OPERATING DATA REPORT i
DOCKET NO. 050-298 DATE July 1.
1980 COMPLETED BY P.
L. Ballinger TELEPHONE 402-825-3811 OPERATING STATUS Notes
- 1. Unit Name:
Cooper Nuclear Station June 1980
- 2. Reporting Penod.
- 3. Licensed Thermal Power (MWt):
2381 836
- 4. Nameplate Rating (Gross MWe):
l 778 S. Design Electrical Rating (Net MWe):
660
- 6. Mhan Dependable Capacity (Gross MWe):
^"
- 7. Max %um Dependable Capacity (Net MWe):
- 8. If Cha.w Occur in Capacity Ratings (items Number 3 Through 7) Since Last Report. Give Reasons:
Turbin tnodifications to remove cracked turbine discs and to replace turbine blades and discs with pressure controlling baffle plates resulted in reduced generating capacity
- 9. Power Level To Which Restricted,if Any (Net MWe):
- 10. Reasons For Restrictions.lf Any:
This Month Yr to.Date Cumulative 720.0 4.367.0 52.608.0 i1. Hours la Reporting Period 658.3 2,105.3 43,342.6
- 12. Number Of Hon Reactor Was Critical 0.0 o,o-o,o
- 13. Reactor Reserve 2,hutdown Hours
- 14. Hours Generator On-Line 616.7 2.054.4 42.530.0
- 15. Unit Reserve Shutdown Hours 0.0 0.0 0.0
- 16. Gross Thermal Energy Generated (MWH) 1 911,nAA n go qa g.,_
nn A71 a1nA
- 17. Gross Electrical Energy Generated (MWH) 329.828.0._.
1.34. _.3.d 25.886.871.0
- 18. Net Electrical Energy Generated (MWH) 315,966.0 1,297 ;94.0 24,955,371.0
- 19. Unit Service Factor 85 1 _
47.0 80.8
- 20. Unit Availability Factor 85.7 47.0 80.8 69.1 46.8 74.7
- 21. Unit Capacity Factor (Using MDC Net) 56.4 38,2 61.0
- 22. Unit Capacity Factor (Using DER Net) 0.9 1.4 4.4
- 23. Unit Forced Outage Rate
- 24. Shutdowns Scheduled Over Next 6 Months (Type. Date,and Duration of Each t:
None
- 25. If Shut Down At End Of Report Period. Estimated Date of Startup:
- 26. Units in Test Status iPrior to Commercial Operation):
Ferecast Achieved INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION 80070803 a -
7b com
.e---
+
t----
,---4..
AVERAGE DAILY UNIT POWER LEVEL 050-298 DOCKET NO.
UillT Cooper Nuclear Station DATE July 1, 1980 COMPLETED BY P. L. Ballinner TELEPHONE 402-825-3811 MONTH 3"=
DAY AVERAGE DAILY POWER LEVEL DAY
.tVERAGE DAILY POWER LEVEL (MWe-Net)
(MWe-Net) 1 0
37 575 2
n 18 555 0
3 19 546 4
3 20 547 37 5
21 541 6
W 22 374 7
324 23 500 355 8
24 529 9
443 25 621 10 547 26 626 11 585 27 621 12 559 23 615 13 566 29 59R 566 14 10 601 15 553 3g 16 556 r
INS 1 RUCTIONS On this format. list the average dady unit power levelin MWe Net for each day in the reporting month. Compute to the nearest whole megawatt.
I' (9/77) i l
050-298 DOCKETNO.
UNITSilU1 DOWNS AND POWER REDUCTIONS UNIT NAME
('nnpor helanr Station DATE July 1, 1980 COMPLETED BY
.P.
I. Ballinger REPORT MONTil June TELEPHONE 402 825-3811
~h Licensee
,E r, b.
.! E 3
.h Y k Cause & Connective k
3 Action to No.
Daic g
3g g
jg5 Event u?
fU
$E 5
j5g Report #
'E U Pievent Recurrence 6
80-5 800301 S
55.8 C
2 NA NA NA 1980 Refueling and Maintenance Outage 80-6 800604 F
5.9 A
3 NA NA NA Reactor scram from low reactor water level following reactor feedwater pump overspeed trip. Malfunctioning reactor feed pump controller problem was corrected and reactor returned to operation.
80-7 800622 S
NA H
NA NA NA NA Power was reduced to allow adjustment of the control rod pattern.
I 2
3 4
F: Forted Reason:
Method:
Edibit G -Instmetions S: E
'uted A-Equipment Failure (Explain) 1-Manual for Picpa ation of Data B-Maintenance of Test 2-Manual Scram.
Eni y Sheets fo 1.icensee 3 Automatic Scram.
Event Repost ILER) File INtlRIG C-Refueling D-Regulatory Restriction 4-Other (Explain) 0161)
E-Operator Training & Ucense Exam; nation F-Administrative 5
Exhibit I - Same Source G-Operational Error (Explain) 19/77)
Il-Other (Explain)
~ -
COOPER NUCL' EAR STATION OPERATIONS NARRATIVE JUNE 1980 Startup for Cycle 6 began on June 3, 1980 and first reactor criticality occurred at 0748 hours0.00866 days <br />0.208 hours <br />0.00124 weeks <br />2.84614e-4 months <br />. Maintenance work on the turbine resulted in removal of 12 rows of low pressure turbine blades.
Pressure controlling baffle plates were installed in the turbine to allow continued operation until replacement turbine rotors can be obtained from manufacturer. A reduced electrical generating capacity of approximately 140 MWe has resulted from removal of the 12 rows of turbine blades.
Reactor scram occurred at 2349 hours0.0272 days <br />0.653 hours <br />0.00388 weeks <br />8.937945e-4 months <br />, June 4,1980 resulting from reactor low water level scram signal. Reactor feed pump tripped during the main turbine overspeed trip testing. A malfunctioning RFP con-troller allowed the feed pump turbine speed to increase to trip level.
Feedwater flow was lost to the reactor resulting in a low water level scram. Control problem with feed pump corrected and returned reactor to criticality at 0542 hours0.00627 days <br />0.151 hours <br />8.96164e-4 weeks <br />2.06231e-4 months <br />, June 5,1980.
Plant operated the remainder of June with no unscheduled power reduction and with only one scheduled power reduction on June 22 to allow for adjustment of the control rod pattern.
i l