O O

55.$=L. LW cswL r=1e E r.

/

'y ~., ~ m u j

/

METRO?OLITAN EDISON COMPANY. sw c.ure crww.m= ummes-4re r,

POST OFFICE GOX 460 A88COLETOWN PENNSYLVANtA 17057

~ TELEPHONE 717 9 54 4CM1 Farch 20,1977 D@@M O

Pr. J. P. O' Reilly Directorate or Peculate y OperationJ_...

p[}

,' D _@"'

g {Q d

Faqion I U

3 Nuclear Fegalatory Comission 631 Park Avenue King of Prussia,.Eas:nsylvania 19406 Cberatina 1.icense DPP.-50 Docket 50-289 Subiect: Feoortable Occurrence fb. 77-05/4P Cear Mr. O'Fe111y:

This telegra' is to confirn the telecon between Mr. A. N. Fasano (Region I - TAC) and Pr. G. A. Kunder (T'il-1 Svoervisor of Operations) at 1140 hours0.0132 days <br />0.317 hours <br />0.00188 weeks <br />4.3377e-4 months <br /> on 20 Parch 1977.

j l

A violation of the Environmental Technical Specification ~ 2.1.b(2) occurred in that during the Routine Peactor Plant Cooldewn on 03/19/77, the river water differential te perature was chanced by rore than 20 in any cne hour.

0 The river water 6 was beino raintained at 0 F t;o to the tire the Decay Feat Penoval Syster. was olated inservice at 2100 hours0.0243 days <br />0.583 hours <br />0.00347 weeks <br />7.9905e-4 months <br />. As the Decay Fest Femval System was placed in service the river water discharge tero-erature began to increase causing an increase in the river water 6.

Since the Pechanical Craft Cooling Tower was operating at its full available '

capacity, i rediate steos were taken to reduce the Cecay Feat Fenoval beat load which in turn decreased the river water IT rate of chance. The 0

river water 6 rate of change reached a rtaxirm of 3.5 F/hr. which exceeded the specification.

The incident will be revie%ed and the results of the evaluation and any corrective action taken will be reported in the 14 day recort.

Very truly yours, G G 64{

r li f

(J. 'J. Coli tt Unit I Sucerintendent Three Mile Island t;uclear Station JJC:11r 7910250 3'7 ol $