ML19321A509
| ML19321A509 | |
| Person / Time | |
|---|---|
| Site: | South Texas |
| Issue date: | 07/17/1980 |
| From: | Oprea G HOUSTON LIGHTING & POWER CO. |
| To: | |
| References | |
| ST-HL-AE-496, NUDOCS 8007230540 | |
| Download: ML19321A509 (4) | |
Text
-
The Light company u_,,_ u se,o_ m s_17eo a_,,_.m.,
zooi nim 2s.e2,i s
July 17, 1980 ST-HL-AE-496 SFN: V-0530 Mr. Karl Seyfrit Director, Regien IV Nuclear Regulatory Commission 611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76102
Dear Mr. Seyfrit:
South Texas Project Units 1&2 Docket Nos. STN 50-498, STN 50-499 Interim Report on Material Control of ASTM A-325 Structural Steel Bolts On June 17, 1980, pursuant to 10CFR50.55(e), Houston Lighting & Power Comphny notified your office of a potentially reportable deficiency concerning material control of ASTM A-325 structural steel bolts.
Improper segregation and identification of Category I and non-Categcry I ASTM A-325 structural steel bolts in the field resulted in bolts procured under a non-Category I specification being used for Category I applications. This condition has been documented in Nonconformance Report S-C4377.
The inadequate material control concern was first identified during an investigation of an apparent premature inventory shortage of Category I structural steel bolts. This revealed the misapplication of non-Category I bolts. However, most of these bolts were supplied with certified material test reports (CMTR) which would allow the material traceability necessary for Category I application.
The following actions will be taken in order to resolve this potentially reportable deficiency:
1)
Release of structural steel bolts for Category I applications has been halted under Stop Work #S-22 until full material traceability is established.
- 2) Documentation for installed bolts in Category I applications is being identified and located.
A Qf 8007230 @ D
=
won ughting & Power compar!y July 17, 1980 ST-HL-AE-496 SFN: V-0530 Page 2
- 3) Material control methods and procedures are being evaluated for neces-sary modifications and improvements.
4). Documentation and Quality requirements contained in Category I Structural Steel and Miscellaneous Steel specifications are being reassessed to determine the adequacy of the bolts installed.
Sufficient information is not currently available to determine if this is a reportable deficiency under 10CFR50.55(e). However, at this time there is no indication that the installed bolts pose a potential safety hazard. An update to the status of this concern will be submitted to your office by August 27, 1980.
Should there be any questions, please contact Mr. S. S. Rodgers at (713) 676-7953.
Very truly yours,
- 2. w. opy G. W. Oprea, Jr.
Executive Vice President PLW/did
Houston Lighdng & Power Company ST-HL-AE-496 SFN: V-0530 Page 3 cc:
D. G Barker C. L. McNeese H. R. Dean R. L. Waldrop G. B. Painter A. J. Granger R. A. Frazar M. D. Schwarz (Baker & Botts)
R. Gordon Gooch (Baker & Botts)
J. R. Newman (Lowenstein, Newman, Reis, Axelrad & Toll)
Director, Office of Inspection & Enforcement Nuclear Regulatory Commission Washington, D. C. 20555 1
M. L. Borchelt Executive Vice President Central Power & Light Company P. O. Box 2121 Corpus Christi, Texas 7B403 R. L. Range Central Power & Light Company P. O. Box 2121 Corpus Christi, Texas 78403 R. L. Hancock Director of Electrical Utilities City of Austin P.O. Box 1088 Austin, Texas 78767 M. C. Nitcholas City of Austin P.O. Box 1088 Austin, Texas 78767 J. B. Poston Assistant General Manager of Operations City Public Service Board P. O. Box 1771 San Antonio, Texas 78296 A. vonRosenberg City Public Service Board
- 9. 0. Box 1771 San Antonio, Texas 78296
Houston b hting & pour compary 5
ST-HL-AE-496 Page 4 Charles Bechoefer Esquire Chairman, Atomic Safety & Licensing Board U.S. Nuclear Regulatory Commission Washington, D.C. 20555 Dr. James C. Lamb, III 313 Woodhaven Road Chapel Hill, North Carolina 27514 Dr. Emmeth A. Luebke Atomic Safety & Licensing Commission U.S. Nuclear Regulatory Commission Washington, D.C.20555 l
Steven A. Sinkin Esquire 116 Villita Street i
San Antonio, Texas 78205 Citizens for Equitable Utilities c/o Ms. Peggy Buchorn l
Route 1, Box 432 Brazoria, Texas 77422
)
l Richard W. Lowerre, Esquire Assistant Attorney General for the State of Texas P. O. Box 12548 Capitol Station Austin, Texas 78711 Henry J. McGurren Esquire Hearing Attorney Office of the Executive Legal Director U.S. Nuclear Regulatory Commission Washington, D.C. 20555 l
t