ML19322B538

From kanterella
Jump to navigation Jump to search
Responds to & Bulletin 72-03, Limitorque Valve Operator Failures. Torque Switch Torsion Spring Replaced in Cited Valve Operators.Replacement Program Completed by Late 1972.Sys W/Limitorque Valve Operators Listed
ML19322B538
Person / Time
Site: Oconee  
Issue date: 01/19/1973
From: Thies A
DUKE POWER CO.
To: Jennifer Davis
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
IEB-72-03, IEB-72-3, NUDOCS 7912040567
Download: ML19322B538 (2)


Text

7 DLxz power COMPm Powza Puzz.ones 4aa Sourn Caunca Srazzr, CuAar.orrz, N. C. assos A. C. THIES P. o. Box 2178 sameO= vics passeosar P#OOUCTION AND TRANSes499tOae January 19, 1973 Mr. John G. Davis, Director Atomic Energy Commission Directorate of Regulatory Operations Region II - Suite 818 230 Peachtree Street, Northwest Atlanta, Georgia 30303 Re: RO:II:50-269,-270, -287

Dear Mr. Davis:

c Please refer to your letter of December 4, 1972 which transmitted Directorate of Regulatory Operations Bulletin No. 72-3, "Limitorque Valve

/

Operator Failures." As requested by this bulletin, we are providing the following information regarding valve operators at the Oconee Nuclear Station.

A total of 502 limitorque operators of the models and vintage described by Bulletin 72-3 were installed at Oconee Nucleat Station, Units 1-2-3.

The systems in which valves with these operator.s.were installed are j

listed below.

The torque switch torsion spring was replaced in each of these operators. This replacement program was completed late in 1972.

Atrruiary Steam System Heater Drain System Reactor Building Spray System High' Pressure Injection System Component Cooling System Iow Pressure Injection System Condensate System Low Pressure Service Water System Core Flooding System Liquid Waste Disposal System Coolant Storage System Main Steam System

~

Condenser Circulating Water System Penetution Room System

~

Demineralized Water System

~

Reacror Coolant System Feedwater System Steam Seal Header System Gaseous Waste Disposal System Steam Drain System Very truly yours,

.,,t*

A. C. Thies ACT:vr 1r 91304og7

p.

i e,

~1 i

Letter from Duke Power Company, A. C. Thies, dated January 19, 1973 DISTRIBUTION:

MAR 6 1973 J. B. Henderson, RO J. G. Keppler, R0 RO:HQ (4)

Directoratem f Licensing (4)

ErhDRCentralFiles PDR Local PDR NSIC OIS, OR State 6

0 l

.a i

A 4

.1

. I

'l

  • - ame* *

.=en enunum w ====en s wee,-

,.3,

-.,-.,.w

.,, y,ep w,. 7 w.....g

---