REGION I O
631 PARK AVENUE 4
KING OF PRUSSIA, PENNSYLVANIA 19406
- ,o March 7, 1980 Docket Nos. 50-289 50-320 Metropolitan Edison Company ATTN:
Mr. R. C. Arnold Senior Vice President 100 Interpace Parkway Parsippany, New Jersey 07054 Gentlemen:
The enclosed IE Information Notice No. 80-09, Possible Occupational Health Hazard Associated With Closed Cooling Systems for Operating Power Plants, is forwarded to you for information.
No written response is required.
Should you have any questions regarding this mitter, please contact this office.
Sincerely, Boyce H. Grier Director
Enclosures:
1.
IE Informatior Notice No. 80-09 2.
List of Recently Issued IE Information Notices CONTACT:
R. J. Bores (215-337-5260) cc w/encls:
J. G. Herbein, Vice President Nuclear Operations E. G. Wallace, Licensing Manager R. J. Toole, Manager, TMI-1 W. E. Potts, Radiological Controls Manager, TMI-1 R. W. Heward, Radiological Controls Manager, TMI-2 J. J. Colitz, Plant Engineering Manager, TMI-1 J. J. Barton, Manager Site Operations, TMI-2 B. Elam, Plant Engineering Manager, TMI-2 L. W. Harding, Supervisor of Licensing R. F. Wilson, Director, TMI-2 I. R. Finfrock, Jr.
R. W. Conrad J. B. Lieberman, Esquire G. F. Trowbridge, Esquire Ms. Mary V. Southard, Chairperson, Citizens for a Safe Environment k
8oo.9ranos,1
ENCLOSURE 1 SSINS:
6870 Accession No.:
UNITED STATES 7912190681 NUCLEAR REGULATORY COMMISSION O!FICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.
20555 IE Information Notice No. 80-09 Date:
March 7, 1980 Page 1 of 1 POSSIBLE OCCUPATIONAL HEALTH HAZARD ASSOCIATED WITH CLOSED COOLING SYSTEMS FOR OPERATING POWER PLANTS As a result of information that the causative agent for meningoencephalitis, the amoeba Naeglaria fowleri, had been found in warm water ponds in Florida and Texas where two fatalities were reported, NRC initiated a study by Oak Ridge National Laboratory on the occurrence of Naeglaria in power plants with closed cycle cooling systems.
For seven power stations examined (6 fossil, 1 nuclear), this study confirmed the presence of pathogenic Naeglaria at three plants including the nuclear plant (Dresden).
Recently, Northern States Power Company (NSP), while monitoring the Prairie Island Nuclear Generating Plant closed cooling system for the amoeba, did identify the presence of Naeglaria.
Although the Minnesota Department of Health does not consider the existence of the organism to be a public health threat, it was recognized as a possible occupatinnal health hazard.
Plant perscnnel were instructed to wear rubber gloves when coming into contact with the circulating water and to wear respirators when working in the area of the cooling towers.
In November 1979, NSP conducted a special chlorination program at Prairie Island that was designed by Dr. Richard Tyndall of Oak Ridge to eradicate this organism.
Chlorine concentrations in the circulating water system was raised to 2.0 mg/l (measured as free chlorine) for a period of six hours to destroy both the amoebae and its encysted form.
This program also included dechlorination prior to discharge and intensive monitoring to document chlorine concentrations, the impacts of chlorinated cooling tower draft and sampling to determine the efficacy of the special chlorination program in destroying Naeglaria.
Preliminary results indicate that the program was successful in reducing the number of organisms present by two to three orders of magnitude.,
It is recognized that there have been no reported cases of meningoencephalitis reported among power plant personnel to date; however, the seriousness of the disease (if contracted) and the confirmed presence of Naeglaria at four plants, leads us to inform all licensees with closed cycle cooling water systems of the potential occupational hazard and advise that they take appropriate action.
This Information Notice is provided as an early notification of a possibly significant matter.
It is expected that recipients will review the informa-tion for possible applicablility to their facilities.
No specific action or i
response is requested at this time.
If further NRC evaluations so indicate, an IE Circular, Bulletin or NRR Generic Letter will be issued to recommend or request specific licensee actions.
If you have any questions regarding the matter, please contact the Director of the appropriate NRC Regional Office.
A
ENCLOSURE 2 IE Information Notice No. 80-09 Date:
March 7, 1980 Page 1 of 1 RECENTLY ISSUED IE INFORMATION NOTICES Information Subject Date Issued to Notice No.
Issued 79-33 Improper Closure of Primary 12/21/79 All Power Reactor Faci-Containment Access Hatches lities with an Operating License (OL) or Construc-tion Permit (CP) 79-34 Inadequate Design of Safety-12/31/79 All Power Reactor Faci-Related Heat Exchangers lities with an OL or CP 79-35 Control of Maintenance 12/31/79 All Power Reactor Faci-and Essential Equipment lities with an OL or CP 79-36 Computer Code Defect in 12/31/79 All Power Reactor Faci-Stress Analysis of Piping lities with an OL or CP Elbow 79-37 Cracking in Low Presssure 12/31/79 All Power Reactor Faci-Turbine Discs lities with an OL or CP 80-01 Fuel Handling Events 1/4/80 All Power Reactor Faci-lities with an OL or CP 80-02 8X8R Water Rod Lower 1/25/80 All BWR Facilities with End Plug Wear an OL or CP 80-03 Main Turbine Electro-1/31/80 All Power Reactor Faci '
hydraulic Control System lities with an OL or CP 80-04 BWR Fuel Exposure in Excess 2/4/80 All BWR Facilities with of Limits an OL or CP 80-05 Chloride Contamination of 2/8/80 All Power Reactor Faci-Safety Related Piping and lities with an OL or CP Components and applicants for a CP 80-06 Notification of Signif-2/27/80 All Power Reactor Faci-icant Events lities with an OL and applicant for OL 80-07 Pump Fatigue Cracking 2/29/80 All Power Reactor Faci-lities with an OL or CP 80-08 The States Company Sliding 3/7/80 All Power Reactor Faci-Link Electrical Terminal lities with an OL or CP l
Block l
l