e TABLE I SECONDARY CONTAINMENT LEAK RATE TEST DATA TEST DATE: APRIL 23, 1980 TEST CONDITIONS Wind Direction North Wind Velocity 10 MPH Barometric Pressure (outside Rx. Bldg.)
29.27" Hg Outside Temperature 430 F.
Inside Temperature 750 F.
BASE READING (0 Flow)
Reactor Bldg. Atmosphere A P ("H O) 2 N.
.75 E.
.08 W.
.80 S.
.28 "A"
SGTS PERFORMANCE System Flow Rate 2700 cfm Reactor Bldg. AtmosphereAP ("H O) 2 N.
-1.16 E.
.35 W.
-1.12 S.
.58 Secondary Containment Vacuum
. 30" H 0 2
"B" SGTS PERFORMANCE System Flow Rate 2800 cfm Reactor Bldg. Atmosphere AP ("H 0) 2 N.
-1.14 E.
.38 W.
-1.12 S.
.58 Secondary Containment Vacuum
.33"H 0 2
80 07180M
-