Final Deficiency Rept Re Const QA Audit.Concrete Placement Evaluated & Found Acceptable.Inspectors Instructed in Requirements of General Const Spec
ML19320C551
Person / Time
Site: Yellow Creek  
Issue date: 07/10/1980
From:
TENNESSEE VALLEY AUTHORITY
To:
Shared Package
ML19320C548 List:
References
YC-C-80-05, YC-C-80-5, NUDOCS 8007170358
Download: ML19320C551 (1)


Text

.

L p

s

~/

ENCIASURE YELLOW CREEK NUCLEAR PLANT UNITS 1 AND 2 CONSTRUCTION QA AUDII YC-C-80-05 10 CFR 50.55(e)

FINAL REPORT Description of Deficiency Observation of the placement and compaction of Concrete Pour A2-D1 took place during the first shift of, April 22, 1980.

It was found, during the auditor's presence th'at the subject pour was not being placed and compacted in accordance with the requirements of TVA General Construction Specification G-2, nor was the QC inspection being performed in accordance with the requirements of QCI C-201.

Approximately thirty-two (32) QCIR's were written in 1979 for honey-comb in concrete. Twenty-two (22) QCIR's have been written to date in 1980 for honeycomb in concrete.

Some of these QCIR's listed more than one concrete pour with honeycomb.

Since improper compaction is the major, if not sole, cause of honeycomb, it appears that improper compaction of concrete is a generic problem at Yellow Creek Nuclear Plant.

Safety Implications The failure to properly install concrete could result in weakening of safety related structures to the point the structures could fail during an event that would challenge their integrity.

This failure could result in failure of safety equipment and/or failure of structural integrity of the building and loss of containment function of the building.

Corrective Action The concrete placement questioned by the auditors was evaluated and found acceptable.

Inspectors have been instructed in the requirements of General Construction Specification G-2 and admonished to be more assertive in seeing that all requirements of G-2 are met.

Honeycomb is an inherent defect in the placement of concrete. The increase in the frequency of honeycomb for 1980 is due to the increase in wall pours which contained significantly more embedded items. The auditor based his decision to indicate honeycomb as significant solely on the increase in frequency for the early part of 1980.

Our analysis of all the honeycomb indicates that the increase could have been expected and was not excessive.