Forwards Response to NRC 800625 Request for Addl Info Re Secondary Water Chemistry Monitoring Program.Info Provides Administrative Control Rept Parameters
ML19320D455
Person / Time
Site: McGuire, Mcguire  
Issue date: 07/14/1980
From: Parker W
DUKE POWER CO.
To: Harold Denton, Youngblood B
Office of Nuclear Reactor Regulation
References
NUDOCS 8007210385
Download: ML19320D455 (2)


Text

,_-

4.Il.Y

'Duxz power COMPANY Powen Butt.ntxo 4c2 Socin Cacacu Srazzr. CnAnz.orre, N. C. asa4a WI L LI AM Q. PA R M E R J R.

July 14, 1980 v.ce Pacs +cca' re ca-o.c:^ac 7c.

Steau Paoswcwoa 37 3-4c a s Mr. Harold R.'Denton, Director Office 'of Nuclear Reactor Regulation U.S.. Nuclear' Regulatory Comnission Washington, DC 20555 Attention:

Mr. B. J. Youngblood, Chief Licensing Projects Branch No. 1

Subject:

McGuire Nuclear Station Secondary Water Chemistry Monitoring and Control

Dear Mr. Denton:

As requested by members of your staff on June 25, 1980, please find attached additional information on the McGuire Nuclear Station program to monitor and control secondary water chemistry supplementing my

-letters of October 25, 1979, May 23, 1980, and June 19, 1980. The information provides the administrative control for reporting out

~

. of specification chemical parameters to appropriate management personnel in order to assure that administrative guidelines for limiting operation are =et.

V.'y truly yours,,

C.

e. / y e

, William O. Parker, Jr. s J LJB/sch Attachment i

l ll n.

8007s'10SS5

w MCGUIRE NUCLEAR STATION Reporting Out-of-Specification Chemical Parameters In all situations involving one or more chemical parameters being out of specification as dr. tined in Section 3.8 of the Chemistry Manual, one of the following is t' be notified within one hour of the original determina-tion of the out at specification chemical parameter:

Note:

-Attempt to notify in order given until one person is contacted.

On Weekdays:

1.

Ch2mistry Supervisor for the Area involved 2.

Chemistry Coordinator (either one) 3.

Station Chemist 4.

Any other Station Chamistry or Radwaste Supervisor 5.

Superintendent of Technical Services On Weekends and Holidays:

1.

On-Call ~ Chemistry Staff personnel 2.

Chemistry Coordinator (either one) 3.

Station Chemist 4.

Any other Chemistry or Radwaste Supervisor 5.

Superintendent of Technical Services

~

When chemical parameters have been verified out of specification (as described in Section 3.8.5 of the Chemist Manual) within systems operated by the Opera-tions Group, the Shift Supervisor or Control Room is to be notified by the Chemistry Supervisor for the Area (Primary, Secondary, etc.) when present, or the Tachnician or Specialist on shift.

If an electrowriter is in use, notifi-cation is to be accomplished by that means.

If an electrowriter is not in use, the Shif t Supervisor or Control Room is to be notified by phone. When notifi-cation is by, phone, the date, time, person contacted, and data reported to him are to be logged in the Laboratory Problem (Events) Book.

e